12
SLC 500™ Power Supplies
Publication 1746-IN004D-MU-P - May 2003
Power Supply Undervoltage Operation
SLC 500 controllers continue to operate (hold-up) for a short period of time if the
input voltage to the power supply drops below the recommended operating
voltage range. The controller continues to scan the user program and control I/O
during this time. CPU hold-up for each power supply is shown on pages
12
and 1
4
.
SLC 500 controllers turn OFF (stop scanning and disable outputs) if input voltage to
the power supply is removed or drops below the recommended operating range
for a period exceeding the CPU hold-up time. The controller resumes operation
automatically when the input voltage is restored to normal.
If the input voltage to the 1746-P7 power supply falls into a range of 4 to 9V for a
period exceeding the CPU hold-up time, the controller turns OFF and will not turn
back ON until:
•
input voltage is increased to 11V dc.
General Specifications (Power Supplies 1746-P1, -P2, -P3,
and -P4)
Description:
Specification: 1746-
P1
P2
P3
P4
Line Voltage
85-132/170-265V ac
47-63 Hz
19.2-28.8V dc
85-132/170-250V ac
47-63 Hz
Typical Line Power
Requirement
135 VA
180 VA
90 VA
150 VA
Maximum Inrush
Current
20A
45A
Internal Current
Capacity
2A at 5V dc
0.46A at 24V dc
5A at 5V dc
0.96A at 24V dc
3.6A at 5V dc
0.87A at 24V dc
10.0A at 5V dc
2.88A at 24V dc
(1)
Fuse Protection
(2)
1746-F1 or
equivalent
(3) (4)
1746-F2 or
equivalent
(3) (5)
1746-F3 or
equivalent
(3) (6)
Fuse is soldered in
place.
24V dc User Power
Current Capacity
200 mA
Not Applicable
1A
(1)
24V dc User Power
Volt. Range
18-30V dc
20.4-27.6V dc
Max. User-supplied
overcurrent
protection
(7)
15A
Not Applicable
15A
Ambient Operating
Temperature
0°C to +60°C (+32°F to +140°F)
Current capacity is derated 5% above +55°C.
0°C to +60°C
(+32°F to +140°F)
no derating
Isolation
(8)
1800V ac RMS for 1 s
None
(9)
2600V dc for 1 s
CPU Hold-up Time
(10)
20 ms (full load) 3000 ms (no load)
5 ms (full load)
1000 ms (no load)
20 ms (full load)
3000 ms (no load)