88 OI/266/FF/ADD-EN Rev. B
| 2600T Series Pressure transmitters
266 Models - FOUNDATION Fieldbus
Output scale 100%
AI2_OUT_SCALE 100%
PTRB_TERTIARY_VALUE_RANGE_100%
Output Scale Unit
AI2_OUT_SCALE_UNIT
MPa
Linearization
AI2_L_TYPE
Direct
Critical Limit Low
AI2_LO_LO_LIM
AI2_OUT_SCALE 0% - 10% of the SPAN
Advisory Limit Low
AI2_LO_LIM
Advisory Limit High
AI2_HI_LIM
AI2_OUT_SCALE 100% + 10% of the SPAN
Critical Limit High
AI2_HI_HI_LIM
Alarm Hysteresis
AI2_ALARM_HYS
0.5% of the SPAN
Analog Input 3 setting
Channel
AI2_CHANNEL
3 = Static Pressure
Channel
AI3_CHANNEL
2 = Sensor temperature
Damping
AI3_PV_FTIME
0 second
Calibation Lower Range Value 0%
AI3_XD_SCALE 0%
PTRB_ SECONDARY_VALUE_RANGE_0%
Calibation Upper Range Value 100%
AI3_XD_SCALE 100%
PTRB_ SECONDARY_VALUE_RANGE_100%
Calibration Unit
AI3_XD_SCALE_UNIT
°C
Output scale 0%
AI3_OUT_SCALE 0%
PTRB_ SECONDARY_VALUE_RANGE_0%
Output scale 100%
AI3_OUT_SCALE 100%
PTRB_ SECONDARY_VALUE_RANGE_100%
Output Scale Unit
AI3_OUT_SCALE_UNIT
°C
Linearization
AI3_L_TYPE
Direct
Critical Limit Low
AI3_LO_LO_LIM
AI3_OUT_SCALE 0% - 10% of the SPAN
Advisory Limit Low
AI3_LO_LIM
Advisory Limit High
AI3_HI_LIM
AI3_OUT_SCALE 100% + 10% of the SPAN
Critical Limit High
AI3_HI_HI_LIM
Alarm Hysteresis
AI3_ALARM_HYS
0.5% of the SPAN
Important
All the above configurable parameters can be afterward modified via DD based software tools