SW1
SW2
Position = 1
Position = 0
Open clear front
cover to access
switches
1
30
End View of Switch
1791N4V2
ANALOG BLOCK
POWER
COMM
FAULT
8
7
6
5
4
3
2
1
0
1
8
7
6
5
4
3
2
1
0
1
ATTENTION:
Recycle power to the block I/O module
after setting the switches.
Configuring Your Block I/O for PLC
Family Programmable Controllers
Chapter 3
3-2
Figure 3.1
Switch Settings for the Analog Block I/O Modules
SW2-8
Not used
SW2-7
Not Used
SW2-6
Last I/O Group
0
Not last rack
1
Last rack
SW2-5
Processor
Restart/Lockout (PRL)
0
Processor Restart
1
Processor Lockout
SW2-4
Hold Last State
0
Reset Outputs
1
Hold Last State
SW2-3
Transfer Type
0
Block Transfer
1
Discrete Transfer
Communication Rate
SW2-2 SW2-1
Bits/s
0
0
57.6 K
0
1
115.2 K
1
0
230.4 K
1
1
230.4 K
Starting Quarter
SW1-2 SW1-1
Module
Group
0
0
0 (1st)
0
1
2 (2nd)
1
0
4 (3rd)
1
1
6 (4th)