Page 12
Infinity S_Dual V_old_QSG
Version 4.0
© 2021 ABB. All rights reserved.
Information: Controller Basic Operation (continued)
All user configurable parameters can be accessed from the front panel, however user convenience and visibility is
enhanced by access through the LAN port using the built
-
in web pages.
Configuration > Communication Ports > Network Settings > DHCP > mode, to SERVER
Once the LAN port is configured as a server, the laptop can be connected to the LAN port, using a standard
ethernet cable. Use a standard web browser to access the controller web pages at default IP address: 192.168.2.1
Warning:
Do not connect LAN port to a network when set to Server mode. Set the controller LAN port to Client or
Static before connecting to the network. Static is the factory default setting and the typical setting for most
networks.
Once connected to the controller web server a log on screen should be visible:
Logon Screen
-
web view
Factory Default password is
“
Administrator
”
and should be used for initial logon. It is highly recommended that
one of the first activities should be to change the default password(s).
Home Page –
Web View
QUICK START GUIDE