-31-
producer, country of production) to
. May
be it would be possible to get newer information.
7.2. Measured discharge method
Warning.
Measured discharge should be done by the
qualified user who studied the present manual and who dis-
tinctly understands the sequence and probable results of the
action.
Measured discharge method of Qulon adjustment is
based on the comparison of estimated battery capacity pro-
duced by Qulon with calibration coefficient K=1 and meas-
ured discharge data for the same battery. This method is the
most correct. Nevertheless the accuracy of the method is
strongly dependent on the accuracy of measured discharge.
Therefore you need to use a special device (device
set) for measured discharge with the characteristics not
worse then following: discharge current stabilization (error < 3
%) or discharge current registration (error < 1 %, sampling
rate < 1 minute); automatic cut off with cut off voltage 10.5 V;
automatic discharge time registration (error < 1 %).
To get the most accurate result keep the battery under
room temperature for time needed for temperature equalizing.
Charge battery in full and keep it under float charge at
least for 24 hours. Disconnect battery from the charger and
from any loads. After 20-30 minutes (or