2600T Series Pressure transmitters |
OI/266/HART-EN Rev. M 61
9 Error messages
9 Error messages
9.1 LCD Display messages
The LCD HMI in case of transmitter errors or malfunctioning is capable of displaying specific error/fault messages to help the user
in identifying the problem and resolve it. In case of an alarm, a message consisting of an icon and text appears at the bottom of
the process display, as shown hereafter. Use the (1) key to call up the information level. Use the “Diagnostics” menu to call up the
error description with a help text. In the error description, the error number is displayed in the second line (M028.018). Two further
lines are used to describe the error. The device status is divided into four groups. The message text beside this icon in the display
provides information about where to look for the error. There are the following areas: Electronic, Sensor, Configuration, Operanting
and Process.
Icon
Description
Error / Failure
Functional check (e.g. during simulation )
Out of Spec (e.g. operating with empty meter pipe)
Maintenance required
9.2 Error states and alarms
— Communication Board / Electronic related error messages.
Error message Tx LCD message
Possible cause
Suggested action
Tx response
F116.023
Electronic Memory Failure
Electronic memory corrupted.
The electronic must be replaced.
Analog Signal to Alarm
F108.040
Output ReadBack Failure
The output circuit could be broken
or not correctly calibrated.
A DAC (digital to outpt converter) trimming
should be performed and if the error persists
the communication board must be replaced.
Analog Signal to Alarm
M030.020
Electronic Interface Error
Data exchange between the sensor
and the electronic is incorrect.
Power off and on the transmitter and check if
the error persists. If yes replace the
communication board as soon as possible.
no effect
M026.024
NV Electronic Memory Burn
Error
Writings to the electronic non-
Volatile Memory has not been
successful.
The communication board should be replaced
as soon as possible.
no effect
F106.035
Unreliable Output Current
The D to A converter is not properly
Calibrated/Trimmed.
Perform an Output Trimming and if the error
persists the communication board must be
replaced. (see NOTE below)
Analog Signal to Alarm
F106.035
Unreliable Output Current
The Device is not properly
configured.
Check the device configuration.
Analog Signal to Alarm
C090.033
Analog Output Fixed
The analog output for the Primary
Variable is derived by the value
simulated in input.
Use a HART configurator (DTM - Hand held) to
place device back in to normal operating mode
(Remove the analog output simulation).
no effect
Note for the calibration of the current output by the user.
For 266 Transmitters with SW.-Rev. </= 7.1.15 and alarm current
setting to ‘low alarm’ The calibration of the current output by the
user requires to perform the calibration procedure with a suitable
configuration tool (DTM, EDD, FIM) and to finalize the procedure by
saving the process with “save configuration as default”.
Содержание 266 HART Series
Страница 40: ...40 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 1 Easy Set up Standard HART version...
Страница 42: ...42 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 3 Device Set up...
Страница 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 43 8 Operation...
Страница 44: ...44 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Страница 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 45 8 Operation...
Страница 46: ...46 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 4 Display...
Страница 47: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 47 8 Operation...
Страница 48: ...48 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Страница 50: ...50 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 6 Calibrate...
Страница 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 51 8 Operation 8 13 7 Totalizer...
Страница 52: ...52 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Страница 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 53 8 Operation...
Страница 54: ...54 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 8 Diagnostics...
Страница 55: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 55 8 Operation 8 13 9 Device Info...
Страница 56: ...56 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 10 Communication...
Страница 71: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 71...
Страница 72: ...72 OI 266 HART EN Rev M 2600T Series Pressure transmitters...
Страница 74: ...74 OI 266 HART EN Rev M 2600T Series Pressure transmitters Intentionally blank...
Страница 75: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 75 Intentionally blank...