Notice to Users, Installers, Authorities Having Jurisdiction, and Other Involved Parties 
This product incorporates field-programmable software. In order for the product to comply with the requirements in 
the Standard for Control Units and Accessories for Fire Alarm Systems (UL1481), certain programming features or 
options must be limited to specific values or not used at all as indicated below: 

Program Feature or Option 

Permitted in UL? (Y/N) 

Possible Settings 

Settings Permitted in UL 

Power outputs that may be 
remotely controlled. 

Apply shunt to disable (Fig. 1a)

Remove shunt to enable (Fig. 1b) 

Apply shunt to disable 

(factory setting, Fig. 1a

Terminal Identification: 

Terminal/Legend 

Description 

Power Supply 1 

Interfaces with the first eFlow Power Supply/Charger. 

Power Supply 2 

Interfaces with the second eFlow Power Supply/Charger. 

RJ45 

Ethernet: LAN or laptop connection. Enables non-supervised LINQ2 programming and status monitoring. 

USB 

Enables temporary laptop connection for LINQ2 programming. Not to be employed for applications requiring UL listing. 

IN1, IN2, IN3 

Reserved for future use. Not evaluated by UL. 

NC, C, NO 

Two (2) network controlled Form “C” relays (contact rated @ 1A/28VDC resistive load). Use 14 AWG or larger. 

LINQ2 Installed Inside the eFlow, MaximalF or Trove Enclosure: 

Fig. 2 

Top edge of Enclosure 

LINQ2 bracket 

LINQ2 Side View 

LINQ2 Module 

L

 

G

 

N

 

NC 

NO 

NC 

NO 

BA

T F

AIL 

AC F

AIL 

AC 

AC1 

DC 

TRIGGER EO

L

SUPER

VISE

5A 250V 

disable

enable 

2 hr

.

1 min.

AC DELAY   

SHUTDOWN 

O N 

eFlow

 

Power

 

Supply/Charger

 

OFF  --- 24V 
ON  --- 12V 

ON

 

Please be sure to visit altronix.com for latest firmware and installation instructions. 

LINQ2

 - 3 ­

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Содержание LINQ2

Страница 1: ...lation instructions Ethernet Network Communications Module Installation and Programming Manual LINQ2 Two 2 Port Connectivity Module DOC LINQ2 Rev 060514 More than just power Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Страница 2: ...VDC resistive load Management interface software included USB flash drive Includes interface cables and mounting bracket Three 3 programmable input triggers Control relays and power supplies via external hardware sources Access control and user managment Restrict read write Restrict users to specific resources Installing LINQ2 Board 1 Using the mounting bracket mount the LINQ2 network module to th...

Страница 3: ...ger Power Supply 2 Interfaces with the second eFlow Power Supply Charger RJ45 Ethernet LAN or laptop connection Enables non supervised LINQ2 programming and status monitoring USB Enables temporary laptop connection for LINQ2 programming Not to be employed for applications requiring UL listing IN1 IN2 IN3 Reserved for future use Not evaluated by UL NC C NO Two 2 network controlled Form C relays con...

Страница 4: ...ned to the LINQ2 module by the network administrator to allow remote access and monitoring The default inbound port setting is 80 e Click the button labeled Submit Network Settings A dialog box will display New network settings will take effect after the server is rebooted Click OK After all information has been entered click on the button labeled Reboot Server A dialog box will display Please all...

Отзывы: