2600T Series Pressure transmitters |
OI/266/FF-EN Rev. B 37
10 HMI local indicator
10.6 LCD structure
The Device TAG and Node Address are always visible in the
top side of the LCD. The line/s and bar-graph view depends by
the
HMI_MODE
Selection
The displayed variables are identified by a max of the three
character strings visible on the left side of the value when two
lines mode is selected or below the value when one line mode
is selected. The list of all the strings identifying the variable is
available in the
HMI_VARIABLE_1
within the HMITB table, see
“APPENDIX A – Device Data Blocks”.
Example of how the indicator looks with one and two
lines plus bar-graph
1 Tag | 2 Node address | 3 Variable identification | 4 Line 1 |
5 Line 2 | 6 Bar-graph
10.7 LCD setting
The variables to be displayed can be selected in two ways:
—
Locally using the optional LCD keypad from the menu
“Display/settings/…”
see APPENDIX B for further
information.
—
From remote station via Fieldbus communication writing
in the HMITB.
In the HMITB there are up to 4 variables called
HMI_
VARIABLE_x
(where x is from 1 to 4) and each of them can be
set with one variable to be displayed, selected from a list of 10
different variables.
Then the
HMI_LINE_1, HMI_LINE_2
and
HMI_BARGRAPH
must be set to one of the
HMI_VARIABLE_x
depending by
which variable the user wants see on the Line 1 or Line 2 or
bar-graph. The parameter
HMI_SEQUENCE
allows the
enabling of the automatic scrolling of the 4
HMI_VARIABLE_x
3
1
2
3
4
5
6
Figure 47: Display layout
Important.
It is recommended to use the Auto-scrolling only with
HMI_MODE set to One Line..
10.8 HMI as Diagnostic Indicator
While the HMI works as Variable Indicator, also diagnostic
strings can be displayed. Whenever a failure or warning
condition is detected within the transmitter, a message appears
in the low side of the display below the bar-graph.
The message is formed by the NAMUR NE107 icon and the
string of the component where the problem occurred.
NAMUR icons
Description
Source of error
Error / Failure
ELECTRONICS
Functional check (e.g. during
simulation )
SENSOR
Out of Spec (e.g. Sensor temperature
outside the specs limits)
PROCESS
Maintenance required
CONFIGURATION
Example of “Maintenance / Sensor” and “Failure /
Electronics” diagnostic
Figure 48: Diagnostic messages
Содержание 266FF
Страница 40: ...40 OI 266 FF EN Rev B 2600T Series Pressure transmitters 10 HMI local indicator Display ...
Страница 41: ...2600T Series Pressure transmitters OI 266 FF EN Rev B 41 10 HMI local indicator ...
Страница 42: ...42 OI 266 FF EN Rev B 2600T Series Pressure transmitters 10 HMI local indicator ...
Страница 43: ...2600T Series Pressure transmitters OI 266 FF EN Rev B 43 10 HMI local indicator Device Info ...
Страница 44: ...44 OI 266 FF EN Rev B 2600T Series Pressure transmitters 10 HMI local indicator Communication ...
Страница 54: ...54 OI 266 FF EN Rev B 2600T Series Pressure transmitters ...
Страница 55: ...2600T Series Pressure transmitters OI 266 FF EN Rev B 55 ...