background image

6

VENT PIPE TERMINATION

NOTE: Before installing the Sealed Shot power vent, it is

recommended that the location of the vent  pipe
terminations (intake vent terminal and exhaust vent
terminal) be determined.

 

WARNING

THIS UNIT CONSISTS OF AN INTAKE VENT TERMINAL AND
AN EXHAUST VENT TERMINAL.  THE INTAKE VENT TERMINAL
CONSISTS OF A 45 DEGREE ELBOW WITH A DIVERTER
PLATE AND SCREEN ADAPTER.  SEE FIG. 3.

IT IS VERY CRUCIAL THAT THE INTAKE VENT TERMINAL HAS
THE DIVERTER PLATE AND SCREEN ADAPTER ORIENTED
CORRECTLY AS SHOWN IN FIG. 3.  IF THE DIVERTER PLATE
IS NOT LOCATED AS SHOWN, GO TO THE NEAREST DEALER
AND HAVE THE INTAKE VENT TERMINAL REPLACED.

FIGURE 3

THE EXHAUST VENT TERMINAL CONSIST OF A 45 DEGREE
ELBOW WITH A MESH SCREEN PRESSED INTO THE ELBOW.
SEE FIG 3.

 

WARNING

IF THE  INTAKE VENT TERMINAL  AND  EXHAUST VENT
TERMINAL DO NOT RESEMBLE THE DIAGRAMS SHOWN IN
FIG. 3, THEN GO TO THE NEAREST DEALER AND HAVE THEM
REPLACE THE VENT TERMINALS WITH THE CORRECT
ONES.

VENT TERMINAL  INSTALLATIONS

IMPORTANT

The vent system must terminate so that proper clearances are
maintained as cited in local codes or the latest edition of the
National Fuel Gas Code, ANSI Z223.1, 7.3.4e, and 7.8a, b as
follows.

1.

The intake and exhaust vent terminals of a mechanical vent
system shall be not less than 7 feet above grade when located
adjacent to public walkways. (fig. 4)

2.

The venting system shall terminate at least 3 feet above any
forced air inlet located within 10 feet. (fig. 4)

3.

The venting system shall terminate at least 9 inches below,
9 inches horizontally from or 9 inches above any door,
window, or gravity air inlet into building.

4.

The manufacturer also recommends the vent system
terminations not to be installed closer than 3 feet from an
inside corner of an L shaped structure, and not less than 1
foot above grade. The vent shall terminate a minimum 12"
above expected snowfall level to prevent blockage of vent
termination.

5.

The vent termination shall not be mounted directly above or
within 3 feet horizontally from an oil tank vent or gas meter
to avoid potential freeze-up from condensation.

Plan the vent system layout so that proper clearances are
maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by
building codes as “vent connectors”.  Required clearances from
combustible materials must be provided in accordance with
information in this manual under LOCATION OF HEATER and
VENT HOOD INSTALLATIONS, and with the National Fuel Gas
Code and local codes.

IMPORTANT

Plan the layout of the vent system backwards from the vent
termination to the appliance.  Take into consideration that an elbow
will be necessary to make the first vent pipe connection to the
blower outlet.

 

WARNING

USE ONLY THE VENT HOOD SUPPLIED WITH THIS KIT.
TERMINATION OF A VENT SYSTEM WITH A DEVICE OTHER
THAN THE SUPPLIED VENT HOOD WILL AFFECT SYSTEM
PERFORMANCE AND RESULT IN A SAFETY HAZARD.

SIDE WALL VENT TERMINAL INSTALLATION

IMPORTANT

THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE
VENT TERMINAL AND AN EXHAUST VENT TERMINAL.  THE
INTAKE VENT TERMINAL IS A 45 DEGREE PVC ELBOW WITH
A DIVERTER PLATE AND SCREEN ADAPTER WHILE THE
EXHAUST VENT TERMINAL IS A 45 DEGREE ELBOW WITH A
MESH WIRE SCREEN.

IMPORTANT

WHEN TERMINATING THE TERMINALS ON A SIDEWALL, THE
FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL
LOCATION MUST BE FOLLOWED.

1.

The intake vent terminal and the exhaust vent terminal must
terminate on the same exterior wall.

2.

The vertical centerline of the intake vent terminal must be
located at a minimum of 16 inches from the vertical centerline
of the exhaust vent terminal.

3.

The horizontal centerline of the intake vent terminal may not
be located lower than 4 inches below the horizontal centerline
of the exhaust vent terminal.

The specifications are displayed in fig. 5.

Содержание FPD SEALED SHOT

Страница 1: ... for buying this energy efficient water heater from A O Smith Water Products Company We appreciate your confidence in our products You should thoroughly read this manual before installation and or operation of this water heater Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS RESIDENTIAL GAS WATER HEATERS OWNER S MANUAL A DIVIS...

Страница 2: ...chased locally A VENT PIPE EXHAUST B ANODE C HOT WATER OUTLET D OUTLET 115 V AC E FLUE BAFFLE F GAS SUPPLY G MAIN MANUAL GAS SHUT OFF VALVE H GROUND JOINT UNION J DIRT LEG K OUTER DOOR L UNION M INLET WATER SHUT OFF VALVE N COLD WATER INLET O INLET DIP TUBE P TEMPERATURE AND PRESSURE RELIEF VALVE Q EMBLEM AND RATING PLATE R INSULATION S VENT TERMINAL EXHAUST T DRAIN VALVE U HSI ASSEMBLY V FLUE W D...

Страница 3: ...ur A O Smith water heater meets or exceeds the National Appliance Energy Conservation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary WARNING Should you choose to apply an insulation blanket to this heater you should follow these instructions See Figure 1 for identification of components mentioned below Failure to follow these instruc...

Страница 4: ...OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE AREA ADJACENT TO THE HEATER OR TO LOWER FLOORS OF THE STRUCTURE When such locations cannot be avoided a suitable drain pan should be installed under the heater see fig 1 The pan should have a minimum length and width of at least 2 inches greater than the diameter of the heater and should be piped to an adequate drain Drain pans suitable for these hea...

Страница 5: ... valve inlet The valve inlet has a hexagon shape for use with a backup wrench Apply joint compounds pipe dope sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on gas valve DISCONNECT THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF VALVE FROM THE GAS SUPPLY PIPING ...

Страница 6: ...de The vent shall terminate a minimum 12 above expected snowfall level to prevent blockage of vent termination 5 The vent termination shall not be mounted directly above or within 3 feet horizontally from an oil tank vent or gas meter to avoid potential freeze up from condensation Plan the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power...

Страница 7: ...t for a saws all or sabre saw blade Cut around the marked circle staying approximately one quarter inch outside of the line This will allow the vent pipe to easily slide through the opening The resulting gap will be covered up by the vent terminal cover plates Repeat this step on the inside wall if necessary 4 Cut a length of 3 inch PVC pipe about 3 5 inches longer than the wall thickness at the o...

Страница 8: ... vent termination must not be closer than 16 and not farther away than 24 6 The intake vent terminal and the exhaust vent terminal must be oriented facing downward and the same direction The specifications are displayed in figure 7 FIGURE 7 INSTALLATION SEQUENCE NOTE BEFORE BEGINNING INSTALLATION OF ANY VENT PIPE READ VENT PIPE PREPARATION SECTION ON PAGES 12 14 1 After the points of termination h...

Страница 9: ...e the larger flexible rubber coupling on the rear air tube and tighten the hose clamp Make sure to remove plastic cap on air tube before installing coupling 7 Cut a 3 inch PVC pipe approximately 4 inches for the 40 gallon and approximately 5 75 inches for the 50 gallon Take the cut 3 inch PVC pipe and place into rubber coupling and tighten hose clamps Fig 10 8 Locate the blower assembly and previo...

Страница 10: ...be placed so as to hold the harness as close as possible to the side of the unit and away from any hot surfaces THIS UNIT IS MANUFACTURED WITH AN EXTERNAL CONTROL HARNESS FOR EASIER REPLACEMENT IF THE HARNESS OR CONNECTORS SHOULD BECOME INOPERABLE 13 Do not plug in power cord until vent system is completely installed The power vent operates on 110 115 VAC therefore a grounded outlet must be within...

Страница 11: ... ASTM F 891 Schedule 40 CPVC ASTM F 441 or ABS ASTM D 2661 pipe The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM D 2665 Use CPVC fittings ASTM F 438 for CPVC pipe and ABS fittings ASTM D 2661 3311 for ABS pipe If CPVC or ABS pipe and fittings are used then the proper cement must be used for all joints including joining the pipe to the Termination Tee P...

Страница 12: ...install the vent system with a slight 1 8 inch per five foot of pipe maximum downward slope maximum of 1 inch in total run 7 The vent system should be installed starting at the blower assembly discharge and running to the coupling installed to join the vent terminal on the inside wall figures 15 16 for reference The vent system should be supported every five 5 feet of vertical run and every three ...

Страница 13: ...ompletely removed NOTE Power saws should be specifically designed to cut plastic pipe STEP A B Deburring Use a knife plastic pipe deburring tool or file to remove burrs from the end of small diameter pipe Be sure to remove all burrs from around the inside as well as the outside of the pipe A slight chamfer bevel of about 10 15 should be added to the end to permit easier insertion of the pipe into ...

Страница 14: ... system to escape 3 Fully open the cold water inlet pipe valve allowing the heater and piping to be filled Fig 1 M 4 Close the hot water faucet as water starts to flow 5 The heater is ready to be operated TEMPERATURE REGULATION DANGER DANGER THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY ...

Страница 15: ...ny appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Turn the ON OFF switch on the blower control box to the OFF position 3 Set the thermostat to the lowest setting Turn thermostat dial fully...

Страница 16: ...NSI Z223 1 NFPA 54 FAILURE TO REPLACE THE ORIFICE WILL RESULT IN IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE PRODUCING CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH WATER HEATING IGNITION SEQUENCE Make sure gas and electric power are connected properly 1 The ignition control module is powered and monitors the system waiting for a call f...

Страница 17: ...t that a serviceman be called to determine the reason for limit operation and thus avoid repeated thermostat replacement Lower the temperature adjustment dial setting on new control VENTING SYSTEM HAVEVENTING SYSTEM CHECKED EVERY SIX MONTHS FOR OBSTRUCTIONS AND OR DETERIORATION IN VENT PIPING POWER VENTER MAINTENANCE The SEALED SHOT venter must be inspected four times a year Points of inspection a...

Страница 18: ...A d e n o i t i s o p t o n r o d e t a n i m a t n o c d o r e s n e s e m a l F y l t c e r r o c y l t c e r r o c d e n o i t i s o p t o n t n e m e l e I S H t o n g n i r i w d o r e s n e s e m a l f r o t n e m e l e I S H y l r e p o r p d e t c e n n o c r e n r u b d n a d o r e m a l f n e e w t e b c a V 0 0 1 n a h t s s e L l o r t n o c o t t u p n i c a V 0 2 1 h t i w n a p r o ...

Страница 19: ... s n I E M A L F W O L L E Y s t r o p r e n r u b n i t r i D A r e n r u b n a e l c s a g d n a r e t a e h f f o n r u T d a e h d e t c i r t s e r h t a p r i a n o i t s u b m o C B r o f t n e m e g n a r r a g n i t n e v e k a t n i k c e h C s n o i t c u r t s b o r e p o r p r o f r i a n o i t u l i d h g u o n e t o N C n o i t s u b m o c r o f t n e m e g n a r r a g n i t n e v e...

Страница 20: ...uding freezing fire floods or lightning any misuse abuse or alteration of it any operation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMENT WATER HEATER OR PART THEREOF THE OWNER IS RESPONSIBLE FOR ALL OTHER COSTS Such costs may include but are not...

Отзывы: