CLOSED WATER SYSTEM

A closed system will exist if a back-flow preventer (check valve),
pressure reducing valve, or other similar device is installed in
the cold water line between the water heater and the street main
(or well).  Excessive pressure may develop due to the thermal
expansion of heated water causing premature tank failure or
intermittent relief valve operation. This type of failure is not covered
by the limited warranty.  An expansion tank may be necessary in
the cold water supply to alleviate this situation, see Figure 1.
Contact the local plumbing authority.

If the temperature and pressure relief valve on the appliance
discharges periodically, this may be due to thermal expansion
in a closed water supply system.  Contact the water supplier or
local plumbing inspector on how to correct the situation.  

Do not

plug the temperature and pressure relief valve.

GAS CONNECTIONS

The minimum gas supply pressure for input adjustment is
5.0" W.C. (1.25 kPa) for natural gas 11.0" W.C. (2.74 kPa) for propane.

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 10.5" (2.6 kPa) FOR NATURAL & 13.0" (3.24 kPa) FOR
PROPANE WATER COLUMN SUPPLY PRESSURE.  EXPOSURE
TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO
THE CONTROL WHICH COULD RESULT IN FIRE OR EXPLOSION.

If overpressure has occurred such as through improper testing of gas
lines or emergency malfunction of the supply system, the control must
be checked for safe operation.  Make sure that the outside vents on the
supply regulators and the safety vent valves are protected against
blockage. These are parts of the gas supply system not the
heater.  Vent blockage may occur during ice storms.

IT IS IMPORTANT TO GUARD AGAINST CONTROL FOULING
FROM CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

All piping must comply with local codes and ordinances or with
the National Fuel Gas Code (ANSI Z223.1, NFPA 54) whichever
applies. Copper and brass tubing and fittings (except tin lined
copper tubing) shall not be used.

REFER TO FIGURE 1 FOR CONNECTION DETAILS.  BEFORE
ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS
CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY
LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG) MUST BE
INCORPORATED IN THE PIPING, SEE FIGURE 1.

 The dirt leg must

be readily accessible. Install in accordance with recommendations of
serving gas supplier.  Refer to the current edition of ANSI Z223.1.

To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve inlet. The
valve inlet has a hexagon shape for use with a backup wrench.

Apply joint compounds (pipe dope) sparingly and only to the
male threads of pipe joints. Do not apply compound to the first
two threads. Use compounds resistant to the action of liquefied
petroleum gases. Do not use teflon tape on gas valve.

DISCONNECT THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSI
(3.5 kPa).  GAS SUPPLY LINE MUST BE CAPPED WHEN
DISCONNECTED FROM THE HEATER. FOR TEST PRESSURES AT
1/2 PSI (3.5 kPa) OR LESS, THE APPLIANCE NEED NOT BE
DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY
PRESSURE TEST BY CLOSING THE MAIN MANUAL GAS VALVE.

BEFORE PLACING THE HEATER IN OPERATION, CHECK
FOR GAS LEAKAGE. USE SOAP AND WATER SOLUTION OR
OTHER MATERIAL ACCEPTABLE FOR THIS PURPOSE. DO NOT
USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF
IGNITION TO LOCATE GAS LEAKS.

RELIEF VALVE (P)- See FIGURE 1.

A NEW TEMPERATURE AND PRESSURE RELIEF VALVE
COMPLYING WITH THE STANDARD FOR RELIEF VALVES AND
AUTOMATIC GAS SHUT OFF DEVICES FOR HOT WATER
SUPPLY SYSTEMS, ANSI Z21.22 (CURRENT EDITION) MUST
BE INSTALLED IN THE HEATER IN THE MARKED OPENING
PROVIDED. THE VALVE MUST BE OF A SIZE (INPUT RATING)
THAT WILL BE ADEQUATE FOR YOUR SIZE HEATER.

Check the metal tag on the relief valve and compare it to the
heater’s rating plate. The pressure rating of the relief valve must
not exceed the working pressure shown on the rating plate of the
heater. In addition, the hourly Btu rated temperature steam
discharge capacity of the relief valve shall not be less than the
input rating of the heater.  

NO VALVE IS TO BE PLACED BETWEEN

THE RELIEF VALVE AND TANK.  DO NOT PLUG THE RELIEF VALVE.

The drain line connected to this valve must not contain a reducing
coupling or other restriction and must terminate near a suitable
drain to prevent water damage during valve operation. The
discharge line shall be installed in a manner to allow complete
drainage of both the valve and line. 

DO NOT THREAD, PLUG OR

CAP THE END OF THE DRAIN LINE.

VENTING

  WARNING

NEVER OPERATE THE HEATER UNLESS THE INTAKE AND
EXHAUST ARE VENTED TO THE OUTDOORS AND HAS ADEQUATE
AIR SUPPLY TO AVOID RISKS OF IMPROPER OPERATION, FIRE,
EXPLOSION, OR ASPHYXIATION. IF THE WATER HEATER IS BEING
INSTALLED AS A REPLACEMENT FOR AN EXISTING POWER
VENTED HEATER IN PRE-EXISTING VENTING, A THOROUGH
INSPECTION OF THE EXISTING VENTING SYSTEM MUST BE
PERFORMED PRIOR TO ANY INSTALLATION WORK. VERIFY THAT
THE CORRECT MATERIAL AS DETAILED ABOVE HAS BEEN USED,
AND THAT THE MINIMUM OR MAXIMUM VENT LENGTHS AND
TERMINAL LOCATION AS DETAILED IN THIS MANUAL HAVE BEEN
MET. CAREFULLY INSPECT THE ENTIRE VENTING SYSTEM FOR
ANY SIGNS OF CRACKS OR FRACTURES, PARTICULARLY AT THE
JOINTS BETWEEN ELBOWS AND OTHER FITTINGS AND THE
STRAIGHT RUNS OF VENT PIPE. CHECK THE SYSTEM FOR SIGNS
OF SAGGING OR OTHER STRESSES IN THE JOINTS AS A RESULT
OF MISALIGNMENT OF ANY COMPONENTS IN THE SYSTEM. IF ANY
OF THESE CONDITIONS ARE FOUND, THEY MUST BE
CORRECTED IN

 

ACCORDANCE WITH THE VENTING

INSTRUCTIONS IN THIS MANUAL BEFORE COMPLETING THE
INSTALLATION AND PUTTING THE WATER HEATER INTO SERVICE.

  WARNING

THESE MODELS ARE CERTIFIED FOR VERTICAL VENTING
AND SIDE WALL VENTING.  THE UNIT CONSISTS OF AN INTAKE
VENT TERMINAL AND AN EXHAUST VENT TERMINAL WHICH
MUST BE USED TO TERMINATE THE VENTING ARRANGEMENT.
IF THE VENT TERMINALS SUPPLIED WITH THIS UNIT ARE
NOT USED TO TERMINATE THE VENTING ARRANGEMENT,
THE RISK OF IMPROPER OPERATION, FIRE, EXPLOSION, OR
ASPHYXIATION WILL INCREASE.

Содержание GPDH

Страница 1: ...er heater from A O Smith Water Products Company We appreciate your confidence in our products You should thoroughly read this manual before installation and or operation of this water heater Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS ADIVISION OFA O SMITH CORPORATION www aosmithwaterheaters com GET TO KNOWYOUR WATER HEATE...

Страница 2: ...CONTROL HARNESS AND INSIDE JACKET GAS MODEL GPDH GPDT GPDX WITH HOT SURFACE IGNITION CERTAIN MODELS ARE EQUIPPED WITH SIDE PLUMBING CONNECTIONS FOR SPACE HEATING HOT AND COLD FITTING ASSEMBLIES PART NO 900126 2 TEMPERATURE INDICATORS TEMPERATURE ADJUSTMENT BUTTONS TYPICALNATURALGAS PILOT MAIN BURNER HOT SURFACE IGNITION ASSEMBLY Replacement parts and recommended delimer may be ordered through auth...

Страница 3: ...aking an insulation blanket unnecessary WARNING Should you choose to apply an insulation blanket to this heater you should follow these instructions see Figure 1 for identification of components mentioned below Failure to follow these instructions can restrict the air flow required for proper combustion potentially resulting in fire asphyxiation serious personal injury or death Do not cover the ou...

Страница 4: ...THE HEATER OR TO LOWER FLOORS OF THE STRUCTURE When such locations cannot be avoided a suitable drain pan should be installed under the heater see Figure 1 The pan should have a minimum length and width of at least 2 inches 51mm greater than the diameter of the heater and should be piped to an adequate drain Drain pans suitable for these heaters are available from your dealer or A O Smith Water Pr...

Страница 5: ...UT OFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSI 3 5 kPa GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTEDFROMTHEHEATER FORTESTPRESSURESAT 1 2 PSI 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURETESTBYCLOSINGTHE MAIN MANUALGAS VALVE BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE ...

Страница 6: ...ve any door window or gravity air inlet into the building see Figure 4 The Power Direct Vent outlet terminal of over 50 000 BtuH input models shall terminate at least 12 30 5 cm below 12 30 5 cm horizontally from or 12 30 5 cm above any door window or gravity air inlet into the building see Figure 4 18 45 7 cm minimum from other natural draft gravity direct vent power vent or power direct vent app...

Страница 7: ...pported at 3 1 2 foot 8 9 cm intervals and vertical runs supported at 5 foot 1 5 cm intervals VENTING THROUGH AN OUTSIDE WALL A ALL 75 GAL 283 9L 65 000 70 000 BTU HR MODELS 50 GAL 189 3L 60 000 65 000BTU HRMODELS SEE FIGURE 10 In the carton is supplied 1 Two 3 inlet and outlet PVC Schedule 40 45 vent caps 2 A 3 ABS Schedule 40 90 street elbow used to connect the outlet vent pipe to the water heat...

Страница 8: ... vent piping cannot under any circumstances be run downhill FIGURE 12 The vent piping can be installed as follows 1 Horizontal runs require a minimum1 8 3 2mm rise per 5 1 52 m FIGURE 13 FIGURE 14 FIGURE 15 2 The total vertical and horizontal vent runs cannot exceed the maximum length with the number of 90 elbows as specified in the table below If more elbows are required the venting distance must...

Страница 9: ...mer cleaner 4 Apply a thin coat of cement to fitting avoiding puddling inside 5 Apply a liberal coat of cement to pipe leaving no voids 6 QUICKLY assemble parts while cement is fluid If you wait too long re coat pipes 7 Push pipe completely into socket of fitting turning as it goes until it bottoms 8 Hold pipe and fitting together for 30 seconds Then carefully clean off excess with a cloth Allow c...

Страница 10: ...al 189 3 L Hi BTU input all 75 Gal 283 9 L Models only is supplied on certain models only More may be required and must be supplied locally 1 The water heater requires its own separate venting system 2 Only 3 ABS Schedule 40 piping and fittings are acceptable materials on the first 5 1 52 m of the outlet vent system for some 50 Gal 189 3 L and 75 Gal 283 9 L models 3 3 PVC ABS or CPVC Schedule 40 ...

Страница 11: ...secure with screws FIGURE 24 SCHEMATIC DIAGRAMS FIGURE 25 WARNING DISCONNECT FROM ELECTRICAL SUPPLY BEFORE SERVICING UNIT REPLACE ALL DOORS AND PANELS BEFORE OPERATING HEATER IF ANY OF THE ORIGINAL WIRES SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH APPLIANCE WIRE MATERIAL WITH MINIMUM TEMPERATURE RATING OF 105 C AND A MINIMUM SIZE OF NO 18 AWG FIGURE 26 T P VALVE AND PIPE ...

Страница 12: ...cond Then press the COOLER button until the WARM indicator light appears BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATERANDAIR PURGED FROMALL LINES 1 STOP Read the safety information above on this label 2 Set the ON OFF switch on the control box to the ON position 3 Set the thermostat to the lowest setting by first pressing the COOLER and HOTTER buttons together and holding for 1 second T...

Страница 13: ...G OF GAS VALVE WILL REDUCE THE RISK OF SCALDS Some states require settings at specific lower temperatures Figure 28 shows the approximate water temperatures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30 F 1 C If you experience this type of use you shou...

Страница 14: ...onds Flame Recognition Period 1 second Ignition Trial 4 seconds Interpurge 5 seconds Post purge 5 seconds Retries 2 Reset from Lockout 1 hr Flame Sensing Nominal HSI Off Run Mode 4 0µ DC HIGH ALTITUDE INSTALLATION WARNING INSTALLATIONS ABOVE 2000 610 m FEET REQUIRE REPLACEMENT OF THE BURNER ORIFICE IN ACCORDANCE WITH THE NATIONAL FUEL GAS CODE ANSIZ223 1 NFPA54 FAILURE TOREPLACETHEORIFICEWILLRESUL...

Страница 15: ...ING OUT OF THE VALVE DURING THIS CHECKING OPERATION MAY BE EXTREMELY HOT AVOID CONTACT AND DISCHARGE SAFELY TO PREVENT WATER DAMAGE DRAINING If the heater is to be shut off and exposed to freezing temperatures it must be drained Water if left in the tank and allowed to freeze will damage the heater Turn off the gas and cold water inlet valve to the heater Open a nearby hot water faucet and the hea...

Страница 16: ...ontact your dealer or theA O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If after working with your dealer or service agent the problem has not been resolved to your satisfaction please let us know by either writing to us at A O Smith Water Products Company Service Department 106 Adkisson St Ashland City TN 37015 o...

Страница 17: ...s correct and secure 2 Replace hot surface igniter System in lockout 1 Gas supply is off or too low to operate 2 Hot surface igniter not positioned correctly 3 Low voltage to the water heater 4 Electric polarity to unit is incorrect test and correct Problem in the gas valve driver circuit 1 Turn power to the water heater off for 10 seconds and the back on 2 Replace gas control valve Problem with t...

Страница 18: ...ice A Dirt in burner ports Turn off heater and gas clean burner head B Combustion air path restricted Check intake venting arrangements for YELLOWFLAME obstructions C Not enough dilution air for proper Check Intake venting arrangement for combustion obstructions A Water on the floor under heater See CONDENSATION section CONDENSATION B Water dripping from pan Provide drip TEE to catch condensation ...

Страница 19: ...IBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILLPROVIDE ONLY A REPLACEMENT WATER HEATER OR PART THEREOF THE OWNER IS RESPONSIBLE FOR ALL OTHER COSTS Such costs may include but are not limited to LIMITED RESIDENTIAL GAS WARRANTY a Labor charges for service removal or reinstallation of the water heater or part thereof b Shipping and delivery charges for forwarding the new water heater or repla...

Страница 20: ...20 125 SOUTHEAST PARKWAY FRANKLIN TN 37068 Phone 1 800 433 2545 Fax 1 800 433 2515 www aosmithwaterheaters com email parts hotwater com ...

Отзывы: