LCD SCREENS
Copeland VFD Screens
Copeland VFD Screens
Refer to the following map when navigating through the
Copeland VFD Screens. From the Copeland VFD Screen, press
<ENTER>
to scroll through the screens.
COPELAND
ENVELOP<
2700 RPM
MINIMUM COMPRESSOR SPEED LIMIT
Minimum compressor envelope speed in RPM.
ENVELOP>
4500 RPM
MAXIMUM COMPRESSOR SPEED LIMIT
Maximum compressor envelope speed in RPM.
ENABLE
ON/OFF
COMPRESSOR ENABLED
ON,OFF or NO RESP
Compressor enable read from VFD.
SPEED
0 RPM
CURRENT SPEED OF COMPRESSOR
Compressor speed read from VFD in RPM.
When in Force Mode, speed can be adjusted from this screen by
using the UP and DOWN arrow keys.
REG 78 thru 85
0
COPELAND VFD FAULT CODES 78 THROUGH 85
Used for troubleshooting faults.
See Copeland manual for descriptions.
TO CLEAR
FAULT:UP
CLEAR FAULT
To clear faults at the VFD, press the <UP> button. Faults will auto-
matically clear after five minutes on their own.
MODEL#
MODEL NUMBER
Displays compressor model number that is configured into the drive.
Model number must match compressor to ensure safe speed limit
and current limit operation.
I LIMIT
8.7AMPS
CURRENT LIMIT SETPOINT CONFIGURED
Current limit threshold of specified compressor model in Amps.
CURRENT
CURRENT AMPS
Live current reading of compressor in Amps.