and 12" (30.5 cm) from the top. (Standard clearance.) If clearances 
stated on the heater differ from standard clearances, install water 
heater according to clearances stated on the heater.

Adequate clearance for servicing this appliance should be considered 
before installation, such as changing the anodes, etc.

A minimum clearance of 5" (12.7 cm) must be allowed for access 
to replaceable parts such as the thermostats, drain valve and relief 
valve.

When installing the heater, consideration must be given to proper 
location. Location selected should be as close to the wall as practicable 
and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount 
of air for combustion.  Do not install in a con

fi

 ned area such as a closet, 

unless you provide air as shown in the “Locating The New Water 
Heater” section.  Never obstruct the 

fl

 ow of ventilation air.  If you have 

any doubts or questions at all, call your gas supplier.  Failure to provide 
the proper amount of combustion air can result in a 

fi

 re or explosion 

and cause death, serious bodily injury, or property damage.

FIGURE 5.

If this water heater will be used in beauty shops, barber shops, cleaning 
establishments, or self-service laundries with dry cleaning equipment, it 
is imperative that the water heater or water heaters be installed so that 
combustion and ventilation air be taken from outside these areas.  

Propellants of aerosol sprays and volatile compounds, (cleaners, 

chlorine based chemicals, refrigerants, etc.) in addition to being highly 

fl

 ammable in many cases, will also react to form corrosive hydrochloric 

acid when exposed to the combustion products of the water heater.  
The results can be hazardous, and also cause product failure.

INSULATION BLANKETS

Insulation blankets are available to the general public for external use 
on gas water heaters but are not necessary with these products.  The 
purpose of an insulation blanket is to reduce the standby heat loss 
encountered with storage tank heaters.  Your water heater meets or 
exceeds the National Appliance Energy Conversation Act standards 
with respect to insulation and standby loss requirements, making an 
insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you 
should follow these instructions (For identi

fi

 cation of components 

mentioned below, see Figure 1).  Failure to follow these instructions 
can restrict the air 

fl

 ow required for proper combustion, potentially 

resulting in 

fi

 re, asphyxiation, serious personal injury or death.

• Do not apply insulation to the top of the water heater, as this will 

interfere with safe operation of the draft hood.

•  Do not cover the outer door, thermostat or temperature & pressure 

relief valve.

• Do not allow insulation to come within 2" (5.1 cm) of the 

fl

 oor  to 

prevent blockage of combustion air 

fl

 ow to the burner.

• Do not cover the instruction manual.  Keep it on the side of the 

water heater or nearby for future reference.

•  Do obtain new warning and instruction labels from the manufacturer 

for placement on the blanket directly over the existing labels.

• Do inspect the insulation blanket frequently to make certain it 

does not sag, thereby obstructing combustion air 

fl

 ow.

COMBUSTION AIR AND VENTILATION FOR 
APPLIANCES LOCATED IN UNCONFINED SPACES

UNCONFINED SPACE

 is space whose volume is not less than 

50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the 
aggregate input rating of all appliances installed in that space.  Rooms 
communicating directly with the space in which the appliances are 
installed, through openings not furnished with doors, are considered 
a part of the uncon

fi

 ned space.

In uncon

fi

 ned spaces in buildings, in

fi

 ltration may be adequate to 

provide air for combustion, ventilation and dilution of 

fl

 ue  gases.  

However, in buildings of tight construction (for example, weather 
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air 
may need to be provided using the methods described in “Combustion 
Air and Ventilation for Appliances Located in Con

fi

 ned Spaces.”

COMBUSTION AIR AND VENTILATION FOR 
APPLIANCES LOCATED IN CONFINED SPACES

CONFINED SPACE

 is a space whose volume is less than 50 cubic 

feet per 1,000 Btu per hour (4.8 cm per kW)  of the aggregate input 
rating of all appliances installed in that space.

Содержание ProMax Power-Vent 185237-004

Страница 1: ...ECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WA...

Страница 2: ...T DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understand...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...fety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance...

Страница 5: ...tally vented gas fueled heating appli ance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Страница 6: ...in Valve X Gas Control Valve Y Drain Pan Z Air Intake Screen Base Pan AA Inner Door B B Outer Door CC HSI Burner Assembly D D Air Intake Screen Blower Assembly E E FV Sensor Bracket Assembly 40K 50K M...

Страница 7: ...than others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state l...

Страница 8: ...er an alarm or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the...

Страница 9: ...xceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulati...

Страница 10: ...ors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 8 3 When co...

Страница 11: ...res higher than required for domestic water purposes a tempering valve must be installed Please refer to Figure 2 for suggested piping arrangement CLOSED WATER SYSTEMS Water supply systems may because...

Страница 12: ...ctly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm above or at any dist...

Страница 13: ...er heater Use a soapy water solution not a match or open flame Rinse off soapy solution and wipe dry When installed at elevations above 7 700 feet 2 347 meters input rating should be reduced at the ra...

Страница 14: ...is still mounted securely and the air intake screen of the blower assembly is installed in the dilution air opening Also make sure the drain port of the rubber boot vent adapter is capped off Lastly m...

Страница 15: ...this water heater to an existing vent or chimney It must be vented separately from all other appliances Nonmetallic vent may be used if it has Heat Deflection Temperature HDT 66 psi or 455 kPa of at l...

Страница 16: ...llations will have water condensate in the vent piping If this occurs then adequate means of draining and disposing of the condensate needs to be made by the installer CONDENSATE Condensate formation...

Страница 17: ...building The manufacturer also recommends that the vent termination should not be installed closer than 18 45 7 cm from an inside corner of an L shaped structure and not be less than 1 foot 0 31 m abo...

Страница 18: ...lied for decorative purposes only and is not a requirement for the vent termination if not needed by the installer VERTICAL VENT THROUGH ROOF This unit is approved for venting through the roof with th...

Страница 19: ...15 2 cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes fo...

Страница 20: ...he distance and make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process...

Страница 21: ...21...

Страница 22: ...If a suitable area is not available a cover should be installed over the thermostat to prevent tampering The water temperature setting was factory set at the lowest temperature Pressing the COOLER bu...

Страница 23: ...expansion Contact a local plumbing service agency to have a thermal expansion tank installed STRANGE SOUNDS Possible noises due to expansion and contraction of some metal parts during periods of heat...

Страница 24: ...Viewport on the Inner Door see Figure 1 The main burner should provide complete combustion of gas ignite rapidly give reasonably quiet operation and cause no excessive flame lifting from the burner po...

Страница 25: ...ils to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperature pressure relief valve wit...

Страница 26: ...he tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Water in the water heater bottom or on th...

Страница 27: ...odels only 26B FV Sensor Bracket 55K 62 5K models only 27 Nipple with Heat Trap 28 Secondary Anode with Heat Trap Not Shown Optional Now that you have purchased this water heater should a need ever ex...

Страница 28: ...INES TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Please check guidelines below For your safety water heater service should be performed only by a qualified service technician Read the GENERAL SAFETY I...

Страница 29: ...29...

Страница 30: ...be utilized by a qualified service agent When calling for service notify the service agent that this is a Flammable Vapor Ignition Resistant Product TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELI...

Страница 31: ...t any operation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ON...

Страница 32: ...32...

Отзывы: