2600T Series Pressure transmitters |
OI/266/FF/ADD-EN Rev. B 21
Idx
Parameter
Data
Type
Size
Storage
Description / Range / Selections / Note
15
PILD_OUTPUT
R
S
U8
1
D
Status of the Impulse Lines
Bit 0
Normal
The pr
ocess connections ar
e OK and the device is
working
normally
. Lines Not Plugged
Bit 1
Not V
alid
When the PILD algorithm is not working like, for
example
, during the T
raining phase or if the training
phase didn’
t pr
oduce a valid r
esult
Bit 2
Max Pr
essur
e Deviation
The pr
essur
e value curr
ently detected is too dif
fer
ent
from what used for the T
raining. A new T
raining is
necessary
for this new pr
ocess condition
Bit 3
One Line Plugged
One undetected pr
ocess connection is plugged. It was
not possible identify which one
Bit 4
Two Lines Plugged
Both the
Pr
ocess connections, high side (+)
and
low side
(-) ar
e plugged
Bit 5
Line H Plugged
The Pr
ocess connection on the high side (+) is
plugged
Bit 6
Line L Plugged
The Pr
ocess connection on the low side (-) is
plugged
Bit 7
not used
16
PILD_AFFECT_PV
RW
S
U8
1
S
This parameter indicates if the PILD
algorithm must
af
fect the
PR
TB_PRIMAR
Y_V
ALUE.
if YES, when the PILD r
eveals an
abnormal
situation, it sets
the
PR
TB_PRIMAR
Y_V
ALUE Status to
BAD.
0
No
Doesn’
t af
fect primary value status (default value)
1
Ye
s
Af
fect primary value status
17
PILD_DETECTION_TIME
RW
S
U8
1
S
This parameter r
epr
esents the length of the algorithm slot. This is the time interval (minutes) over which the algorithm bases
the decision on the plugging state of the impulse lines
18
PILD_MAX_PRESSURE_
DEV
RW
S
U8
1
S
This parameter is used in the normal operation checks. It is the maximum allowed deviation of the dif
fer
ential pr
essur
e fr
om
the mean dif
fer
ential pr
essur
e Red in the training phase. If the deviation is gr
eater
, than the PILD output is set to OUTPUT
NOT V
ALID, because the conditions ar
e too dif
fer
ent fr
om the training phase
19
PILD_RETRAIN
RW
S
U8
1
S
The PILD algorithm can be for
ced to
train again when the pr
ocess condi
-
tions pass the maximum allowed
deviation
0
No
Re-trainings ar
e Disabled / not executed
1
Ye
s
Af
fect primary value status
20
PILD_TRAIN_TIME
RW
S
U8
1
S
This parameter r
epr
esents the duration of the training period
21
PILD_TRAIN_RETRIES
RW
S
U8
1
S
At the end of the training pr
ocedur
e, ther
e ar
e the training checks on the Red data. If they fail, the algorithm is allowed to
retry the pr
ocedur
e adding a further slot of data. This parameter is the max number of allowed r
etries