AAON Orion ASM01824 Скачать руководство пользователя страница 8

CO

SENSOR

Technical Guide

 

8

Troubleshooting

Setting the Sensor Address Switch

LED ON/OFF Push-Button Operation for Setting

Address

The LED ON/OFF Push-Button is used to set the CO

2

 Sensor’s address. 

The LED ON/OFF Push-Button is located on the Sensor’s board and is 
only visible by removing the back cover. See location in

 Figure 6

. The 

default addresses are as follows:

• 

Space or Return CO

2

 Sensor = Address 1 (Default)

• 

Address 2 is reserved.

• 

Open addresses for Custom Applications = Addresses 3-10

To set the address, follow these instructions:

1.  Power up the VCM-X Controller that the Sensor is plugged 

into.

2.  Press the LED ON/OFF Push-Button for 5 seconds until the 

LEDs turn off .

3.  Then press the push-button the number of times that repre-

sents the address. Press once for address 1, press twice for 
address 2, etc.

4.  The address range can be set to 1 (default) and from 3 to 10.
5.  To verify that the correct address has been entered, refer to 

the STATUS LED information below.

The board address is stored in nonvolatile memory. Once the address is 
set, the address will be saved after loss of power.

Using LEDs to Troubleshoot 

LEDs are available for troubleshooting the CO

2

 Sensor. The Front LED 

is visible through the front cover of the CO

2

 Sensor. See 

Figure 7

 for 

location. The other LEDs are located on the Sensor’s board and are only 
visible by removing the back cover. See 

Figure 6

 for locations. 

LED ON/OFF Push-Button

This button is located on the CO

Sensor’s board. See 

Figure 6

. This 

button is initially set for “LEDs OFF.” Push this button to enable/disable 
the LEDs. Pushing this button ON will make the Front LED light up. 
This LED is also used for setting the address.  

Front LED

When the LEDs are turned on, a green LED will be visible through the 
front plastic cover of the CO

2

 sensor. See 

Figure 7

. The Front LED 

will blink whenever a CO

2

 sample is taken. A sample is taken every 

30 seconds.

STATUS LED

Initially, the STATUS LED blinks fast for 30 seconds. It then stays on 
and blinks the board address whenever a CO

2

 sample is taken. A CO

2

 

sample is taken once every 30 seconds.

COMM LED

The COMM LED blinks on whenever communications are sensed.

Altitude Correction

Altitude correction can be confi gured using one of our operator inter-
faces. The altitude can be confi gured at a value of 0-15,000 feet. The 
default is 500 feet. 

Содержание Orion ASM01824

Страница 1: ...I2 C CO2 Sensor Technical Guide ...

Страница 2: ...18 382 6450 Controls Support Phone 866 918 1100 AAON P N G042470 Rev 01F Copyright August 2019 AAON Inc AAON is a registered trademark ofAAON Inc Tulsa OK AAON assumes no responsibility for errors or omissions This document is subject to change without notice PART NUMBER TABLE PART DESCRIPTION AAON P N Wall Mounted I2 C CO2 Space Sensor ASM01824 Duct Mounted I2 C CO2 Sensor RA or SA ASM01826 I2 C ...

Страница 3: ... box to sample the CO2 level in the duct Some typical applications are Controlling ventilation in a building where the occupancy varies frequently Controlling ventilation to ensure excess outdoor air is not causing energy waste Ensuring good air distribution throughout building zones Demand Control Ventilation Sensor Overview Features The CO2 Sensor provides the following Uses the patented dual be...

Страница 4: ... with the CO2 Sensor is a mounting plate that can be used if necessary to cover the sensor sheet rock opening This mounting plate screws onto the back of the housing base The mounting plate is then mounted and covers the recessed space in the wall A locking screw secures the sensor to the wall See Figure 8 page 10 for mounting plate dimensions Wiring to the HVAC Unit Controller The Wall Mounted Sp...

Страница 5: ...sensing the current CO2 level in the HVAC unit s return air stream The return air sensing use of this sensor is applied when you want an average CO2 reading in the area served by the HVAC unit or when you don t want a wall mounted CO2 Sensor due to sensor tampering concerns in the space The OE256 02 Duct Mounted CO2 Sensor is designed to be mounted in the return air duct of the HVAC unit and uses ...

Страница 6: ...ale cable connector s and cable s through the cable clamp opening and into the Aspiration Box using the appropriate length of pre fabricated TSDRSC cable s as required by your applica tion STEP 3 Remove the CO2 Sensor cover with circuit board by using the included Allen wrench to loosen the set screw located at the bottom edge of the CO2 Sensor assembly and pulling the Sensor cover with circuit bo...

Страница 7: ...Technical Guide CO2 SENSOR 7 Figure 5 Mounting and Cable Installation for Duct Mounted CO2 Sensor Duct Mounted CO2 Sensor Installation ...

Страница 8: ...ll be saved after loss of power Using LEDs to Troubleshoot LEDs are available for troubleshooting the CO2 Sensor The Front LED is visible through the front cover of the CO2 Sensor See Figure 7 for location The other LEDs are located on the Sensor s board and are only visible by removing the back cover See Figure 6 for locations LED ON OFF Push Button This button is located on the CO2 Sensor s boar...

Страница 9: ... and the sensor and controller are powered up Directions Set the meter for DC volts and connect the GND probe to the GND terminal and the probe to the CO2 0 5 terminal Look at the output voltage and record it Multiply the voltage times 400 The value should match the CO2 as read on the System Manager TS Modular System Manager Modular Service Tool or Prism If the signal doesn t match the sensor read...

Страница 10: ...he sensor sheet rock opening This mounting plate screws onto the back of the housing base The mounting plate is then mounted and covers the recessed space in the wall A locking screw secures the sensor to the wall See Figure 8 below for dimensions 1 638 1 810 0 882 1 407 1 842 0 733 2 110 2 920 0 810 R0 220 3 275 0 060 0 160 5 037 3 278 3 766 4 153 Figure 8 Mounting Plate Dimensions ...

Страница 11: ...Technical Guide CO2 SENSOR 11 Notes ...

Страница 12: ...ts Reserved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM central standard time NOTE Before calling Technical Support please have the model and serial number of the unit available PARTS For replacement parts please contact your local AAON Representative ...

Отзывы: