![ABB ACH580-34 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/abb/ach580-34/ach580-34_quick-installation-manual_2532007.webp)
EN – Quick installation guide 7
EN
DA
DE
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
Default I/O connections
The default I/O connections of the HVAC default configuration are shown below.
Wire sizes: 0.14…2.5 mm
2
(26...16 AWG): All terminals.
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft).
Total load capacity of the Auxiliary voltage 24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Run status
Fault status
Damper actuator
max.
500 ohm
1…10 kohm
X1
1
SCR
Reference voltage and analog inputs and outputs
2
AI1
Signal cable shield (screen)
3
AGND
Output frequency/speed reference
: 0…10 V
4
+10V
Analog input circuit common
5
AI2
Reference voltage 10 V DC
6
AGND
Actual feedback:
0…20 mA
7
AO1
Analog input circuit common
8
AO2
Output frequency:
0…10 V
9
AGND
Motor current:
0…20 mA
X2 & X3
Analog output circuit common
10
+24V
Aux. voltage output and programmable digital inputs
11
DGND
Aux. voltage 24 V DC, max. 250 mA
12
DCOM
Aux. voltage output common
13
DI1
Digital input common for all
14
DI2
15
Not configured
DI3
Stop (0) / Start (1)
16
DI4
Constant frequency/speed selection
17
DI5
18
Not configured
DI6
Start interlock 1 (1 = allow start)
Not configured
19
RO1C
X6, X7, X8
Relay
outputs
20
RO1A
21
RO1B
22
Damper control
250 V AC / 30 V DC
2 A
RO2C
23
RO2A
24
RO2B
25
Running
250 V AC / 30 V DC
2 A
RO3C
26
RO3A
27
X5
RO3B
Fault (-1)
250 V AC / 30 V DC
2 A
29
B+
Embedded fieldbus
30
A-
31
DGND
S4
Embedded fieldbus, EFB (EIA-485)
TERM
S5
BIAS
Termination switch
X4
34
Safe torque off
OUT1
Bias resistors switch
35
OUT2
36
SGND
37
IN1
38
IN2
X10
40
24 V AC/DC
24 V AC/DC+ in
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
7KH
Safe torque off function
LQ WKH
$&+
KDUGZDUHPDQXDO
$;'>(QJOLVK@
.
41
24 V AC/DC- in
Ext. 24V AC/DC input to power up the control unit
when the main supply is disconnected.
Содержание ACH580-34
Страница 1: ... ABB DRIVES FOR HVAC ACH580 34 drive modules Quick installation guide English 3 EN ...
Страница 8: ...8 EN Quick installation guide EN DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 22: ...www abb com drives www abb com drivespartners 3AXD50000424627 Rev C MUL 2019 09 12 Contact us ...