Notice to Users, Installers, Authorities Having Jurisdiction, and Other Involved Parties
This product incorporates field-programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems (UL1481), certain programming features or
options must be limited to specific values or not used at all as indicated below:
Program Feature or Option
Permitted in UL? (Y/N)
Possible Settings
Settings Permitted in UL
Power outputs that may be
remotely controlled.
N
Apply shunt to disable (Fig. 1a);
Remove shunt to enable (Fig. 1b)
Apply shunt to disable
(factory setting, Fig. 1a)
Terminal Identification:
Terminal/Legend
Description
Power Supply 1
Interfaces with the first eFlow Power Supply/Charger.
Power Supply 2
Interfaces with the second eFlow Power Supply/Charger.
RJ45
Ethernet: LAN or laptop connection. Enables non-supervised LINQ2 programming and status monitoring.
USB
Enables temporary laptop connection for LINQ2 programming. Not to be employed for applications requiring UL listing.
IN1, IN2, IN3
Reserved for future use. Not evaluated by UL.
NC, C, NO
Two (2) network controlled Form “C” relays (contact rated @ 1A/28VDC resistive load). Use 14 AWG or larger.
LINQ2 Installed Inside the eFlow, MaximalF or Trove Enclosure:
Fig. 2
Top edge of Enclosure
LINQ2 bracket
LINQ2 Side View
LINQ2 Module
L
G
N
NC
C
NO
NC
C
NO
BA
T F
AIL
AC F
AIL
AC
AC1
DC
TRIGGER EO
L
SUPER
VISE
D
5A 250V
disable
enable
2 hr
.
1 min.
AC DELAY
SHUTDOWN
O N
eFlow
Power
Supply/Charger
OFF --- 24V
ON --- 12V
ON
Please be sure to visit altronix.com for latest firmware and installation instructions.
LINQ2
- 3
Available from A1 Security Cameras
www.a1securitycameras.com email: [email protected]