Example 4
&KDSWHU
&XELFOHOD\RXWV
([DPSOH
The following scope of supply applies for a 115 kV Line bay cubicle (diameter 4) for
xxx substation:
2 Protection & Control terminals, REx 5xx for
feeder 1 and 2 with the following functions:
•
control
•
scheme communication logic
•
automatic switch onto fault logic
•
power swing blocking
•
autorecloser, 3-phase
•
synchrocheck
•
directional earth fault protection
•
remote communication
•
test switch
1 Control terminal, REx 5xx including breaker
failure protection for the middle breaker
1 Back-up panel for 3 breaker
2 RAICA, Breaker failure relays
5 RXMS 1 Tripping relay
5 SPER 1C1 Trip circuit supervision
3 sets of Micro Circuit Breakers
1
5
9
13
17
21
25
29
33
37
41
43
HINGED FRAME, MP=U
MODULE
POSITION
(S=44,5mm)
700
Tripping relays
Trip circuit superv.
MCB
ABB
S
(
&
REx 5xx
Prot. & Control
terminal
Feeder 1
(
&
REx 5xx
Control and BFR
terminal
Breaker 2
(
&
REx 5xx
Prot. & Control
terminal
Feeder 2
BF
M
M
0 1
;
;
;
en04000345.vsd
BF