1.5 Terminal units (AC500 standard)
Hot swap
System requirements for hot swapping of I/O modules:
–
Types of terminal units that support hot swapping of I/O modules have the
appendix TU5xx-H.
–
I/O modules as of index F0.
The following I/O bus masters support hot swapping of attached I/O modules:
–
Communication interface modules CI5xx as of index F0.
–
Processor modules PM56xx-2ETH with firmware version as of V3.2.0.
NOTICE!
Risk of damage to I/O modules!
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
Conditions for hot swapping
–
Digital outputs are not under load.
–
Input/output voltages above safety extra low voltage/
protective extra low voltages (SELV/PELV) are switched off.
–
Modules are completely plugged on the terminal unit with both snap fit
engaged before switching on loads or input/output voltage.
Hot swap
Further information about hot swap: .
1.5.1 TU507-ETH and TU508-ETH for Ethernet communication interface modules
● TU507-ETH, Ethernet terminal unit, 24 V DC, screw terminals
● TU508-ETH, Ethernet terminal unit, 24 V DC, spring terminals
● TU508-ETH-XC, Ethernet terminal unit, 24 V DC, spring terminals, XC version
Device specifications
Terminal units (AC500 standard) > TU507-ETH and TU508-ETH for Ethernet communication interface modules
2022/01/31
3ADR010278, 3, en_US
122