DESCRIPTION
This Signal Conditioner allows analog voltage levels to be set and read
via its RS-232 serial port. Commands are provided to perform various
functions: an analog output, read an analog input, verify the communica-
tions link, programming, and enter calibration mode.
(c)
FEATURES
The
I/O
is capable of operating in a voltage output mode or a current out-
put mode. When operating in the voltage mode the analog input and out-
put range is 0.00 to 5.00 volts. In the current mode the analog input and
output range is 4.00 to 20.0 milliamps. See Selecting the Operating Mode.
(d)
SPECIFICATIONS
d.1
General Attributes
INPUT AND OUTPUT ANALOG RANGE:
0 - 5 Vdc or 4 - 20 mA, jumpers selectable.
INPUT OVERVOLTAGE/OVERCORRECT PROTECTION:
15 Vdc, 50 mA.
MINIMUM OUTPUT VOLTAGE COMPLIANCE IN 4-20 mA MODE:
8 Vdc.
MAXIMUM INPUT VOLTAGE DROP IN 4-20 mA MODE:
5 Vdc.
POWER SUPPLY REQUIREMENTS:
10 to 30 Vdc, less than 0.75 watts (OPTIONAL).
OPERATING TEMPERATURE RANGE:
0
F
C to 70
F
C.
ALTITUDE:
to 10,000 feet.
DIGITAL VOLTAGE STANDARD:
RS-232 or RS-485 (not galvanically isolated).
COMMUNICATIONS PARAMETERS:
8 bits, one stop bit no parity (N,8,1).
RS-232 COMMON MODE CAPABILITY:
+10 volts.
RESOLUTION:
10 bits (0.1%).
DATA FORMAT:
ASCII.
DATA TRANSFER RATE:
300 baud to 9600 baud.
MODULE CONNECTION METHOD:
Pinch Type terminals.