Integrated Access Controller – Installation manual
All rights reserved. © AAT HOLDING S.A.
15
Programming the controller in network mode
Controller KZ-1000-IP can operate in stand-alone mode or network mode
under the supervisory software installed on computer.
It is also possible operation of the controller in the "off-line" after programming
with the supervisory software when the controller is connected through an IP
port.
Supervisory program on PC gives a much more powerful programming and mon-
itoring system based on controllers KZ-1000-IP. A detailed description of control-
ler programming in network mode refer to the instructions for the program
KaDe Premium Plus
and the help files dynamically displayed on the operator
panel.
General guidelines for the installation of the controller
Before installing the controller should be familiar with this manual.
Installation of the controller can be performed only by qualified personnel
with the appropriate certified to install and service this type of equipment.
The controller must be installed within a protected space at a temperature
of above + 2 ° C and normal humidity.
Controllers in the system should be located so that the minimum distance
from cables and high-voltage devices and other devices that generate elec-
trical noise was 2 m. The minimum distance from telephone lines should be
1 m, and from 8 m transmitting devices.
As the housing of the controller is equipped with a tamper sensor so care
must be taken to the surface for mounting the controller housing it was
hard and smooth.
The controller should be powered from a linear power supply with backup
battery with parameters. 12 VDC, 1A. This takes into account the possible
supply of an electric lock with the same power supply. In this case the at
the lock terminals should be installed diode 1N4004 in the reverse direction.
Wiring and performing any work on the internal components of the control-
ler while power is categorically prohibited. This can lead to damage.
Before connecting the controller to the power supply must perform all the
necessary connections in accordance with the instructions.
The connection to the computer is to be implemented using the IP port.
Each controller must be set to a different IP address.