Technical data
35
Technical data
RBIP-01
Enclosure:
Mounting:
Into the option slot on the control board of the drive.
Degree of protection:
IP20
Power supply:
12...26 V DC / AC, 200 mA, internal fuse
Resistors:
• Network bias resistors, 560 ohms (DIP switches)
• Network termination resistor, 120 ohms (DIP switch)
Weight:
<100 g
Ambient temperature range:
0...45 °C, 32…113 °F
Ambient humidity range:
20...80 percent relative humidity, non-
condensing
95 mm
34 mm
20
mm
62 mm
RBIP-01
BACnet ROUTER
CHASSIS
X1
BACnet/IP
123
4567
8
ON
X2
POWER
X3
MS/TP
S1
1=Network bias
2=Network bias
3=Termination