ACS/ACC/ACP 604/607 Drives
ACx=ACS/ACC/ACP
A-1
Appendix A – ACS/ACC/ACP 604/607 Technical Data
IEC Ratings
The IEC ratings ratings for ACx 604 and ACx 607 with 50 Hz and 60 Hz
supplies are below. ACx = ACS/ACC/ACP. The ACx 607 is housed in a
Drives-MNS cabinet. The ACx 604 is to be installed in a cabinet by the
user. The 690 V series and 2 x R8 and 2 x R9 frame sizes are not
available for ACP 600.
See next page for symbols.
Frequency
Converter
Type
Normal Use
Heavy-duty Use
Frame
Type
Duty Cycle
1/10 min
Duty Cycle
1/10 min
Duty Cycle
1)
2/15 s
I
2N
9/10min
[A]
I
2Nmax
1/10min
[A]
S
N
[kVA]
P
N
[kW]
P
N
[HP]
I
2hd
9/10min
[A]
I
2hdmax
1/10min
[A]
I
2hd
13/15s
[A]
I
2hdmax
2/15s
[A]
S
hd
[kVA]
P
hd
[kW]
P
hd
[HP]
Three-phase supply voltage 380 V, 400 V or 415 V
ACx 604/607-0100-3
147
162
100
75
100
112
168
112
224
70
55
75
R7
ACx 604/607-0120-3
178
196
120
90
125
147
221
147
294
100
75
100
ACx 604/607-0140-3
216
238
140
110
150
178
267
178
356
120
90
125
R8
ACx 604/607-0170-3
260
286
170
132
200
216
324
216
432
140
110
150
ACx 604/607-0210-3
316
348
210
160
250
260
390
260
520
170
132
200
ACx 604/607-0260-3
395
435
260
200
300
316
474
316
632
210
160
250
R9
ACx 604/607-0320-3
480
528
320
250
350
395
593
395
790
260
200
300
ACx 604/607-0400-3
600
661
400
315
400
494
741
494
988
320
250
350
2xR8
ACx 604/607-0490-3
751
827
490
400
500
600
901
600
1200
400
315
400
2xR9
ACx 604/607-0610-3
912
1003
610
500
600
751
1127
751
1502
490
400
500
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACx 604/607-0120-5
135
149
120
90
100
112
168
112
224
100
75
75
R7
ACx 604/607-0140-5
164
180
140
110
125
135
203
135
270
120
90
100
ACx 604/607-0170-5
200
220
170
132
150
164
246
164
328
140
110
125
R8
ACx 604/607-0210-5
240
264
210
160
200
200
300
200
400
170
132
150
ACx 604/607-0260-5
300
330
260
200
250
240
360
240
480
210
160
200
ACx 604/607-0320-5
365
402
320
250
300
300
450
300
600
260
200
250
R9
ACx 604/607-0400-5
460
506
400
315
350
365
548
365
730
320
250
300
ACx 604/607-0490-5
570
627
490
400
500
456
684
456
912
400
315
400
2xR8
ACx 604/607-0610-5
694
764
610
500
600
570
855
570
1140
490
400
500
2xR9
ACx 604/607-0760-5
874
961
760
630
700
694
1041
694
1388
610
500
600
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
ACx 604/607-0100-6
88
97
100
75
100
65
98
65
98
70
55
75
R7
ACx 604/607-0120-6
105
116
120
90
125
88
132
88
132
100
75
100
ACx 604/607-0140-6
127
140
140
110
150
105
158
105
158
120
90
125
R8
ACx 604/607-0170-6
150
165
170
132
150
127
191
127
191
140
110
150
ACx 604/607-0210-6
179
197
210
160
200
150
225
150
225
170
132
150
ACx 604/607-0260-6
225
248
260
200
250
179
269
179
269
210
160
200
ACx 604/607-0320-6
265
292
320
250
300
225
338
225
338
260
200
250
R9
ACx 604/607-0400-6
351
386
400
315
350
265
398
265
398
320
250
300
ACx 604/607-0490-6
428
470
490
400
450
340
511
340
510
400
315
350
2 x R8
ACx 604/607-0610-6
504
555
610
500
500
428
642
428
642
490
400
450
2 x R9
ACx 604/607-0760-6
667
734
760
630
700
504
756
504
756
610
500
500
Содержание ACC 604
Страница 2: ......
Страница 4: ......
Страница 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 81: ......