6. Operating Conditions

7. Operating & Commissioning

AstroFan FFU is designed to for moving clean air with low concen-
trations of dust or aerosols, as well as slightly aggressive gases and 

vapours up to a density of 1.3 kg/m³.

Operating temperature to be between -30 

o

C and +40 

o

C. Relative 

humidity to be below 95% to avoid condensation.

Avoid intrusion of water.

Do not operate in explosion hazard areas.

Switching frequencies:

The fan is designed for S1 constant operation.

Avoid operations at the outer range limits of the control equipment.

Observe the special instructions for the EC motors and controls

If the leakage current exceeds 3.5 mA, the equipment has to be 
earthed in accordance with DIN VDE 0180/5.88, Par. 6.5.2.1.

Before initial operation the following checks need to be carried out:

•  Installation and electrical connections are completed and have 
  been carried out in accordance with instructions.

• 

All safety equipment is properly installed and secured. (protection

 

  grills etc.)

•  Any debris and materials left-behind and other loose materials 
  have been removed from the FFU housing.

• 

Thermistors and/or motor cut out switches have been correctly

 

  connected and are functional.

•  Cable entry points are sealed.

• 

Nominal power consumption (as per nameplate) is not exceeded.

•  Connection data comply with the data from nameplate. See also  
  capacitor rating.

•  Keep inlet opening clear.

 
Switch fan into ‘on’ position in accordance with the switching 

arrangement and local conditions. Check for:

• 

Direction of fan rotation and airflow. The direction of rotation is

 

  always indicated with an arrow on the top of the AstroFan FFU  
 housing.

•  Check that the fan is running smoothly and in balance. 
 

The AAF AstroFan FFU will require very little maintenance.

Due to the selection of bearings with lifetime lubrication (by using a 

special lubricant), the FFU-fan does not require any maintenance. 
Under normal operating conditions the lifetime lubrication will 
provide a working life of 30-40,000 hours. After depletion of the 
lubricant, the entire bearing needs to be replaced.

Access to the fan and motor is gained from the top by lifting the 

FFU-housing from the HEPA/ULPA filter.

Periodic checks should be carried out on the filter resistance and 
also on the air volume / air velocity. Lifetime of AstroCel II HEPA/
ULPA filter and RedPleat pre filter depend on local operating 
conditions (velocity, working point, dust load and running hours) 

and cannot easily be predicted.

RedPleat pre filter final resistance is 250 Pa maximum. However 

AAF recommends a periodical check and replacement of the pre 

filter at, for example, 100 Pa to ensure optimal energy efficiency of 

the AstroFan FFU.

AstroCel II HEPA/ULPA final resistance depends on the available 

free static pressure of the AstroFan FFU in the cleanroom arrange-

ment. Depending on operating conditions (velocity, filter class and 
depth, working point, pre filter or other external static pressure 
elements) a free static pressure of 80-100 Pa is available.

All maintenance work should be carried out with the highest regard 

for safety. For access to the fan/motor the AstroFan FFU top plate 
needs to be lifted from its position and removed before the fan/

motor arrangement can be reached.

•  Ensure fan impeller is not moving.

•  Ensure power supply is interrupted and provisions are taken to    
  avoid accidental closure of circuit.

•  Ensure all working instructions are properly followed.

• 

Always keep fan unobstructed. Regular cleaning helps to prevent

 

  motor imbalance; use a cleaning brush where necessary.

• 

Do not use high-pressure cleaners (water, steam, and air)

•  Do not bend fan blades.

•  Monitor for unusual fan noise.

Change the fans at the end of their working life, or if a bearing is 

damaged. Bearings are not replaced. When required, the fan is 

replaced.

Replace AstroCel II HEPA/ULPA filter and RedPleat pre filter 
only by original AAF filters. Contact AAF International Filter Sales 

Department with reference of the part numbers that are always 

displayed on a label on the filters.

8. Maintenance

Содержание AstroFan Base

Страница 1: ...AstroFan Base Instruction Manual...

Страница 2: ...2...

Страница 3: ...Instructions 4 Transport Storage 5 Mechanical Installation 8 Network Connections 9 Operating Conditions 9 Operating Commissioning 9 Maintenance 10 Fault Finding 10 Manufacturer s Declaration of Confor...

Страница 4: ...e inlet grill and terminal HEPA ULPA filter must not be removed or by passed neither are they to be rendered inoperative The AAF AstroFan FFU is a self contained ceiling filter fan unit designed for u...

Страница 5: ...f the AstroFan fan top to carefully position the fan top onto the adapter frame Do not apply force The unit rests on the gasket of the adapter and seals by its own weight Mechanical fixtures are prefe...

