Instruction manual SGE
78
13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom
Cause
Solution
Remark
Gas smell
Gas leak
Warning
Close the main gas valve immediately.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Contact your installation engineer or local gas company
immediately.
Display is off
Appliance is turned off
Start the appliance up
(9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the SGE electrical diagram
(17 "Appendices")
If the error persists, consult your installation engineer.
Defective fuse(s)
Replace fuse(s)
To replace the fuses, you must contact your installation engineer.
Содержание SGE
Страница 1: ...40 60 Installation User and Service Manual Installation User and Service Manual...
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual SGE gis...
Страница 8: ...Table of contents 8 Instruction manual SGE...
Страница 12: ...Introduction 12 Instruction manual SGE 1 gis...
Страница 30: ...Installation 30 Instruction manual SGE 3 is Types of appliances...
Страница 48: ...Conversion to a different gas category 48 Instruction manual SGE 4 is...
Страница 49: ...Instruction manual SGE 49 gis 5 Filling Installation diagram...
Страница 53: ...Instruction manual SGE 53 gis 6 Draining Installation diagram...
Страница 64: ...Shutting down 64 Instruction manual SGE 10 gis...
Страница 92: ...Maintenance frequency 92 Instruction manual SGE 14 is...
Страница 101: ...Instruction manual SGE 101 is...
Страница 106: ...Appendices 106 Instruction manual SGE 17 is...
Страница 108: ...Instruction manual SGE 108...