paragraph. The new valve must be marked with a maximum set 

pressure not to exceed the marked hydrostatic working pressure 

of the water heater (150 psi = 1,035 kPa) and a discharge capacity 

not less than the water heater Btu/hr or KW input rate as shown on 

the water heater’s model rating plate.

For safe operation of the water heater, the temperature and pressure 

relief valve must not be removed from its designated opening nor 

plugged. The temperature-pressure relief valve must be installed 

directly into the fitting of the water heater designed for the relief valve. 

Install discharge piping so that any discharge will exit only within 6 

inches (15.2 cm) above, or at any distance below the structural floor. 

Be certain that no contact is made with any live electrical part. The 

discharge opening must not be blocked or reduced in size under 

any  circumstances.  Excessive  length,  over  30  feet  (9.14  m),  or 

use of more than four elbows can cause restriction and reduce the 

discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve 

and the tank. Do not connect discharge piping directly to the drain 

unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, 

hazard to life, or property damage, the relief valve must be allowed 

to  discharge  water  in  adequate  quantities  should  circumstances 

demand. If the discharge pipe is not connected to a drain or other 

suitable means, the water flow may cause property damage.

The Discharge Pipe:

• 

Shall not be smaller in size than the outlet pipe size of the valve, or 

have any reducing couplings or other restrictions.

• 

Shall not be plugged or blocked.

• 

Shall be of material listed for hot water distribution.

• 

Shall be installed so as to allow complete drainage of both the 

temperature-pressure relief valve and the discharge pipe.

• 

Must terminate a maximum of six inches above a floor drain or 

external to the building. In cold climates, it is recommended that the 

discharge pipe be terminated at an adequate drain inside the building.

• 

Shall not have any valve or other obstruction between the relief 

valve and the drain.

The temperature-pressure relief valve must be manually operated 

at least once a year. Caution should be taken to ensure that (1) no 

one is in front of or around the outlet of the temperature-pressure 

relief valve discharge line, and (2) the water manually discharged 

can  cause  bodily  injury  or  property  damage  because  the  water 

may be extremely hot. If after manually operating the valve, it fails 

to  completely  reset  and  continues  to  release  water,  immediately 

close the cold water inlet to the water heater, follow the draining 

instructions in this manual, and replace the temperature-pressure 

relief valve with a properly rated/sized new one. 
If you do not understand these instructions or have any questions 

regarding  the  temperature-pressure  relief  valve  call  the  toll  free 

number listed on the back cover of this manual for technical assistance.

CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements or such 

conditions  as  high  line  pressure,  among  others,  have  installed 

devices such as pressure reducing valves, check valves, and back 

flow preventers. Devices such as these cause the water system to 

be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed system 

the volume of water will grow when it is heated. As the volume of 

water grows there will be a corresponding increase in water pressure 

due to thermal expansion. Thermal expansion can cause premature 

tank failure (leakage). This type of failure is not covered under the 

limited  warranty. Thermal  expansion  can  also  cause  intermittent 

temperature-pressure relief valve operation: water discharged from 

the valve due to excessive pressure build up. This condition is not 

covered under the limited warranty. The temperature-pressure relief 

valve is not intended for the constant relief of thermal expansion.
A properly sized thermal expansion tank should be installed on all 

closed systems to control the harmful effects of thermal expansion. 

Contact a local plumbing service agency to have a thermal expansion 

tank installed.

Содержание LTE 66D

Страница 1: ...P FOR FUTURE REFERENCE COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products 500 Tennessee Waltz Parkway Ashland City...

Страница 2: ...ition to electrical testing skills when performing service ANSI Z223 1 2006 Sec 3 3 83 Qualified Agency Any individual firm corporation or company that either in person or through a representative is...

Страница 3: ...be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater HYDROGEN GAS FLAMMABLE Hydrogen gas can be produced in a hot water system served by thi...

Страница 4: ...Code CSA C22 1 The National Electrical Code may be ordered from National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 The Canadian Electrical Code is available from the Canadian St...

Страница 5: ...5 102 92 85 77 73 4000 4000 GPH 90 81 60 54 45 41 36 32 30 27 26 8 LPH 341 307 227 205 170 153 136 123 114 102 97 4500 4500 GPH 101 91 68 61 51 46 41 36 34 30 29 9 LPH 384 345 256 230 192 173 153 138...

Страница 6: ...c MODEL NUMBER 22U1 COMMERCIAL STORAGE TANK WATER HEATER WATTS LOWER MAX WORKING PRESSURE PSI 1 PH 3 PH 1 PH 3 PH RATED MEASURED WATTS INTERLOCK SIMULTANEOUS CAPACITY US GAL STANDBY LOSS TOTAL WATTS C...

Страница 7: ...LVE INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDER WATER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE REFER TO WATER HEATER LOCATION ON PAGE 8...

Страница 8: ...er heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented b...

Страница 9: ...imum of 125 degree F Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory setting on the thermostat read...

Страница 10: ...at an adequate drain inside the building Shall not have any valve or other obstruction between the relief valve and the drain The temperature pressure relief valve must be manually operated at least...

Страница 11: ...t 2 Four wire T 4 circuit for dual element water heater equipped with two high limit controls and single phase power input This is an example of calculating heater amperage for both types of element o...

Страница 12: ...LT NON SIMULTANEOUS SINGLE PHASE OPERATION RED BLACK YELLOW BLUE BLACK RED BLACK BLACK BLACK RED RED RED BLACK RED BLACK T 4 208 or 240 VOLT SIMULTANEOUS OPERATION SINGLE PHASE OPERATION GND GREEN GND...

Страница 13: ...ghtness Also check connections on top and or sides of heater Repair water leaks and tighten electrical connections as necessary 3 Depress the red manual reset button on each Thermostat ECO combination...

Страница 14: ...1st Degree Burn Less Severe Burns Time for Permanent Burns 2nd 3rd Degree Most Severe Burns 110 43 normal shower temp 116 47 pain threshold 116 47 35 minutes 45 minutes 122 50 1 minute 5 minutes 131...

Страница 15: ...y the anode rod This does not affect water s taste or color The rod must be maintained to keep tank in operating condition Anode deterioration depends on water conductivity not necessarily water condi...

Страница 16: ...ating The sounds are normal however the tank bottom and elements should be cleaned See the Maintenance section of this manual WATER LEAKAGE IS SUSPECTED Refer to Leakage Checkpoint on the following pa...

Страница 17: ...ary to shut off electricity and drain tank to perform procedure Water leaks at the elements may be due to 1 Defective element which leaks at terminals or thru flange Replace element 2 Loose element ga...

Страница 18: ...gas supply line sizing gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Abuse misuse accident fire flood...

Страница 19: ...on the rating plated located above the lower access panel Be sure to provide all pertinent facts when you call or visit WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION MODEL NUMBER VO...

Страница 20: ...TAGE CHART K W ELEMENT WATTAGE 208V 240V PART NO PART NO 3 0 3000 9003956115 9001879005 3 5 3500 9000092015 9003948115 4 0 4000 9003951115 9003956115 4 5 4500 9002645005 9000092015 5 0 5000 9004688105...

Страница 21: ...21 NOTES...

Страница 22: ...22 NOTES...

Страница 23: ...23 NOTES...

Страница 24: ...24 www hotwater com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2016 A O Smith Water Heater Company All rights reserved...

Отзывы: