RESIDENTIAL GAS AND ELECTRIC WATER HEATER
SERVICE HANDBOOK
Residential Electric – continued
Three Phase – Unbalanced Circuit
SIMULTANEOUS DUAL ELEMENTS
(both elements ‘on’ when entire tank is cold)
Element
Wattage
Upper/Lower
Full Load Current in Amperes
Connected to Three Phase Power
(Terminal L2/ Terminals L1 & L3
208V
240V
480V
3000/3000 25.0/14.4
21.7/12.5 10.8/6.3
4000/4000 33.3/19.2
28.9/16.7 14.4/8.3
4500/4500 37.5/21.6
32.5/18.8 16.2/9.4
5000/5000 N/A
36.1/20.8
18.0/10.4
6000/6000 N/A N/A
21.7/12.5
(See A-7 Circuit)
3 Supply Wires
4 Element Wires
3 Supply Wires
6 Element Wires
Note:
Residential heaters may or may not offer the ability to wire elements for simultaneous
operation. If they are wired for non-simultaneous operation, amperage will be as if wired single
phase.
A.O. Smith Water Products Company
Technical Training Department
©
2005
Ashland City, TN
37
Содержание TC-049R3
Страница 69: ......