background image

 

18

   

• In ambient temperature below 

0

℃(32℉ ), the engine will run at the rated

 

speed (2800r/min) for 5 minutes to warm 

up the engine. 

• In ambient temperature below

 

5

(

41

℉)

 , the engine will run at the 

speed (2800r/min) for 3 minutes to warm 

up the engine. 

• The ESC unit operates normally after the 

above time period, while the ECS switch 

(Black) is “ON” position. 

 
Manual starting:

 

7. Turn the engine switch to “

ON

” 

position. 

 

 

8. Pull slowly on the recoil starter until it is 

engaged, then pull it briskly. 

NOTE:

 Grasp the carrying handle firmly 

to prevent the generator from falling 

over when pulling the recoil starter. 

 

9. After the engine starts, warm up the 

engine until the engine does not stop. 

when press the choke knob full in.   

10. Push the choke knob fully in.

 

 

11. Allow the generator to run for several 

minutes before attempting to connect 

any electrical devices. This allows the 

generator to stabilize its speed and 

temperature. 

ECONOMY CONTROL SWITCH 

This generator is equipped with an 

Economy Control Switch. Engaging the 

switch will automatically adjust the engine 

speed to match the load at hand. When 

an electrical device comes on line, the 

generator engine will automatically speed 

up to supply the power needed and will 

slow down as the need decreases. The 

variable engine speed can reduce fuel 

consumption and noise level. When the 

economy swich is off, the engine runs at 

normal speed continuously.

 

STOPPING THE 
GENERATOR 

To Stop The Generator 

1. 

Turn off any electric devices

 prior to 

unplugging them from the generator. 

NOTE: 

Unplugging running devices can 

cause damage to the generator

 

2. 

Turn the economy control switch 

(Black)

 to the 

OFF

 position

 

2. Disconnect any electric devices.   

Содержание A112004

Страница 1: ...anual before assembling operating and maintaining this unit You are responsible for operating the product properly safely Version V1 20171124 A A V I X O U T D O O R S 3000W DIGITAL INVERTER GENERATOR...

Страница 2: ...39 A112004 Exploded View Part List 40 A112005 Exploded View Part List 45 SAFETY RULES Read and observe all warnings cautions and instructions on the generator and in this owner s manual before operat...

Страница 3: ...hese areas Using a fan or opening windows and doors does NOT supply enough fresh air ONLY use a generator outdoors and far away from open windows doors and vents These openings can pull in generator e...

Страница 4: ...rkers Use a ground fault circuit interrupter GFCI in highly conductive areas such as metal decking or steel work GFCIs are available in line with some extension cords Do not use in rainy conditions Do...

Страница 5: ...vibration Have damaged items repaired or replaced as necessary Do not use plugs or cords that show signs of damage such as broken or cracked insulation or damaged blades For power outages permanently...

Страница 6: ...to commercial power outlet Avoid connecting the generator in parallel with any other generator WARNING Before the generator can be connected to a building s electrical system a licensed electrician mu...

Страница 7: ...ductors excluding the equipment grounding conductor The frame of the generator shall be connected to an approved grounding electrode Any improper connection may cause damage to the generator or cause...

Страница 8: ...be grounded with a good quality insulated conductor CAUTION Make sure the control panel louver and the inverter bottom side cooling well and without chips mud and water come in it may damage the engi...

Страница 9: ...ort 5V 1 A 2 1A Phase Single Engine Engine Type Single cylinder 4 stroke forced air cooling OHV Displacement cc 192 Fuel Type Unleaded Gasoline Fuel Tank Capacity 3 9 US gallon 15 liters Fuel Consumpt...

Страница 10: ...2 Fuel tank cap 6 Recoil starter 3 Draw handle 7 Louver 4 Control panel 8 Muffler Accessories 1 Socket Wrench 1pc 2 Oil funnel 1pc 3 Screw driver 1pc 4 12V DC Battery charging cable 1pc 5 Spark plug...

Страница 11: ...his manual are a guide but not necessarily an exact copy of the actual product CONTROL FUNCTION Engine switch The engine switch controls the ignition system 1 OFF Insert the key provided ignition circ...

Страница 12: ...ect current is not output CAUTION Reduce the load of the connected electric device below the specified rated output of the generator if the DC protector turns off If the DC protector turns off again s...

Страница 13: ...r reading this section you are unsure about how to perform any of the steps please call customer service center Failure to perform these steps properly can damage the generator or shorten its life Ste...

Страница 14: ...t 7 Check for oil leaks Tighten dipstick firmly before closing the access panel Step 2 ADD GASOLINE DANGER This generator may emit highly flammable and explosive gasoline vapors which can cause severe...

Страница 15: ...ning fuel from the tank and the CARBURETTOR when storing the product for over 30 days Step 3 GROUND Earth THE GENERATOR WARNING Make sure to ground earth the generator Failure to properly ground the g...

Страница 16: ...d or battery backup CO alarm in the home If you start to feel sick dizzy or weak after the generator has been running move to fresh air RIGHT AWAY See a doctor You may have carbon monoxide poisoning W...

Страница 17: ...ssible as overheating and damage can occur DO NOT crank the engine switch more than 5 seconds on any one attempt If engine does not start refer to TROUBLESHOOTING in MAINTENANCE section 8 After the en...

Страница 18: ...n 11 Allow the generator to run for several minutes before attempting to connect any electrical devices This allows the generator to stabilize its speed and temperature ECONOMY CONTROL SWITCH This gen...

Страница 19: ...pair WARNING If any item in the Pre operation check is not working properly have it inspected and repaired before operating the generator The condition of a generator is the owner s responsibility Vit...

Страница 20: ...nearby open flame can lead to explosion even if not direcdy in contact with fuel Do not operate near open flame Do not smoke near generator Always operate on a firm level surface Always turn generator...

Страница 21: ...run for a few minutes to stabilize the speed and voltage output CAUTION Become familiar with the markings on the panel before connecting electrical devices Connect electrical devices running on AC cur...

Страница 22: ...ng to the following procedure 1 Plug in each electrical device making sure that the device is turned off 2 Check the overload light and power indicator light If the overload light RED is on and the in...

Страница 23: ...e sure the total load is within generator rated output otherwise generator damage will occur NOTE Some precision equipment is voltage sensitive and may require a more uniform voltage supply than porta...

Страница 24: ...a connected electrical device is detected the inverter control unit overheats or the AC output voltage rises Then the electronic breaker will activate stopping power generation in order to protect the...

Страница 25: ...roperly connected and is not damaged or obstructed At full charge electrolyte specific gravity is between 1 26 and 1 28 Check specific gravity hourly Never smoke or make and break connections at the b...

Страница 26: ...arting to charge the battery press to resetthe DC protector If the DC protector turns off again stop charging the battery immediately and consult our service center 5 Disconnect the plug from the rece...

Страница 27: ...ather hose for cracks or damage Muffler screen Check Clean replace Cylinder head piston Clean up Carbon 225cc every 125hrs 225cc every 250hrs The installation and major repair work shall be carried ou...

Страница 28: ...g To check the oil level 1 Make sure the generator is on a level surface 2 Open access panel Clean around oil fill Remove dipstick and wipe the dipstick with a clean rag Insert the dipstick into the o...

Страница 29: ...CAUTION Do not tilt the generator when adding engine oil Tilting the generator to assist in filling will cause oil to flow into engine areas and will cause damage Keep generator level Refer to the ADD...

Страница 30: ...round the spark plug base then re gap the spark plug 7 Screw the spark plug back into the spark plug hole using the spark plug wrench Do not over tighten spark plug Recommended tightening of spark plu...

Страница 31: ...cleaner element will cause the engine to wear out prematurely 1 Loosen the screws and remove the access panel 2 Remove the clip holding the air filter cover Take out the air filter cover and foam elem...

Страница 32: ...filter case so there is no air leak The engine should never run without the element excessive piston and cylinder wear may result Never use solvent while smoking or in the vicinity of an open flame R...

Страница 33: ...ging or scratching of muffler screen and spark arrester 5 Check the muffler screen and spark arrester Replace them if damaged 6 Reinstall the spark arrester and muffler screen and the muffler cap 7 Re...

Страница 34: ...s and dangerous causing severe burns etc It contains sulfuric sulphuric acid Avoid contact with skin EYES or clothing Antidote EXTERNAL Flush with water INTERNAL Drink large quantities of water or mil...

Страница 35: ...3 6 in the access panel but donot tighten it fully 3 put the screw 2 5 in the access panel but donot tighten it fully 4 tighten all screws well 11 Start generator without any device connected to it un...

Страница 36: ...ove the spark plug pour about one table spoon of SAE 10W30 or 20W40 motor oil into the spark plug hole and reinstall the spark plug 2 Pull the Choke knob to out OFF position Recoil start the engine by...

Страница 37: ...he fuel in the tank Not enough oil in crankcase Add or replace engine oil Spark plug is dirty or wet Remove carbon or wipe spark plug dry Spark plug is broken Replace spark plug Generator is not on le...

Страница 38: ...cal devices connected Bad connecting wires cables If using an extension cord try a different one Bad electrical device connected to generator Try connecting a different device Generator is overloaded...

Страница 39: ...39 WIRING DIAGRAM...

Страница 40: ...A112004 1 7 1 8 30A Socket 1 A112004 1 8 1 9 20A Socket 1 A112004 1 9 1 10 30A AC Protector 1 A112004 1 10 1 11 20A AC Protector 1 A112004 1 11 1 12 DC Protector 1 A112004 1 12 1 13 USB Port 8 A11200...

Страница 41: ...Muffler Cover 1 A112004 2 3 2 4 Wheel 2 A112004 2 4 2 5 Cross Screw M6X30 4 A112004 2 5 2 6 M10x70 Flange Bolt 2 A112004 2 6 2 7 Bushing 2 A112004 2 7 2 8 Wheel Support 2 A112004 2 8 2 9 Hexagonal Nut...

Страница 42: ...112004 3 7 3 8 Hexagonal Flange Bolt 51 A112004 3 8 3 9 Limit Speed Part 1 A112004 3 9 3 10 Support Frame 1 A112004 3 10 3 11 Inverter Board 1 A112004 3 11 3 12 Hexagonal Flange Bolt M6x25 4 A112004 3...

Страница 43: ...rt 1 A112004 3 29 3 30 Push Handel Box 1 A112004 3 30 3 31 Right Panel 1 A112004 3 31 3 32 Top Cover 1 A112004 3 32 3 33 Tank Mouth Rubber 1 A112004 3 33 3 34 Mirror 1 A112004 3 34 FIG 4 Fuel Tank Com...

Страница 44: ...A112004 5 3 5 4 Hexagonal Flange Nut M14 1 A112004 5 4 5 5 Stator 1 A112004 5 5 5 6 Hexagonal Flange Bolt M6x 55 4 A112004 5 6 5 7 Rotor 1 A112004 5 7 5 8 Flange Nut M6 X 18 4 A112004 5 8 5 9 Alterna...

Страница 45: ...A112005 1 7 1 8 30A Socket 1 A112005 1 8 1 9 20A Socket 1 A112005 1 9 1 10 30A AC Protector 1 A112005 1 10 1 11 20A AC Protector 1 A112005 1 11 1 12 DC Protector 1 A112005 1 12 1 13 USB Port 8 A11200...

Страница 46: ...Muffler Cover 1 A112005 2 3 2 4 Wheel 2 A112005 2 4 2 5 Cross Screw M6X30 4 A112005 2 5 2 6 M10x70 Flange Bolt 2 A112005 2 6 2 7 Bushing 2 A112005 2 7 2 8 Wheel Support 2 A112005 2 8 2 9 Hexagonal Nut...

Страница 47: ...112005 3 7 3 8 Hexagonal Flange Bolt 51 A112005 3 8 3 9 Limit Speed Part 1 A112005 3 9 3 10 Support Frame 1 A112005 3 10 3 11 Inverter Board 1 A112005 3 11 3 12 Hexagonal Flange Bolt M6x25 4 A112005 3...

Страница 48: ...rt 1 A112005 3 29 3 30 Push Handel Box 1 A112005 3 30 3 31 Right Panel 1 A112005 3 31 3 32 Top Cover 1 A112005 3 32 3 33 Tank Mouth Rubber 1 A112005 3 33 3 34 Mirror 1 A112005 3 34 FIG 4 Fuel Tank Com...

Страница 49: ...A112005 5 3 5 4 Hexagonal Flange Nut M14 1 A112005 5 4 5 5 Stator 1 A112005 5 5 5 6 Hexagonal Flange Bolt M6x 55 4 A112005 5 6 5 7 Rotor 1 A112005 5 7 5 8 Flange Nut M6 X 18 4 A112005 5 8 5 9 Alterna...

Отзывы: