WE/XE/SE/XC Series 

Quarter-Turn Electric Actuator 

Installation & Maintenance Manual  

 

 

 

11 

12/17/19 

www.atcontrols.com 

IOM8011 REVISION 01 

  

 

Wiring

 

 

  Remove actuator cover and ensure power supply 

voltage matches the nameplate or label, and that 
power supply is capable of providing the stated full 
load current.  

  Two conduit entries are provided on each actuator; 

one for power and the other for control signal.  

  A minimum of 18AWG wiring is recommended for all 

field wiring. 

  Wiring diagram showing terminations is provided in 

each actuator. 

  The actuator should be wired and grounded in 

accordance with local and national electrical codes. 

  Conduit should be sealed at the actuator housing to 

prevent water or moisture from entering the actuator 
through the conduit openings. 

  The compartment heater should be continuously 

energized to reduce accumulation of moisture 
withing actuator housing. 

  Unused conduit entries must be closed off with plug 

fitting approved for use per actuator enclosure 
ratings. 

 

CAUTION:

  

Each actuator must have its own independent 
control contact. Actuators wired in parallel will 
not operate properly and doing so may cause 
damage to the actuator.

 

 

  Terminals in -690 actuator accept maximum wire 

size of 16AWG. Terminals in -1350 thru -25900 size 
actuators accept maximum wire size of 14AWG. 

 

Press in spring clamp with small flat head 
screwdriver to open terminal for wiring.

 

 

 
 
 
 

  Grounding 

 
Internal and external ground connections are provided. 
 

Internal Ground 

 

Terminal Block #1 

 
 

External Ground 

 

 

 
 

  Operation 

 

6.3.1. General 

 
Manually operate the actuator to the 50% open position. 
Electrically operate the actuator to the fully Open (CCW) 
position. The motor should rotate actuator 
counterclockwise and then de-energize when the OLS 
cam trips the open position limit switch. 

 

Electrically operate the actuator to the fully Close (CW) 
position. The motor should rotate the actuator clockwise 
and then de-energize when the CLS cam trips the close 
position limit switch. 
 

Press 

Содержание Triad Controls WE Series

Страница 1: ...C Series Quarter Turn Electric Actuator Installation Maintenance Manual 1 12 17 19 www atcontrols com IOM8011 REVISION 01 Installation and Operation Manual WE XE SE 690 thru WE XE SE 25900 XC 00690 th...

Страница 2: ...al Features 5 Standard Model External Parts 6 4 4 1 Size 690 thru 10500 6 4 4 2 Size 17500 and 25900 6 4 4 3 Standard Model Internal Parts 6 Manual Operation Handwheel 7 Space Heater 7 5 Installation...

Страница 3: ...allation commissioning and operation of the electric actuator and who has appropriate qualifications which may include o Is trained in the operation and maintenance of electric equipment and system in...

Страница 4: ...output shaft Accurate positioning is achieved by the indicator cam shaft connecting directly to the output drive Standard Specification Enclosure WE Weatherproof IP67 CSA approved for NEMA 4 4X SE Su...

Страница 5: ...vo cards WE XE SE XC Series Additional Aux switches SPDT 250V AC 10A Rating WE XE SE Series SICU Semi integral control unit Local Remote Selector Switches WE XE SE Series except 690 ICU Intelligent Di...

Страница 6: ...s CAUTION The 690 size actuator does not contain torque switch assembly Forcing actuator into mechanical stops or preventing rotation in some other manner may damage motor Window Indicator Lever Hand...

Страница 7: ...ace Heater Condensation may form in the actuator due to change in ambient temperature Powering the internal space heater will help prevent this Standard heaters are ceramic with thermostat to prevent...

Страница 8: ...must be used To avoid backlash there should be no flexibility in the mounting Valve output shaft must be in line with actuator output drive to avoid side loading the shaft Operate with handwheel befor...

Страница 9: ...Hex Size 690 6mm 1350 1700 8mm 2640 4400 5200 10mm 6900 10500 10mm 17500 25900 10mm Limit Switch Setting WARNING Hazardous voltage Turn off all power and lock out service panel before installing or mo...

Страница 10: ...set the close mechanical stop bolt operate the actuator clockwise to the Close CW position until the CLS limit switch trips Tighten the close travel stop bolt until it stops on the secondary worm whe...

Страница 11: ...Unused conduit entries must be closed off with plug fitting approved for use per actuator enclosure ratings CAUTION Each actuator must have its own independent control contact Actuators wired in paral...

Страница 12: ...l limit switches 6 3 3 Jamming If the actuator travels into a mechanical travel stop the worm gear will jam Remove power from the command input Briefly apply power in the reverse direction to release...

Страница 13: ...to perform its intended function safely during its useful life However the purchaser or user of A T Controls products should be aware that A T Controls products might be used in numerous applications...

Отзывы: