Water supply systems may, because of such events as high line pressure,
frequent cut-offs, the effects of water hammer among others, have
installed devices such as pressure reducing valves, check valves, back
flow preventers, etc. to control these types of problems.  When these
devices are not equipped with an internal by-pass, and no other measures
are taken, the devices cause the water system to be closed.  As water is
heated, it expands (thermal expansion) and closed systems do not allow
for the expansion of heated water.

The water within the water heater tank expands as it is heated and increases
the pressure of the water system.  If the relieving point of the water heater’s
temperature-pressure relief valve is reached, the valve will relieve the
excess pressure.  

The temperature-pressure relief valve is not intended

for the constant relief of thermal expansion.

 This is an unacceptable

condition and must be corrected.

It is recommended that any devices installed which could create a closed
system have a by-pass and/or the system have an expansion tank to
relieve the pressure built by thermal expansion in the water system.
Expansion tanks are available for ordering through a local plumbing
contractor. 

 

Contact the local water supplier and/or a service agency for

assistance in controlling these situations.

NOTE:

 

To protect against untimely corrosion of hot and cold

water fittings, it is strongly recommended that di-electric unions
or couplings be installed on this water heater when connected
to copper pipe.

All gas piping must comply with local codes and ordinances or with the National
Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural Gas and Propane
Installation Code (CAN/CSA B149.1) whichever applies. Copper and brass
tubing and fittings (except tin lined copper tubing) shall not be used.

FIGURE 10.

CHEMICAL VAPOR CORROSION

CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF
AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH
CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.

Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium and
sodium chloride (water softener salt), waxes, and process chemicals
are typical compounds which are potentially corrosive.

Do not store products of this sort near the heater. Also, air which is
brought in contact with the heater should not contain any of these
chemicals. If necessary, uncontaminated air should be obtained from
remote or outside sources. The limited warranty is voided when failure
of water heater is due to a corrosive atmosphere. (See limited warranty
for complete terms and conditions).

WATER PIPING

HOTTER  WATER  CAN  SCALD:
Water heaters are intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes washing, dish
washing, cleaning and other sanitizing needs can scald and permanently
injure you upon contact. Some people are more likely to be permanently
injured by hot water than others. These include the elderly, children, the
infirm, or physically/mentally handicapped. If anyone using hot water in
your home fits into one of these groups or if there is a local code or
state law requiring a certain temperature water at the hot water tap,
then you must take special precautions. In addition to using the lowest
possible temperature setting that satisfies your hot water needs, a means
such as a *mixing valve, shall be used at the hot water taps used by
these people or at the water heater, see Figure 2. Valves for reducing
point of use temperature by mixing cold and hot water are also available:

Consult a Qualified Installer or Service Agency. Follow  manufacturer’s
instructions for installation of the valves. Before changing the factory
setting on the thermostat, read the “Temperature Regulation” section
in this manual.

This water heater shall not be connected to any heating systems or
component(s) used with a non-potable water heating appliance.

All piping components connected to this unit for space heating applications
shall be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment shall not be
introduced into this system.

When the system requires water for space heating at temperatures higher
than required for domestic water purposes, a tempering valve must be
installed.  Please refer to Figure 2 for suggested piping arrangement.

INSTALLING THE NEW WATER HEATER

Содержание RESIDENTIAL GAS WATER HEATER

Страница 1: ...URFACE IGNITION NOT FOR USE IN MANUFACTURED MOBILE HOMES ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PL...

Страница 2: ...onal Fuel Gas Code as it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features of water heaters and have a thorough understandin...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...4 GENERAL SAFETY...

Страница 5: ...r whose name appears on the rating plate 5 Carefully plan the place where you are going to put the water heater Correct combustion vent action and vent pipe installation are very important in preventi...

Страница 6: ...Shown D D Plastic Top E E On Off Switch F F Exhaust Tee G G Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut O...

Страница 7: ...so must be primed by filling half of the loop with water prior to operating the water heater Carefully plan the location of the loops and straight sections of hose prior to cutting hoses If necessary...

Страница 8: ...than others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state l...

Страница 9: ...installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced o...

Страница 10: ...or exceeds the Energy Policy Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulation blanket to this he...

Страница 11: ...unicate directly or by ducts with the outdoors or spaces crawl or attic that freely communicate with the outdoors 1 When directly communicating with the outdoors each opening shall have a minimum free...

Страница 12: ...chemicals calcium and sodium chloride water softener salt waxes and process chemicals are typical compounds which are potentially corrosive Do not store products of this sort near the heater Also air...

Страница 13: ...installed directly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm above...

Страница 14: ...he water heater Use a soapy water solution not a match or open flame Rinse off soapy solution and wipe dry When installed at elevations above 2 000 feet 610 meters for standard models or 4 500 feet 1...

Страница 15: ...llow water to run until a constant flow is obtained This will let air out of the water heater and the piping 4 Check all water piping and connections for leaks Repair as needed VENT PIPE ASSEMBLY Ther...

Страница 16: ...e CAN CSA B149 1 Instructions on proper installation through a sidewall are provided in Figure 15 Plan the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pip...

Страница 17: ...t and ABS Materials should use ASTM D 2235 Grade Cement If the water heater is being installed as a replacement for an existing power vented heater in pre existing venting a thorough inspection of the...

Страница 18: ...r housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the outer h...

Страница 19: ...ely one quarter inch 0 64 cm outside of the line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on...

Страница 20: ...lashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed the equivalent feet of pipe as listed in Table 1 Provide support for all pipe protruding...

Страница 21: ...o prevent any combustion gases escaping into the room If the plug is not securely tightened remove and reinstall using Teflon tape on the threads Once installed along with the rest of the vent configu...

Страница 22: ...r leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical V...

Страница 23: ...nd above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning...

Страница 24: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristlebrush Thisprocesssoftensandprepares...

Страница 25: ...nd HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off...

Страница 26: ...er s instructions for installation of the valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual see Figure 26 Never allow small children t...

Страница 27: ...rod and the water The most common complaint associated with the anode rod is one of a rotten egg smell in the hot water The smell is a result of four factors which must all be present for the odor to...

Страница 28: ...Contact a qualified installer or service agency to replace a flooded water heater Do not attempt to repair the unit It must be replaced At least once a year a visual inspection should be made of the...

Страница 29: ...the temperature pressure relief valve discharge line and 2 that the water discharge will not cause any property damage as the water may be extremely hot see Figure 28 If after manually operating the...

Страница 30: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 31: ...en 4 36 Wall Plate 4 37 Flexible Tubing 38 Reducing Hose Barb Tee 39 Hose Barb Tee REPAIR PARTS LIST Not Shown Optional Now that you have purchased this water heater should a need ever exist for repai...

Страница 32: ...is energized wiring If the control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly...

Страница 33: ...resistance is not within 11 5 and 18 8 ohms at room temperature 8 Ensure the correct size of vent pipe 2 3 4 was used per installation manual for vent length Using larger pipe than required may cause...

Страница 34: ...EE to catch condensation see Figure 1 Improperly sealed hot or cold supply connections relief valve drain valve or thermostat threads Check for leaks at all condensate points See Figure 1 Also see LEA...

Страница 35: ...ation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLA...

Страница 36: ...36...

Отзывы: