9
and 12" (30.5 cm) from the top. (Standard clearance.) If clearances
stated on the heater differ from standard clearances, install water
heater according to clearances stated on the heater.
Adequate clearance for servicing this appliance should be considered
before installation, such as changing the anodes, etc.
A minimum clearance of 5" (12.7 cm) must be allowed for access
to replaceable parts such as the thermostats, drain valve and relief
valve.
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the wall as practicable
and as centralized with the water piping system as possible.
FIGURE 4.
A gas water heater cannot operate properly without the correct amount
of air for combustion. Do not install in a con
fi
ned area such as a closet,
unless you provide air as shown in the “Locating The New Water
Heater” section. Never obstruct the
fl
ow of ventilation air. If you have
any doubts or questions at all, call your gas supplier. Failure to provide
the proper amount of combustion air can result in a
fi
re or explosion
and cause death, serious bodily injury, or property damage.
FIGURE 5.
If this water heater will be used in beauty shops, barber shops, cleaning
establishments, or self-service laundries with dry cleaning equipment, it
is imperative that the water heater or water heaters be installed so that
combustion and ventilation air be taken from outside these areas.
Propellants of aerosol sprays and volatile compounds, (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being highly
fl
ammable in many cases, will also react to form corrosive hydrochloric
acid when exposed to the combustion products of the water heater.
The results can be hazardous, and also cause product failure.
INSULATION BLANKETS
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with these products. The
purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your water heater meets or
exceeds the National Appliance Energy Conversation Act standards
with respect to insulation and standby loss requirements, making an
insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you
should follow these instructions (For identi
fi
cation of components
mentioned below, see Figure 1). Failure to follow these instructions
can restrict the air
fl
ow required for proper combustion, potentially
resulting in
fi
re, asphyxiation, serious personal injury or death.
• Do not apply insulation to the top of the water heater, as this will
interfere with safe operation of the draft hood.
• Do not cover the outer door, thermostat or temperature & pressure
relief valve.
• Do not allow insulation to come within 2" (5.1 cm) of the
fl
oor to
prevent blockage of combustion air
fl
ow to the burner.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from the manufacturer
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it
does not sag, thereby obstructing combustion air
fl
ow.
COMBUSTION AIR AND VENTILATION FOR
APPLIANCES LOCATED IN UNCONFINED SPACES
UNCONFINED SPACE
is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the
aggregate input rating of all appliances installed in that space. Rooms
communicating directly with the space in which the appliances are
installed, through openings not furnished with doors, are considered
a part of the uncon
fi
ned space.
In uncon
fi
ned spaces in buildings, in
fi
ltration may be adequate to
provide air for combustion, ventilation and dilution of
fl
ue gases.
However, in buildings of tight construction (for example, weather
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in “Combustion
Air and Ventilation for Appliances Located in Con
fi
ned Spaces.”
COMBUSTION AIR AND VENTILATION FOR
APPLIANCES LOCATED IN CONFINED SPACES
CONFINED SPACE
is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input
rating of all appliances installed in that space.
Содержание ProMax Power-Vent 185237-004
Страница 3: ...3 GENERAL SAFETY...
Страница 21: ...21...
Страница 29: ...29...
Страница 32: ...32...