Module Calibration
Chapter 7
7-2
Table 7.B
Calibration Block Transfer Write or Discrete Output Bit/Word Descriptions
Word
Decimal Bit
(Octal Bit)
Description
Bit 00
Input select bit. Indicates input channel 0 being calibrated.
Bit 01
Input select bit. Indicates input channel 1 being calibrated.
Bit 02
Input select bit. Indicates input channel 2 being calibrated.
Bit 03
Input select bit. Indicates input channel 3 being calibrated.
Bit 04
Output select bit. Indicates output channel 0 being calibrated.
Bit 05
Output select bit. Indicates output channel 1 being calibrated.
Word 0
Bit 06
High/low bit
HL
. Indicates whether full scale or zero data point is being
updated:
Bit 06 = 1 - full scale
Bit 06 = 0 - zero data point
Bit 07
Execute Bit.
EX
. When set (1), starts calibration and updates the
selected channels.
Bit 08 (10)
Input Mode Bit
IM
.
Bit 08 (10) = 0 - Use for voltage inputs. Input scaling in mV
Bit 08 (10) = 1 - Use for current inputs. Input scaling in
µ
A
Bits 910 (1112)
Not used
Bit 11 (13)
EEPROM write bit
OK
. When set (1), requests the current calibration
data be saved.
Bits 1215 (1417) Calibration mode bits. Set to 1100 to select a calibration sequence.
Word 1
Bits 0015 (0017)
Output Channel 0 Calibration Data - user entered calibration data
when EX = 0 (bit 07 in word 0), scaled and corrected output data when
DN bit (bit 07 in BTR) = 1.
Word 2
Bits 0015 (0017)
Output Channel 1 Calibration Data - user entered calibration data
when EX = 0 (bit 07 in word 0), scaled and corrected output data when
DN bit (bit 07 in BTR) = 1.
Table 7.C
Calibration Block Transfer Read Data File
Word/ Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Word/Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
0
1
1
0
0
OK
IM
DN
HL
O1
O0
I3
I2
I1
I0
1
Corrected Input Channel 0 Data
2
Corrected Input Channel 1 Data
3
Corrected Input Channel 2 Data
4
Corrected Input Channel 3 Data