ABB 07 MK 92 R1161 Скачать руководство пользователя страница 5

Advant Controller 31 / Issued: 10.99

7.2-3

Hardware 07 MK 92 R1161

2

Hardware

1 Mounting the unit on a DIN rail

2 Mounting the unit with screws

3 6.3 mm Faston earthing terminal

4 24 V DC supply voltage

5 Configurable serial interface COM3

6 Configurable serial interface COM4

7 Serial interface COM5

8 Serial interface COM6

9 Networking interface for the Advant

Controller 31 basic unit

10 Switch for RUN/STOP operation

Fig. 7.2-2: Communication module 07 MK 92 R1161 with reference points (see below for explanation)

7.2.2

Structure of the front panel elements

2

2

2

2

4

3

1

9

10

7

8

6

5

Serial Comm. Processor

 

Advant Controller 31

07 MK 92

RUN
ERR
Supp.

2
3
4

1

LED

12

11

RUN

STOP

The status of the application program is indicated by the
LED RUN: The LED RUN lights up while the program is
being processed. If an error occurred during loading (e.g.
program not present), the LED RUN remains OFF.

RUN –> STOP

If the switch is switched from RUN to STOP, the program
processing is aborted. The LED RUN goes out.

11 LED displays for system messages

12 LED displays freely configurable

The RUN/STOP switch controls the
processing of the user application.

STOP –> RUN

If the switch is switched from STOP to RUN, the user
application is loaded into the main memory and process-
ing of the application program is started.

Application program is running
Fatal or serious error
Supply voltage present

LED1

LED2

LED3

LED4

RUN

ERR

Supply

12

11

Refer to Section 7.2.4 Diagnosis for further information

yellow
yellow
yellow
yellow

green
red
green

Содержание 07 MK 92 R1161

Страница 1: ...7 MK 92 R1161 ABB STOTZ KONTAKT RUN COM4 COM3 Serial Communication Processor Advant Controller 31 07 MK 92 RUN ERR Supply 2 3 4 1 LED Operating Manual Hardware Advant Controller 31 Intelligent Decentralized Automation System ...

Страница 2: ......

Страница 3: ... areas in 07 MK 92 7 2 19 7 2 9 LED control 7 2 19 7 2 10 Allocation of the ports 7 2 19 7 2 Communication module 07 MK 92 R1161 no longer available Connecting external units Fig 7 2 1 Communication module 07 MK 92 R1161 7 2 1 Brief description The 07 MK 92 R1161 communication module is a freely programmable interface module with 4 serial interfaces The communication module allows external units t...

Страница 4: ... 232 or EIA RS 422 or EIA RS 485 COM3 COM4 2 of them are interfaces in accordance with EIA RS 232 COM5 COM6 Freely programmable with a comprehensive function library Communication with AC31 basic unit via library func tions Configurable LEDs for diagnosis Programming and testing on a PC via COM3 Processing of the serial interfaces and the networking in terface is provided for in an applications pr...

Страница 5: ... 1 LED 12 11 RUN STOP The status of the application program is indicated by the LED RUN The LED RUN lights up while the program is being processed If an error occurred during loading e g program not present the LED RUN remains OFF RUN STOP If the switch is switched from RUN to STOP the program processing is aborted The LED RUN goes out 11 LED displays for system messages 12 LED displays freely con...

Страница 6: ... shows an application example with the 07 KT 97 which utilizes various possibilities for connecting inputs and outputs Attention must be paid to the following in detail The earthing measures Connection of the 07 MK 92 communication module Looping through the supply voltage 24 V DC from the 07 KT 97 to the 07 MK 92 Earthing the switch gear cabinet mains socket Handling serial interfaces ...

Страница 7: ... 97 Section 7 2 3 Electrical connection applies in the same way to 07 KR 91 07 KT 92 to 07 KT 97 Output loads for 24 V DC Earth connection Use supplied parts see Figure 7 2 6 Supply voltage Short direct connection between the modules wires 15 cm 2 5 mm2 see Figure 7 2 6 Cable shields In the case of permanent wiring at the switchgear cabinet inlet earth via clamps and do not put shield in the plug ...

Страница 8: ...respond to DIN VDE 0160 The unit is connected via the 6 3 mm Faston terminal bot tom left to the functional earth switch gear cabinet earth via a wire with a cross section of 6 mm2 also see Fig 7 2 6 6 mm2 cross section Fig 7 2 5 Electrical isolation and notes on earthing Connect to the Faston of the basic unit see Figure 7 2 6 Terminal assignment 15 L Supply voltage 24 V DC 16 L Supply voltage 24...

Страница 9: ... 10 99 7 2 7 Hardware 07 MK 92 R1161 2 Hardware 6 mm2 07 MK 92 07 KT 97 PE L 24 V DC M 0 V 15 cm long 2 5 mm2 Use supplied connection parts Switch gear cabinet earth Fig 7 2 6 Earthing connections and voltage supply for 07 MK 92 ...

Страница 10: ...00 Bd for COM3 and COM 4 and from 300 Bd to 9600 Bd for COM5 and COM6 Automatic processing of the SW handshake XON XOFF Automatic processing of the HW handshake RTS CTS Error detection parity framing overrun break Serial interfaces COM3 COM4 Interface standard EIA RS 232 or EIA RS 422 or EIA RS 485 Both interfaces can be run independently of each other in one of the interface standards each Select...