Страница 6: ...fe edge into the gel seal Take care not to apply force to the filter media 5 Ensure all 4 strips are installed fully and the filter is firmly secured 4 Slide the support strips into the room side chan...

Страница 7: ...uilt in electronics connected with a bus line to the control unit or a PC operated visualized control All fans are dynamically balanced at two levels in accordance with VDI 2060 or DIN ISO 1940 Sectio...

Страница 8: ...n the electrical wiring can be connected at the terminal box on top of the housing Options When a pre filter is provided place pre filter into holding frame fan protection grill Pre filters do not req...

Страница 9: ...the lifetime lubrication will provide a working life of 30 40 000 hours After depletion of the lubricant the entire bearing needs to be replaced Access to the fan and motor is gained from the top by l...

Страница 10: ...error than this is a connection error Check if all connectors are properly connected Check the wiring especially of the RS485 network Check if the CCU AstroDrive has been connected correctly Check if...

Страница 11: ...Style code Size Part Number 1 2 3 4 5 Note The filter test report is attached to each individual AstroCel HEPA ULPA filter Please retain the report s and file together with this operating manual PLEAS...

Страница 12: ...94300 Vincennes Phone 33 1 43 98 42 23 sales france aafeurope com www aafeurope fr Greece AAF Environmental Control Epe Ifaistou Kikladon 15354 Glika Nera Tel 30 210 6632015 Greece aafeurope com www a...

Страница 13: ...M o AAF EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING 1162 1 1 350 1 1 392 562 1 1 150 HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS ROOM SIDE CHANGE ALUMINUM...

Страница 14: ...subject to conditions that shall not be reproduced copied loaned or submitted to outside parties without our written consent AAF Filter Fan Unit 612 TITLE B DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2...

Страница 15: ...EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING 1162 1 1 350 1 1 392 862 1 1 HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS ROOM SIDE CHANGE ALUMINUM BOTTOM 400...

Страница 16: ...conditions that shall not be reproduced copied loaned or submitted to outside parties without our written consent Filter Fan Unit 912 TITLE B DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2 1 6 ELECTRONIC...

Страница 17: ...NG NO mm SHEET UL o DO NOT SCALE DRAWING 1162 1 1 350 1 1 392 1162 1 1 HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS ROOM SIDE CHANGE ALUMINUM BOTTOM 400 mm OPTIONAL...

Страница 18: ...onditions that shall not be reproduced copied loaned or submitted to outside parties without our written consent AAF Filter Fan Unit 1212 TITLE B DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2 1 8 ELECTRON...

Страница 19: ...AAF EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS ROOM SIDE CHANGE ALUMINUM BOTTOM 310 mm OPTIONAL PRE FILTER S...

Страница 20: ...o conditions that shall not be reproduced copied loaned or submitted to outside parties without our written consent Filter Fan Unit 69 TITLE B DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2 1 6 ELECTRONIC...

Страница 21: ...ER FM o AAF EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS ROOM SIDE CHANGE ALUMINUM BOTTOM 310 mm OPTIONAL PRE F...

Страница 22: ...s that shall not be reproduced copied loaned or submitted to outside parties without our written consent Filter Fan Unit 66 TITLE B DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2 1 5 ELECTRONIC DOCUMENT PR...

Страница 23: ...UMENT PRINTED COPIES ARE UNCONTROLLED PRODUCT OWNER FM o AAF EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING 1162 1 1 350 1 1 392 562 1 1 150 HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FIL...

Страница 24: ...ons that shall not be reproduced copied loaned or submitted to outside parties without our written consent AAF Filter Fan Unit 612 K Box TITLE 0 DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2 1 6 ELECTRONI...

Страница 25: ...OLLED PRODUCT OWNER FM o AAF EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING 862 1 1 350 1 1 392 862 1 1 HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS ROOM SIDE...

Страница 26: ...conditions that shall not be reproduced copied loaned or submitted to outside parties without our written consent AAF Filter Fan Unit 99 TITLE 0 DATE SCALE PROJECT UNIT 2015026 A2 2 OF 2 1 6 ELECTRONI...

Страница 27: ...ONTROLLED PRODUCT OWNER FM o AAF EUROPE DRAWING NO mm SHEET UL o DO NOT SCALE DRAWING 1162 1 1 200 1 1 242 562 1 1 150 HOUSING MATERIAL FAN ACCESS TYPE FAN EC TYPE SIZE FILTER FAN UNIT SPECIFICATIONS...

Страница 28: ...subject to conditions that shall not be reproduced copied loaned or submitted to outside parties without our written consent AAF Filter Fan Unit 612 SL TITLE 0 DATE SCALE PROJECT UNIT 2015026 A2 2 OF...

Отзывы: