10
RSMVQ2R Technical Guide
INPUTS AND OUTPUTS
RSMVQ2R Module Inputs/Outputs Map
Inputs/Outputs Map
See
Table 2, this page
for the RSMVQ2R inputs and outputs
.
Table 2: RSMVQ2R Inputs and Outputs
REFRIGERATION SYSTEM MODULE
FOR VFD HEAT PUMP COMPRESSORS
Analog Inputs
1
Head Pressure Sensor 1 (HP1)
2
Head Pressure Sensor 2 (HP2)
3
Discharge Temperature 1 (TEMP1)
4
Saturation Temperature 2 (TEMP2)
5-6
Not Used (TEMP3) (TEMP4)
Binary Inputs
1
Compressor Status 1 (BIN1)
2
Compressor Status 2 (BIN2)
3
Not Used (BIN3)
4
Not Used (BIN4)
Analog Outputs (0-10 VDC)
1
Condenser Fan 1 (AOUT1)
2
Condenser Fan 2 (AOUT2)
DMQ EXV COMM Ports
1
Expansion Valve 1 (EXV-1)
2
Expansion Valve 2 (EXV-2)
3
Not Used (EXV-3)
4
Not Used (EXV-4)
Binary Outputs (24 VAC)
1
Compressor 2 Enable Relay (RLY1)
2
Compressor 2 High Speed Relay (RLY2)
3
Condenser 1 Enable Relay (RLY3)
4
Condenser 2 Enable Relay (RLY4)
Communication Terminals
DUAL
E-BUS
2 EBC E-BUS Ports
MODBUS
MODBUS Communication Terminal Block