Страница 11: ...11 RxD N Receive Data Input EIA RS 422 EIA RS 485 12 RTS P Request To Send Output EIA RS 422 13 RTS N Request To Send Output EIA RS 422 14 CTS P Clear To Send Input EIA RS 422 15 CTS N Clear To Send Input EIA RS 422 Fig 7 2 8 Terminal assignment for the serial interface COM4 Programming and test mode This mode is not used with COM4 Pin 6 open Application mode Pin 6 jumpered in the interface connec...

Страница 12: ...EIA RS 232 7 9 PGND Protective Ground Shield 10 TxD Transmit Data Output 11 RxD Receive Data Input 12 RTS Request To Send Output 13 CTS Clear To Send Input 14 SGND Signal Ground 0V Fig 7 2 9 Terminal assignment of the serial interface COM5 Serial interface COM6 Terminal assignment Interface standard EIA RS 232 23 PGND Protective Ground Shield 24 TxD Transmit Data Output 25 RxD Receive Data Input 2...

Страница 13: ...nterface 2 Plug the socket strip of the 40 pole ribbon cable se cured to the 07 MK 92 onto the networking connector of the basic unit 3 Place both units on a level surface and slide them to gether so that they engage 4 Slide in the connection part to fix the housing in posi tion 9 7 2 3 5 Networking interface The networking interface a special parallel interface al lows the 07 MK 92 communication ...

Страница 14: ...tage l Check supply voltage n n H Supply voltage present 07 MK 92 is ready to process the user application Load user application with 907 MK 92 Start processing of application Switch RUN STOP switch to RUN H n H The user application is running X H H A serious error is present which caused the user l Read out error and remedy if this is possible application to abort automatically H H H Initializati...

Страница 15: ... against reversed terminal connection yes only when units with electrically isolated interfaces are connected to COM5 COM6 7 2 6 3 Connection of serial interfaces COM3 COM4 Interface standard EIA RS 232 or EIA RS 422 or EIA RS 485 Programming with 907 MK 92 via IBM PC or compatible Man machine communication yes e g with an operating station Electrical isolation yes interfaces with respect to each ...

Страница 16: ...od by removeable terminal blocks with screw type terminals max 2 5 mm2 Weight 450 g Dimensions for mounting see the following drawing 7 2 6 7 Mounting hints Mounting position vertical terminals above and below Cooling The natural convection cooling must not be hindered by cable ducts or other material mounted in the switch gear cabinet The device is 85 mm deep The interface connectors COM3 and COM...

Страница 17: ...07 MK 92 R1161 2 9 pole terminal blocks 5 08 mm grid 1 5 pole terminal block 5 08 mm grid Cable including terminals for making the earth connection Further literature System description Advant Controller 31 English Order No 1SAC 1316 99 R 0201 Software Programming and test software 907 MK 92 Order No GJP5 2074 00 R0102 907 MK 92 consists of Documentation Software Basic functions for 07 MK 92 R1161...

Страница 18: ...PC 25 pole for programming und test software 907 MK 92 2 3 2 3 4 DTR 5 5 6 CTS SGND DSR 4 RTS 07 MK 92 7 7 SGND RTS 8 CTS DSR Data Set Ready DTR Data Terminal Ready CD Carrier Detect SGND Signal Ground 1 PGND PC PGND Protective Ground TxD Transmit Data RxD Receive Data RTS Request To Send CTS Clear To Send TxD RxD TxD RxD 1 20 CD Shield 15 pole male 25 pole female Fig 7 2 16 Connecting COM3 to PC ...

Страница 19: ...15 RTS P RTS N CTS P CTS N RTS P RTS N CTS P CTS N 2 3 5 CTS SGND 4 RTS 07 MK 92 7 SGND RTS CTS 1 PGND TxD RxD RxD TxD 6 PROG Shield 15polig male Fig 7 2 18 COM3 COM4 as EIA RS 232 interface 7 2 7 3 COM3 COM4 as EIA RS 232 interface Shield 15 pole male Fig 7 2 19 COM3 COM4 as EIA RS 422 interface 7 2 7 4 COM3 COM4 as EIA RS 422 interface Shield 15 pole male Fig 7 2 20 COM3 COM4 as EIA RS 485 inter...

Страница 20: ... 23 PGND TxD RxD RxD TxD 10 11 13 CTS SGND 12 RTS 14 SGND RTS CTS 9 PGND TxD RxD RxD TxD Shield Terminals 07 MK 92 Fig 7 2 21 COM5 as EIA RS 232 interface 7 2 7 6 COM5 as EIA RS 232 interface Signal Shield Terminals 07 MK 92 Fig 7 2 22 COM6 as EIA RS 232 interface 7 2 7 7 COM6 as EIA RS 232 interface Signal ...

Страница 21: ...al Port RAM Not used Free RAM area Used RAM area 7 2 9 LED control Addressing Segment 9800 Offset 0 LED1 1 LED2 2 LED3 3 LED4 4 LED RUN Flash programming voltage 5 EEPROM Vpp 6 LED ERR 7 2 10 Allocation of the ports Port P2PIN Bit 5 RUN STOP 1 STOP 0 RUN Port P2PIN Bit 6 Status of pin 6 at COM3 Port P2PIN Bit 7 Status of pin 6 at COM4 Port P1LTCH Bit 5 Control of RTS COM3 Port P1LTCH Bit 7 RS 485 ...

Страница 22: ...7 2 20 Advant Controller 31 Issued 10 99 07 MK 92 R1161 2 Hardware ...

Страница 23: ......

Страница 24: ...STOTZ KONTAKT GmbH Eppelheimer Straße 82 Postfach 101680 D 69123 Heidelberg D 69006 Heidelberg Telephone 49 6221 701 0 Telefax 49 6221 701 1111 E Mail desst helpline de abb com Internet http www abb de sst ...

Отзывы: