background image

7

BETWEEN THE RELIEF VALVE AND TANK.  DO NOT PLUG THE
RELIEF VALVE.

The drain line connected to this valve must not contain a reducing
coupling or other restriction and must terminate near a suitable
drain to prevent water damage during valve operation.  The
discharge line shall be installed in a manner to allow complete
drainage of both the valve and line. 

DO NOT THREAD, PLUG OR

CAP THE END OF THE DRAIN LINE.

VENTING

 

 WARNING

NEVER OPERATE THE HEATER UNLESS IT IS VENTED TO
THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID
RISKS OF IMPROPER OPERATION, FIRE, EXPLOSION OR
ASPHYXIATION.

VENT PIPE TERMINATION

The first step is to determine where the vent pipe will terminate,
see Figures 3, 8 and 9.  The vent may terminate through the roof
as shown in Figure 9 or through a sidewall as shown in Figure 8.

IMPORTANT

The vent system must terminate so that proper clearances are
maintained as cited in local codes or the latest edition of the
National Fuel Gas Code, ANSI Z223.1, 7.3.4e and 7.8a, b.

For your convenience instructions on proper installation through a
sidewall are provide in Figure 3 and the numbered points below:

1. The exit terminals of a mechanical vent system shall be not

less than 7 feet above grade when located adjacent to public
walkways.

2. A venting system shall terminate at least 3 feet above any

forced air inlet located within 10 feet.

3. The venting system shall terminate at least 4 feet below, 4

feet horizontally from or, 1 foot above any door, window or
gravity air inlet  into any building.

4. The manufacturer also recommends that the vent system

termination not be installed closer than 3 feet from an inside
corner of an L shaped structure and not be less than 1 foot
above grade.  The vent shall terminate a minimum of 12''
above expected snowfall level to prevent blockage of vent
termination.

5. The vent termination shall not be mounted directly above or

within 3 feet horizontally from an oil tank vent or gas meter to
avoid potential freeze-up from condensation.

Plan the vent system layout so that proper clearances are
maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by
building codes as "vent connectors".  Required clearances from
combustible materials must be provided in accordance with
information in this manual under LOCATION OF HEATER and
INSTALLATION OF VENT SYSTEM, and with the National Fuel
Gas Code and local codes.

PLANNING THE VENT SYSTEM

Plan the route of the vent system from the discharge of the blower
to the planned location of the vent terminal.

1. Layout the total vent system to use a minimum of vent pipe

and elbows.  Take into consideration that an elbow will be
necessary to make the first vent pipe connection to the power
venter outlet, see Figure 6.

2. This water heater is capable of venting the flue gases the

equivalent of thirty (30) feet of 3 inch pipe or eighty-five (85)
feet of 4 inch pipe as listed in Table 1.

TABLE 1

Number of

3" Maximum

4" Maximum

90° Elbows

Pipe (Feet)

Pipe Feet

ONE (1)

25

80

TWO (2)

20

75

THREE(3)

15

70

FOUR (4)

10

65

FIVE (5)

- - -

60

Minimum of 7 equivalent feet (one {1} elbow and 2 feet) must
be installed for 3" and 4" pipe.

NOTE:

  The equivalent feet of pipe listed above are exclusive

of  the "Tee" termination.  That is, the termination "Tee", with
installed screens, is assumed to be in the system and the
remainder of the system must not exceed the thirty (30)
equivalent feet of 3 inch pipe or eighty five (85) equivalent feet
of 4 inch pipe.

3. The blower discharge adapter is made to accept only straight

sections of 3" pipe.  To start a minimum of 2 inches of 3" pipe
must be attached to the blower discharge, see Figure 6.

If using 3 inch vent pipe:

A minimum of 2 inches, maximum of 4 feet of 3" pipe must be
attached to the blower before the first 3-inch elbow.  After the
first elbow add the additional venting required for the
installation.  The total system cannot exceed 30 equivalent
feet of venting, where each elbow is equal to 5 feet of straight
pipe.

If using 4 inch vent pipe:

Two inches of 3" pipe must be attached to the blower
discharge.  A 4" x 3" reducer is added and then up to maximum
4 feet of 4 inch pipe added before the first elbow.  An additional
4" x 3" reducer and (1) foot of 3" pipe must be added to the
end of the vent system before terminating into the 3" tee.  The
total system cannot exceed 85 equivalent feet of 4" venting,
where each elbow is equal to 5 feet of straight pipe.

       

FIGURE 4

Содержание FPSH-75

Страница 1: ...ing instructions as well as the WARNING and CAUTIONS CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE RESIDENTIAL GAS WATER HEATERS OWNER S MANUAL ADIVISION OFA O SMITH CORPORATION www hotwater com GET TO KNOWYOUR WATER HEATER 2 GENERAL SAFETY INFORMATION 3 4 INSTALLATION 4 12 OPERATION 12 14 MAIN...

Страница 2: ...ased locally FPSH 75 with Hot Surface Ignition GET TO KNOW YOUR WATER HEATER A VENT PIPE B ANODE C HOT WATER OUTLET D OUTLET 120 VAC E FLUE BAFFLE F GASSUPPLY G MAINMANUALGAS SHUT OFF VALVE H GROUND JOINT UNION J DIRT LEG K OUTER DOOR L UNION M INLET WATER SHUT OFF VALVE N COLD WATER INLET O INLET DIP TUBE P TEMPERATUREAND PRESSURE RELIEF VALVE Q EMBLEMANDRATINGPLATE R INSULATION S VENT TERMINAL T...

Страница 3: ... cause yourself Go to a neighbor s house leaving your doors open to ventilate the house then call your gas supplier or service agent Keep area clear until a service call has been made At times you may not be able to smell an LP gas leak One cause is odor fade which is a loss of the chemical odorant that gives LP gas its distinctive smell Another cause can be your physical condition such as having ...

Страница 4: ...closet having minimum clearances from combustible material of 0 clearance from sides and rear 5 from the front and 12 from the top Standard clearance If clearances stated on the heater differ from standard clearances install water heater according to clearances stated on heater A minimum clearance of 4 must be allowed for access to replaceable parts such as the thermostats drain valve and relief v...

Страница 5: ...e must be installed Please refer to Figure 2 for suggested piping arrangement FIGURE2 CLOSED WATER SYSTEM A closed system will exist if a back flow preventer check valve pressure reducing valve or other similar device is installed in the cold water line between the water heater and the street main or well Excessive pressure may develop due to the thermal expansion of heated water causing premature...

Страница 6: ... manual or on water heater With main burner in operation paint pipe joints including flanges pilot gas tubing connections and control inlet and outlet with rich soap and water solution Bubbles indicate gas leak To stop leak tighten flange screws joints and pipe connections Replace part if leak can t be stopped DISCONNECT THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF VALVE FROM THE GAS SUPPLY PIPING SY...

Страница 7: ...erving power vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and INSTALLATION OF VENT SYSTEM and with the National Fuel Gas Code and local codes PLANNING THE VENT SYSTEM Plan the route of the vent system from the discharge of the blower to the...

Страница 8: ...nt terminal by using the cover plate as a template to mark the hole for the vent pipe to pass through the wall BEWARE OF CONCEALED WIRING AND PIPING INSIDE THE WALL 2 If the Vent Terminal is being installed on the outside of a finished wall it may be easier to mark both the inside and outside wall Align the holes by drilling a hole through the center of the template from the inside through to the ...

Страница 9: ...sure E Splice field wiring into existing wiring using code authorized method wire nuts etc F Be certain that neutral and line connections are not reversed when making these connections G Ground heater properly This water heater must be grounded on accordance with the National Electric Code ANSI NPA70 and or local codes These must be followed in all cases The water heater must be connected to a gro...

Страница 10: ...be supported every 5 feet of vertical run and every 3 feet of horizontal run All piping and fittings must be joined by the proper procedures as described under VENT PIPE PREPARATION FIGURE9 IMPORTANT The vent system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code ANSI Z223 1 and as listed below 1 Vent Termination m...

Страница 11: ... type of cutter is used the flare on the end must be completely removed STEP A NOTE Power saws should be specifically designed to cut plastic pipe B Deburring Use a knife plastic pipe deburring tool or file to remove burrs from the end of small diameter pipe Be sure to remove all burrs from around the inside as well as the outside of the pipe A slight chamfer bevel of about 10 15 should be added t...

Страница 12: ...uld not be disturbed immediately after the cementing procedure and sufficient time should be allowed for proper curing of the joint Exact drying time is difficult to predict because it depends on variables such as temperature humidity and cement integrity For more specific information you should contact your solvent cement manufacturer STEPG OPERATION WARNING DO NOTATTEMPTTO OPERATE WATER HEATER W...

Страница 13: ...a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATINGINSTRUCTIONS 1 STOP Read the safety information above on this label 2 Set the thermostat to the lowest setting 3 Turn the ON OFF switch on the b...

Страница 14: ...exceed the thermostat setting by up to 30 F If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing the point of use temperature by mixing cold and hot water are available see Figure 2 Also available are inexpensive devices that attach to faucets to limit hot water temperatures Contact a licensed plumber or the local plumb...

Страница 15: ...NG THE DRAFT Operate the water heater for several minutes and check to see if it is venting properly by passing a lit match or paper near the opening of the Air Mixing Box see Figure 11 If the draft is proper the match flame will be drawn into the Air Mixing Box If not the combustion products will tend to extinguish the flame If an improper draft exists do not operate the water heater until proper...

Страница 16: ... heater requires no special care other than the normal maintenance as noted above If you are having a problem with your water heater before calling for service please refer to the following TROUBLESHOOTING sections If service becomes necessary contact your dealer installer or an authorized service agent Do not attempt to repair the water heater yourself Any work performed by unauthorized personnel...

Страница 17: ...into 115 vac outlet Repair service to outlet Replace switch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more than 30 Equivalent feet of 3 inch pipe or85 equivalent feet of 4 inch pipe installed or vent terminal blockage If at least 102 vac less than 30 eq...

Страница 18: ...e water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas control valve Flame signal sensed out of 1 Replace gas control valve prop...

Страница 19: ...rnish the ORIGINAL OWNER a replacement A O Smith water heater of equivalent size and current model or a replacement part for any component part which fails in normal use in accordance with the warranty terms and conditions specified below THE A O SMITH REPLACEMENT MODEL OR PART WILL BE WARRANTED FOR ONLYTHE UNEXPIRED PORTION OFTHE ORIGINAL WARRANTY The warranty period will be determined by the ori...

Страница 20: ...20 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E MAIL parts hotwater com ...

Отзывы: