Reading Unit Connector

Detecting Unit Connector

4-20 mA

Connector

5.0  Connecting to 4-20 mA Output

the unit connects to the host control/monitoring system via a standard 

“3-wire” analog loop.
there are three terminals for this connection labeled as follows:
•   +24V  Positive  24 VDC
•   GND 

24 VDC common

•   4-20mA  

Signal to the analog input of the host system. 

The 24 VDC power for the unit must be connected to the same source 

as the host control/monitoring system, and in particular the 24 VDC 

common (GND) must be the same as is used for reference by the 

analog input module in the host control/monitoring system. (Figure 4)

1.  the Communications Module will not enter the menu system if  

data is being transmitted.  transmitting notice will be shown on  

the LCD display.

2.  Press any of the three buttons to enter the menu system.  If the  

unit is not transmitting data, you will enter the menu system  

immediately.  If the unit is transmitting data, you will enter the  

menu system once the transmitting procedure is complete.

3.  When the Communications Module is in the menu, the selected 

field will blink.

4.  Use the UP and DOWN buttons to increase /decrease the setting  

of that field.

5.  Use the OK button to select the value and scroll to the next field.
6.  If Exit (EXT) field is reached using the OK button, press either  

UP or DOWN to exit from menu system back into main mode.

7.  After setting the time and date, it is recommended to initialize the 

sensors.  once you leave the time/ date setup menu, the device 

will ask if the sensors should be initialized.  Press the UP button to 

initialize the sensors or press DOWN to exit the menu system.

Note: The Communications Module will conduct the next data  

transmission when the scheduled time comes though the LCD  

display will NOT change to show this transmission. The red LED  

on the left of the LCD display will blink at a faster rate when the  

transmission is taking place.

7.0  Programming Instructions

When programming your building management software to receive  

the 4-20 mA signal from the SAAFShield CM, you can utilize three 

different languages:  structured text, ladder logic, and function block 

diagram.  Please refer to AAF document SAAFShield Appendix  

GPF-3-118, “Detailed Programming Instructions for SAAFShield  

Communications Module.” 

Up Button

Down Button

OK Button

6.0 Menu System

the SAAFShield Communications Module has three push buttons  

to the right of the LCD display (Figure 5). Press any button to enter  

the menu. 

Figure 5. 

Figure 4. 

Содержание SAAFShield

Страница 1: ...e AAF International SAAFShield Communications Module These instructions must be carefully followed in order to operate the unit safely and correctly If there are any questions regarding the use or car...

Страница 2: ...o read compute and transmit corrosion temperature and relative humidity data Ribbon Connector to SAAFShield DU Ribbon Connector to SAAFShield RU Connector for Power and 4 20 mA Output Menu Bottons Up...

Страница 3: ...hould be placed after the final particulate filter This will protect it from the majority of particulates and allow it to monitor the condition of the outlet air When the rate of corrosion begins incr...

Страница 4: ...rease the setting of that field 5 Use the OK button to select the value and scroll to the next field 6 If Exit EXT field is reached using the OK button press either UP or DOWN to exit from menu system...

Страница 5: ...ading Error Real Error Code Cycle Every 15 minutes the SAAFShield Communications Module sends data to the analog input SigIn It sends the start signal for 3 seconds waits 2 seconds and then begins dat...

Страница 6: ...of the Environment s Classification This will report the harshest of the classifications for the standard used 6 Transmitting 19 Transmit Relative Humidity measurement in the range of 4 20mA for 5 sec...

Страница 7: ...FShield Parts List It is recommended that the following spare parts be stored at the installation site for replacement purposes Consult with your AAF representative to determine actual quantities requ...

Страница 8: ...F 3 118 NOV 13 AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice ISO Certified Firm 2013 AAF International The U...

Отзывы: