Page 9
Infinity S_Dual V_old_QSG
Version 4.0
© 2021 ABB. All rights reserved.
Information: Battery Monitoring Connections
Battery Monitoring is accomplished with a
“
Daisy Chained
”
series of probes connected to J2. The Probes monitor
battery temperature and voltage (ES771 required to monitor voltage). Bolt the Probe under the
“
–
”
terminal
connector hardware; NOT under the connecting lug.
Ordering
Code
Descriptions
CC109142980
QS873A Thermal Probe
CC848817024
B
10’
controller to thermal probe wireset
CC109157434
B
20’
controller to thermal probe wireset
CC848822560
C
1’
thermal probe to thermal probe wireset
848719803
C
5’
thermal probe to thermal probe wireset
CC848822321
C
10’
thermal probe to thermal probe wireset
Temperature Measurement
Temperature and Voltage Measurement
Ordering
Code
Descriptions
108958422
ES771A Voltage Monitor Card
CC848791517
D 2 ½
’
ES771A to probe wireset
CC848797290
D
6’
ES771A to probe wireset
848719829
D
10’
ES771A to probe wireset
CC848791500
G
4’
ES771A to ES771A or controller wireset
848652947
G
10’
ES771A to ES771A or controller wireset
Molex mini
-
fit SR
-
Style, No Plug
CC848822420
(2) 15 ft., 3X8AWG
848710711
(2) 10 ft., 3X8AWG
CC848830522
(2) 4 ft., 3X8AWG
CC848773515
15 ft., 10AWG SO Cord
CC848906586
10 ft., 8AWG, SO Cord
Information: AC Cord Options
Information: Controller Default Voltage Settings
Step 9 –
Configure Controller
Verify and edit controller basic configuration parameters per site engineering instructions.
Refer to Galaxy Pulsar Plus Product Manual for additional information.
Parameter
Range
Valve
-
Reg
(Default)
Flooded
NiCd
Rectifier Float Selective High Voltage Shutdown
-
50 to
-
60V
58.50
58.50
58.50
High Float Voltage Major Alarm
-
50 to
-
60V
57.00
57.00
57.00
High Float Voltage Minor Alarm
-
50 to
-
60V
56.00
56.00
56.00
Rectifier/System Float Voltage
-
42 to
-
56.5V
54.48
52.08
54.40
Battery on Discharge Float Alarm
-
46 to
-
55V
51.00
50.00
51.00
Very Low Float Voltage Alarm
-
40 to
-
51V
46.00
46.00
46.00
Rectifier On Threshold
-
40 to
-
51V
44.00
44.00
44.00
Verify that all AC, DC and Controller connections are complete and secure. Turn on AC input breakers. If there are
no alarms, make required adjustments to the default settings on the controller for this installation.
IEC
-
Style, 8ft, 12AWG
Part Number
Plug
Length
CC848847368
No plug
8 ft
CC848850792
5
-
15P
8 ft
CC848850801
5
-
20P
8 ft
CC848850826
6
-
15P
8 ft
CC848850834
6
-
20P
8 ft
CC848850842
L6
-
20P
8 ft
850044361
L5
-
15P
15 ft
850044362
L5
-
20P
15 ft
CC848895961
L6
-
20P
15 ft
QUICK START GUIDE