1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
215
Technical Manual
by the motor is less than the minimum load current drawn, it can be inferred that the motor
is either disconnected from the load or the coupling mechanism is faulty. If the motor is
allowed to run in this condition, it may aggravate the fault in the coupling mechanism or
harm the personnel handling the machine. Therefore, the motor has to be disconnected
from the power supply as soon as the above condition is detected.
37 detects the condition by monitoring the current values and helps disconnect the motor
from the power supply instantaneously or after a delay according to the requirement.
When the motor is at standstill, the current will be zero and it is not recommended to
activate the trip during this time. The minimum current drawn by the motor when it is
connected to the power supply is the no load current, that is, the higher pickup value
current. If the current drawn is below the lower pickup value current, the motor is
disconnected from the power supply. 37 detects this condition and interprets that the motor
is de-energized and disables the function to prevent unnecessary trip events.
4.1.11.6
Signals
Table 205: 37 Input signals
Table 206: 37 Output signals
4.1.11.7
Settings
Table 207: 37 Group settings
Table 208: 37 Non group settings
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block all binary outputs by resetting timers
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value low
0.01...0.50
xln
0.01
0.10
Current setting/Pickup value low
Pickup value high
0.01...1.00
xln
0.01
0.50
Current setting/Pickup value high
Trip delay time
400...600000
ms
10
2000
Trip delay time
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......