E-BUS Digital Room Sensor Technical Guide

 

                                  

  APPENDIX

15

Connecting a Remote Sensor

Connecting a Remote Sensor

If the job requires this Sensor to be mounted outside of a conditioned 
space, a remote Standard Space Sensor (ASM02227) or Return Air Tem-
perature Sensor (P87140), or any 2-wire 10K Ohm, Type III thermistor 
temperature sensor can be hard-wired to the E-BUS Digital Room Sen-
sor.  Other versions of the AAON standard space sensors (ASM01638, 
ASM01642, ASM01643) with slide adjust and/or override button should 
not be used as the remote sensor.

Contact AAON Controls for wiring information if a four sensor averag-
ing array will be used as the “remote sensor”. 

See 

Figure 21

 for Return Air Temperature Sensor wiring. See 

Figure 

22, page 16

 for Space Sensor wiring. 

E-BUS Digital Room Temperature Only Sensor

Disconnect the modular cable from the E-BUS Digital Room Sensor 
before performing the following modifi cations.

If using the Temperature Only version of the Digital Room Sensor, you 
must fi rst remove the Sensor’s back cover. You will see a loop of wire 
hanging off  of the sensor circuit board. See 

Figure 23, page 17

. This is 

the external thermistor loop wire. Clip the external thermistor loop wire 
so that the sensor will read the remote temperature input.  Be sure to cut 

 Figure 21:  Return Air Temperature Sensor Wiring

the ends of the wire close to the circuit board so that the sensor loop wire 
ends won’t short between each other. The remote sensor then wires to the 
remote sensor terminal block on the back of the Digital Room Sensor. 

If using the Standard Space Sensor as the remote sensor, you must clip 
off  the C1 capacitor from the back of the Sensor  Be sure to cycle power 
to begin reading the remote sensor. See 

Figure 22, page 16

.

E-BUS Digital Room Temperature and Humidity 

Sensor

Disconnect  the  modular  cable  from  the  Digital  Room  Sensor  before 
performing the following modifi cations.

If using the Temperature and Humidity versions of the Digital Room 
Sensor, you only need to wire the remote sensor to the remote sensor 
terminal block on the Digital Room Sensor.  DO NOT CLIP OFF OR 
REMOVE  the  temperature/humidity  sensor  element  on  the  Digital 
Room Sensor. See 

Figure 24, page 17

.  When the remote temperature 

sensor is wired in, it will override the on-board temperature value of the 
Digital Room Sensor, even though the sensor element remains attached.  

If using a Standard Space Sensor as the remote sensor, you must clip off  
the C1 capacitor from the back of the sensor.  Be sure to cycle power to 
begin reading the remote sensor. See 

Figure 22, page 16

.

Содержание Orion ASM01819

Страница 1: ...E BUS Digital Room Sensor Technical Guide...

Страница 2: ...Controller 14 Connecting a Remote Sensor 15 Mounting Plate Dimensions 18 PART NUMBER CROSS REFERENCE TABLE PART DESCRIPTION AAON P N E BUS LCD Digital Room Sensor Temp Only ASM01819 E BUS LCD Room Se...

Страница 3: ...isplays the Current Space Temperature Displays Outdoor Air Temperature if controller is con gured with an OA Temperature Sensor Features Figure 1 ASM01819 ASM01820 E BUS Digital Room Sensor with LCD D...

Страница 4: ...a button has been pressed See Figure 3 for LED and Button Descriptions An icon for the current mode of operation will appear in the sensor display The operation mode icons are a Snow ake for Cooling...

Страница 5: ...The mounting plate is then mounted and covers the recessed space in the wall A locking screw secures the sensor to the wall See Figure 25 page 18 for dimensions Environmental Requirements The E BUS Di...

Страница 6: ...ng of the slide o set and an icon for the current mode of operation once the controller it is connected to is done calibrating The di erent icons shown are a Snow ake for cooling mode a Flame for heat...

Страница 7: ...If the VAV Zone or Unit Controller s slide o set setpoint is set to Zero this screen will not appear when you touch or Figure 9 Operation Mode Screens Cooling Mode with Snow ake Icon Heating Mode wit...

Страница 8: ...TROUBLESHOOTING E BUS Digital Room Sensor Technical Guide 8 Troubleshooting the Temperature Only Sensor Figure 10 Temperature Resistance Testing for ASM01819 Temperature Only Sensor...

Страница 9: ...52500 15 45902 20 40147 25 35165 30 30805 35 27140 40 23874 45 21094 50 18655 52 17799 54 16956 56 16164 58 15385 60 14681 62 14014 64 13382 66 12758 68 12191 69 11906 70 11652 Temperature Resis tanc...

Страница 10: ...ens Sensor Configuration and Test Screens To access the Sensor Configuration Test Screens you rst need to access the Unit Information Screen by touching Display while at the Main Display Screen NOTE W...

Страница 11: ...new temperature reading Touch to increase the number of seconds and touch to decrease the number of seconds To exit this screen touch Dis play NOTE The sensor takes the average of the last 10 reading...

Страница 12: ...er Wiring The E BUS Digital Room Sensor connects to the VCCX2 or VCB X Controller with the EBC E BUS expansion cable The E BUS Digital Room Sensor should be mounted at approximately 5 Ft above the oor...

Страница 13: ...applica tions requiring both a room CO2 sensor and room temperature sensor It should be mounted at approximately 5 Ft above the oor on the wall in an area that does not have drafts or is exposed to di...

Страница 14: ...l Room Sensor connects to the VAV Zone Controller with an EBC E BUS expansion cable It can also be hard wired to the VAV Zone Controller The E BUS Digital Room Sensor should be mounted at approximatel...

Страница 15: ...mistor loop wire so that the sensor will read the remote temperature input Be sure to cut Figure 21 Return Air Temperature Sensor Wiring the ends of the wire close to the circuit board so that the sen...

Страница 16: ...APPENDIX E BUS Digital Room Sensor Technical Guide 16 Connecting a Remote Sensor Figure 22 Attaching the ASM02227 Space Room Sensor...

Страница 17: ...Room Sensor Technical Guide APPENDIX 17 Connecting a Remote Sensor Figure 23 Wire Clipping Instructions For Digital Room Temperature Only Sensor Figure 24 Instructions For Digital Room Temperature Hu...

Страница 18: ...al Mounting Plate Included with the Digital Room Sensor is a mounting plate that can be used if necessary to cover the sensor sheet rock opening This mounting plate screws onto the back of the housing...

Страница 19: ...E BUS Digital Room Sensor Technical Guide NOTES 19...

Страница 20: ...ts Reserved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM central standard time NOTE Before calling Techn...

Отзывы: