10

wall will help minimize discoloration of the wall. Note that the
inside flue mounting adaptors must be slipped over the vent
piping before locating the pipe through the wall. Before securing
the inside and outside collars to the wall, use a silicone sealer
between pipe and opening to insure a water and air tight seal.

INSTALLATION SHOWING USE OF PVC, ABS OR CPVC PIPE
FOR INLET AND OUTLET VENT PIPE.

FIGURE 20.

CONNECTING VENT TO BLOWER

1. If making an immediate horizontal run of vent off the blower,

one 3" PVC inlet and one 3" PVC (ABS for 50 Gal. (189.3 L)
and 75 Gal.(283.9 L) Models) outlet Schedule 40 street elbows
are required. Place the elbow in the required direction on the
blower and using three sheet metal screws, attach the elbow.

FIGURE 21.

2. If there is to be a vertical run from the blower, the 3" PVC inlet

and the 3" PVC (ABS for 50 Gal. (189.3 L) and 75 Gal.(283.9
L) Models) outlet Schedule 40 pipe must be attached to the
blower and venting hood, using six sheet metal screws.

FIGURE 22.

VENTING THROUGH A ROOF

Two 3" inlet and outlet PVC Schedule 40-45° vent caps are supplied.

A 5' (1.52 m) section of 3" ABS Schedule 40 

outlet

 vent pipe

(50 Gal. (189.3 L) Hi BTU input & all 75 Gal. (283.9 L) Models
only) is supplied on certain models only. (More may be required
and must be supplied locally).

1. The water heater requires its own (separate) venting system.
2. Only 3" ABS Schedule 40 piping and fittings are acceptable

materials on the first 5' (1.52 m) of the outlet vent system for
some 50 Gal. (189.3 L) and 75 Gal. (283.9 L) models.

3. 3" PVC, ABS, or CPVC Schedule 40 piping and fittings are

acceptable materials for the inlet vent system and for the outlet
vent system (after the first 5' (1.52 m) for 50 Gal. (189.3 L) Hi
BTU input and 75 Gal. (283.9 L) Models only).

4. It cannot be connected to existing vent piping or chimney.
5. It must terminate vertically to the outdoors.
6. The total vertical and horizontal runs cannot exceed the

maximum length with a maximum number of 90° elbows as
specified in the table below. If more elbows are required, the
venting distance must be reduced 5' (1.52 m) for every 90° elbow.

3" DIA. VENTS

NUMBER OF 90° DEG.

MAX. LENGTH (FT.)

ELBOWS*

45 (13.72  m)

1

40 (12.2 m)

2

35 (10.7 m)

3

*NOTE: Two 45° elbows are equivalent to one 90° elbow. One
90° elbow equals 5 ' (1.52 m) of equivalent vent length.

      

FIGURE 23.

WIRING

 

 DANGER

DO NOT USE AN EXTENSION CORD.  IF THERE IS NOT A
SUITABLE RECEPTACLE AND/OR LOCAL CODES PROHIBIT
USE OF A POWER CORD, FIELD WIRING MUST BE PROVIDED.
THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY

Содержание GPDH

Страница 1: ...er heater from A O Smith Water Products Company We appreciate your confidence in our products You should thoroughly read this manual before installation and or operation of this water heater Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS ADIVISION OFA O SMITH CORPORATION www aosmithwaterheaters com GET TO KNOWYOUR WATER HEATE...

Страница 2: ...CONTROL HARNESS AND INSIDE JACKET GAS MODEL GPDH GPDT GPDX WITH HOT SURFACE IGNITION CERTAIN MODELS ARE EQUIPPED WITH SIDE PLUMBING CONNECTIONS FOR SPACE HEATING HOT AND COLD FITTING ASSEMBLIES PART NO 900126 2 TEMPERATURE INDICATORS TEMPERATURE ADJUSTMENT BUTTONS TYPICALNATURALGAS PILOT MAIN BURNER HOT SURFACE IGNITION ASSEMBLY Replacement parts and recommended delimer may be ordered through auth...

Страница 3: ...aking an insulation blanket unnecessary WARNING Should you choose to apply an insulation blanket to this heater you should follow these instructions see Figure 1 for identification of components mentioned below Failure to follow these instructions can restrict the air flow required for proper combustion potentially resulting in fire asphyxiation serious personal injury or death Do not cover the ou...

Страница 4: ...THE HEATER OR TO LOWER FLOORS OF THE STRUCTURE When such locations cannot be avoided a suitable drain pan should be installed under the heater see Figure 1 The pan should have a minimum length and width of at least 2 inches 51mm greater than the diameter of the heater and should be piped to an adequate drain Drain pans suitable for these heaters are available from your dealer or A O Smith Water Pr...

Страница 5: ...UT OFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSI 3 5 kPa GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTEDFROMTHEHEATER FORTESTPRESSURESAT 1 2 PSI 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURETESTBYCLOSINGTHE MAIN MANUALGAS VALVE BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE ...

Страница 6: ...ve any door window or gravity air inlet into the building see Figure 4 The Power Direct Vent outlet terminal of over 50 000 BtuH input models shall terminate at least 12 30 5 cm below 12 30 5 cm horizontally from or 12 30 5 cm above any door window or gravity air inlet into the building see Figure 4 18 45 7 cm minimum from other natural draft gravity direct vent power vent or power direct vent app...

Страница 7: ...pported at 3 1 2 foot 8 9 cm intervals and vertical runs supported at 5 foot 1 5 cm intervals VENTING THROUGH AN OUTSIDE WALL A ALL 75 GAL 283 9L 65 000 70 000 BTU HR MODELS 50 GAL 189 3L 60 000 65 000BTU HRMODELS SEE FIGURE 10 In the carton is supplied 1 Two 3 inlet and outlet PVC Schedule 40 45 vent caps 2 A 3 ABS Schedule 40 90 street elbow used to connect the outlet vent pipe to the water heat...

Страница 8: ... vent piping cannot under any circumstances be run downhill FIGURE 12 The vent piping can be installed as follows 1 Horizontal runs require a minimum1 8 3 2mm rise per 5 1 52 m FIGURE 13 FIGURE 14 FIGURE 15 2 The total vertical and horizontal vent runs cannot exceed the maximum length with the number of 90 elbows as specified in the table below If more elbows are required the venting distance must...

Страница 9: ...mer cleaner 4 Apply a thin coat of cement to fitting avoiding puddling inside 5 Apply a liberal coat of cement to pipe leaving no voids 6 QUICKLY assemble parts while cement is fluid If you wait too long re coat pipes 7 Push pipe completely into socket of fitting turning as it goes until it bottoms 8 Hold pipe and fitting together for 30 seconds Then carefully clean off excess with a cloth Allow c...

Страница 10: ...al 189 3 L Hi BTU input all 75 Gal 283 9 L Models only is supplied on certain models only More may be required and must be supplied locally 1 The water heater requires its own separate venting system 2 Only 3 ABS Schedule 40 piping and fittings are acceptable materials on the first 5 1 52 m of the outlet vent system for some 50 Gal 189 3 L and 75 Gal 283 9 L models 3 3 PVC ABS or CPVC Schedule 40 ...

Страница 11: ...secure with screws FIGURE 24 SCHEMATIC DIAGRAMS FIGURE 25 WARNING DISCONNECT FROM ELECTRICAL SUPPLY BEFORE SERVICING UNIT REPLACE ALL DOORS AND PANELS BEFORE OPERATING HEATER IF ANY OF THE ORIGINAL WIRES SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH APPLIANCE WIRE MATERIAL WITH MINIMUM TEMPERATURE RATING OF 105 C AND A MINIMUM SIZE OF NO 18 AWG FIGURE 26 T P VALVE AND PIPE ...

Страница 12: ...cond Then press the COOLER button until the WARM indicator light appears BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATERANDAIR PURGED FROMALL LINES 1 STOP Read the safety information above on this label 2 Set the ON OFF switch on the control box to the ON position 3 Set the thermostat to the lowest setting by first pressing the COOLER and HOTTER buttons together and holding for 1 second T...

Страница 13: ...G OF GAS VALVE WILL REDUCE THE RISK OF SCALDS Some states require settings at specific lower temperatures Figure 28 shows the approximate water temperatures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30 F 1 C If you experience this type of use you shou...

Страница 14: ...onds Flame Recognition Period 1 second Ignition Trial 4 seconds Interpurge 5 seconds Post purge 5 seconds Retries 2 Reset from Lockout 1 hr Flame Sensing Nominal HSI Off Run Mode 4 0µ DC HIGH ALTITUDE INSTALLATION WARNING INSTALLATIONS ABOVE 2000 610 m FEET REQUIRE REPLACEMENT OF THE BURNER ORIFICE IN ACCORDANCE WITH THE NATIONAL FUEL GAS CODE ANSIZ223 1 NFPA54 FAILURE TOREPLACETHEORIFICEWILLRESUL...

Страница 15: ...ING OUT OF THE VALVE DURING THIS CHECKING OPERATION MAY BE EXTREMELY HOT AVOID CONTACT AND DISCHARGE SAFELY TO PREVENT WATER DAMAGE DRAINING If the heater is to be shut off and exposed to freezing temperatures it must be drained Water if left in the tank and allowed to freeze will damage the heater Turn off the gas and cold water inlet valve to the heater Open a nearby hot water faucet and the hea...

Страница 16: ...ontact your dealer or theA O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If after working with your dealer or service agent the problem has not been resolved to your satisfaction please let us know by either writing to us at A O Smith Water Products Company Service Department 106 Adkisson St Ashland City TN 37015 o...

Страница 17: ...s correct and secure 2 Replace hot surface igniter System in lockout 1 Gas supply is off or too low to operate 2 Hot surface igniter not positioned correctly 3 Low voltage to the water heater 4 Electric polarity to unit is incorrect test and correct Problem in the gas valve driver circuit 1 Turn power to the water heater off for 10 seconds and the back on 2 Replace gas control valve Problem with t...

Страница 18: ...ice A Dirt in burner ports Turn off heater and gas clean burner head B Combustion air path restricted Check intake venting arrangements for YELLOWFLAME obstructions C Not enough dilution air for proper Check Intake venting arrangement for combustion obstructions A Water on the floor under heater See CONDENSATION section CONDENSATION B Water dripping from pan Provide drip TEE to catch condensation ...

Страница 19: ...IBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILLPROVIDE ONLY A REPLACEMENT WATER HEATER OR PART THEREOF THE OWNER IS RESPONSIBLE FOR ALL OTHER COSTS Such costs may include but are not limited to LIMITED RESIDENTIAL GAS WARRANTY a Labor charges for service removal or reinstallation of the water heater or part thereof b Shipping and delivery charges for forwarding the new water heater or repla...

Страница 20: ...20 125 SOUTHEAST PARKWAY FRANKLIN TN 37068 Phone 1 800 433 2545 Fax 1 800 433 2515 www aosmithwaterheaters com email parts hotwater com ...

Отзывы: