9.0  Local Readout

The LCD on the front of the Communications Module has six (6) 

screens. 

1. The standard the device is currently configured to. The  

  Communications Module standard is set by the factory to the  

  standard of your choice. the choices in the standards are:   

    - Legacy Corrosion Control (ISA 71.04-1985)  

    - RoHS Corrosion Control (ASHRAE TC 9.9) 

    - or Museum & Archive  

  **Display charts of each standard, those on last page of SAAFShield brochure   

     GPF-1-140.

2. Temperature (ºC) and Relative Humidity (%)

3. Copper Corrosion Classification for the past 24 hours and the past   

  30 days

4. Silver Corrosion Classification for the past 24 hours and  the past  

  30 days

5. Summary of the Environment’s Classification. This will report the  

  harshest of the classifications for the standard used

6. transmitting

 19.  Transmit Relative Humidity measurement in the range of 4-20mA  

    for 5 seconds.
 20.  Wait 2 seconds.
 21.  Send two 8.58 mA pulses of 1 second each with inter-pulse  

    pause of 1 second (set loop to 4mA during pause)
 22.  Wait 2 seconds.
 23.  Transmit Temperature measurement in the range of 4-20mA  

    for 5 seconds.
 24.  Wait 2 seconds.
 25.  Send two 8.58 mA pulses of 1 second each with inter-pulse  

    pause of 1 second (set loop to 4mA during pause)
 26.  Wait 2 seconds.
 27.  transmit the fault data for 5 seconds.

 

    6 to 8 mA: 

Power supply out of tolerance

    8 to 10 mA: 

Copper out of range

    10 to 12 mA:  Silver out of range
    12 to 14 mA:  Gold out of range
    14 to 16 mA:  Self diagnostic failed, replace board
    16 to 18 mA:  Invalid time/date
    18 to 20 mA:  other errors

Содержание SAAFShield

Страница 1: ...e AAF International SAAFShield Communications Module These instructions must be carefully followed in order to operate the unit safely and correctly If there are any questions regarding the use or car...

Страница 2: ...o read compute and transmit corrosion temperature and relative humidity data Ribbon Connector to SAAFShield DU Ribbon Connector to SAAFShield RU Connector for Power and 4 20 mA Output Menu Bottons Up...

Страница 3: ...hould be placed after the final particulate filter This will protect it from the majority of particulates and allow it to monitor the condition of the outlet air When the rate of corrosion begins incr...

Страница 4: ...rease the setting of that field 5 Use the OK button to select the value and scroll to the next field 6 If Exit EXT field is reached using the OK button press either UP or DOWN to exit from menu system...

Страница 5: ...ading Error Real Error Code Cycle Every 15 minutes the SAAFShield Communications Module sends data to the analog input SigIn It sends the start signal for 3 seconds waits 2 seconds and then begins dat...

Страница 6: ...of the Environment s Classification This will report the harshest of the classifications for the standard used 6 Transmitting 19 Transmit Relative Humidity measurement in the range of 4 20mA for 5 sec...

Страница 7: ...FShield Parts List It is recommended that the following spare parts be stored at the installation site for replacement purposes Consult with your AAF representative to determine actual quantities requ...

Страница 8: ...F 3 118 NOV 13 AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice ISO Certified Firm 2013 AAF International The U...

Отзывы: