If combustion measurements are not in the range specified, please repeat the Setting of the test mode and Maximum and 

Minimum fire adjustment procedure as described previously.

Start Up Record

Start-up Date ______________________

Model Number _____________________

Series Number______________________

Gas type:___________

Power supply voltage:    Hot /Gnd______ VAC, Hot /Neutral ______ VAC, Neutral /Gnd______ VAC

Maximum Fire

Minimum Fire

Inlet Gas Supply Pressure Inch W.C.
Manifold Pressure Inch W.C.

CO

CO PPM
O

%

Blower RPMs

Flue Gas Temp (°F)

Stack Pressure Inch W.C.

DISPOSITION

All tests and values specified must meet specifications prior to issuing this Start-up certificate. For any discrepancies, please 

explain below what action was taken to correct the problem.

 

 

 

 

 

NOTIFICATION 

All test and values specified must meet specifications prior to issuing this start-up certificate. For any of the field tests performed, 

explain below what action was performed to correct the problem. The owner has been notified that corrections must be made to 

this installation. The owner acknowledges that changes must be made within 30 days, prior to start up being completed.

 

 

 

Required Signature of Owner 

 

     Date 

 

Содержание VF VB 500

Страница 1: ...nch for setting gas mixture at gas valve 3mm or 7 64 in hex wrench for setting gas mixture at gas valve I Verify utilities Ensure that the water piping gas line controls and venting have been installe...

Страница 2: ...follows remove the flat round blue plastic cap from the cover Using a 3mm 7 64 hex wrench turn the adjustment screw counterclockwise to increase or clockwise to decrease gas flow and achieve the desir...

Страница 3: ...W C CO2 CO PPM O2 Blower RPMs Flue Gas Temp F Stack Pressure Inch W C DISPOSITION All tests and values specified must meet specifications prior to issuing this Start up certificate For any discrepanci...

Страница 4: ...E OR EQUIPMENT DAMAGE MAY OCCUR If the boiler is damaged due to any criteria not being met WARRANTY may not cover damaged parts or any labor allowances __________________________________ _____________...

Страница 5: ...e 7 64 po pour r gler le m lange gaz air la commande de gaz I V rification des services S assurer que la tuyauterie d eau et de gaz les commandes et les conduits de ventilation sont install s conform...

Страница 6: ...a chaudi re au mode d essai MAX tel que d crit ci dessus pour que le br leur fonctionne sa puissance maximale Analyser la composition du gaz de combustion au moyen de l appareil appropri Si les lectur...

Страница 7: ...__ Tension terre ______ V c a Tension neutre ______ V c a Neutre terre ______ V c a Niveau de combustion maximale Niveau de combustion minimale Pression du gaz l entr e kPa Pression au collecteur kPa...

Страница 8: ...di re est endommag e en raison d exigences non satisfaites la GARANTIE peut ne pas couvrir le co t de remplacement des pi ces endommag es ou les frais de main d uvre __________________________________...

Отзывы: