2.1.3 Gas connection

The gas supply to this appliance must
be installed in accordance with BS 6891
(1988).
Fit the 1/2" gas supply cock supplied
with this unit immediately before the gas
control block. No heat or soldered joints
should be applied in the vicinity of the
gas control block, as they could cause
damage to the control.
All connections and joints should be
tested for gas soundness with a
suitable leak detector (do not use a
naked flame).

2.1.4 Flue system

The water heater should be fitted with a
flue system connected to the draught
diverter. The flue pipe should rise for at
least 50 cm. vertically before the
inclusion of any bends. If a horizontal
run of flue is required this should be
kept to the minimum length possible and
incorporate a rise of 6 cm. per metre of
run. A split clip or flange should be
provided in the flue close to the draught
diverter for ease of servicing.

All flue materials should be corrosion
resistant i.e. stainless steel or
galvanised and must include a tested
and approved terminal to BS 5440 part I.
If the flue passes through any
combustible material measures must be
taken to protect against the possibility of
fire.
All flues must terminate in free air space
approx. 1.5 metres from any vertical
surface of structure i.e. chimney
stacks, roof parapets, etc. If an existing
chimney or flue is to be used this should
be swept clean and be free of debris
before an approved liner is installed and
connected to the water heater.

2.1.5 Flue down draught safety

device

The draught diverter has already been
provided with a temperature probe ex
factory for signalling returning flue
gases. The probe of the down draught

supervision must remain installed on
the draught hood.

Connect the slide connectors of the
down draught supervision to the
thermocouple (see Figure 5) and install
the head of the down draught
supervision in the bracket; see Figure
5. The draught hood must be positioned
in its normal place with the temperature
probe at the front of the boiler. Pass
the wiring of the temperature probe
through the cable duct.

Note
The screws with which the down
draught supervision has been mounted
in the bracket are already in the
bracket.

Figure 5 -  Down draught supervision
installation

IMD 0422

IMD 0422

Содержание EQ 115 G

Страница 1: ...INSTALLATION AND USER INSTRUCTIONS HOTWATERSTORAGEHEATERS UNITEDKINGDOM IRELAND MODELS EQ 115 G EQ 155 G EQH 200 G...

Страница 2: ...and or bodily harm Installation and commissioning should be carried out by a qualified competent installer The type of gas and the value at which the appliance is set standard in the factory are regis...

Страница 3: ...stment 15 2 4 Putting out of operation 15 2 5 Temperature regulation 16 2 6 Setting the nominal heat input 17 2 7 Conversion to another type of gas 17 2 8 Maintenance 19 2 8 1 Sacrificial anode 19 2 8...

Страница 4: ...sary heat loss When the appliance is filled with water it continuously is under water pressure As hot water is drained from the tank cold water is added immediately A flue baffle has been placed in th...

Страница 5: ...Hot water outlet 3 Insulation 4 Flue tube 5 Glass lined tank 6 Gas control valve 7 Cold water inlet 8 T P valve connection 9 Outer casting 10 Flue baffle 11 Sacrificial anode 12 Drain valve 13 Atmosph...

Страница 6: ...helix coil which is connected to the lower edge of the draught diverter The helix coil has been connected to the thermostat by means of a capillary tube The wiring that is connected to the thermostat...

Страница 7: ...k with T R S 1 T R S thermostat 2 Sensor combustion products dicharge safety device 3 Thermocouple with built in interrupter 4 Thermocouple 5 Gas control block 6 Reset button 7 Pilot burner 8 Temperat...

Страница 8: ...nsions EQ 115 EQ 155 EQH200 A 1280 1370 1670 B 1120 1210 1540 D 465 515 515 F 545 595 605 G 80 80 100 K 325 325 380 L 270 295 395 M 1180 1270 1590 N 1180 1270 1590 R 230 230 255 S 945 1030 1380 V 205...

Страница 9: ...9 Figure 3 Dimensions AOS 0481...

Страница 10: ...50 Diameterpilotorifice mm 2x0 27 2x0 27 2x0 27 Heating time T 44 K min 45 49 40 DATABUTANEG30 28 30mbar Nominalload gross kW 10 1 12 2 17 6 Supplypressure mbar 30 30 30 Burnerpressure mbar 30 30 30...

Страница 11: ...following British standards 5440 5546 6644 6700 6798 and 6891 Some chemicals produce vapours which can cause rapid failure of thermocouples burners and storage tanks if they are drawn into the combust...

Страница 12: ...in valve Figure 4 Connection diagram unvented system 8 Pressure limiting valve 9 Expansion valve A Gas supply B Hot water delivery C Cold water inlet D Hot water taps E Return circulation See Figure 4...

Страница 13: ...al to BS 5440 part I If the flue passes through any combustible material measures must be taken to protect against the possibility of fire All flues must terminate in free air space approx 1 5 metres...

Страница 14: ...and press the piezo ignitor several times until the pilot burns see Figure 6 Figure 6 Operation of the gas control block 5 Keep the control button pushed in for approximately 20 seconds After releasin...

Страница 15: ...he edge of the burner chamber 2 3 Pilot adjustment The pilot can be adjusted by means of the regulating screw under the plastic cover on the right hand side of the gas control block Turn the screw clo...

Страница 16: ...e gas supply The main burner will ignite as soon as a reduction in water temperature is sensed by the thermostat The main burner will shut down as soon as the preset temperature is achieved Position 1...

Страница 17: ...stment see Figure 9 To make this possible the temperature control knob should be removed by pulling it straight forward making the pr adj visible Turning clockwise reduces the pressure turning anti cl...

Страница 18: ...the main gas tap in the gas supply 2 Demount the burner see Cleaning 3 Replace the injector of the main burner and the pilot burner with the correct injectors from the conversion set see tables above...

Страница 19: ...the type of the appliance and the serial number 4 b Conversion from LP gas to natural gas Put the pressure regulator into operation To do this the temperature regulating knob should be pulled straigh...

Страница 20: ...tion of these should be checked If necessary the burner pressure of the main burner should be reset 2 8 3 Inspection of the internal waterside surfaces Formation of lime scale depends on the quality a...

Страница 21: ...or open taps 4 Is the gas supply adequate Check and correct if necessary 5 Perhaps the hot water consumption is higher than was originally calculated 6 Check whether the cold water inlet has been cor...

Страница 22: ...r water supply pressure with a maximum of 8 bar The amount of cold water that is added is equal to the amount of hot water used The gas control block automatically regulates the gas supply The main bu...

Страница 23: ...ief button The water has to flow out in a forceful jet Check whether the discharge pipe is open We recommend a service agreement on an annual basis To be able to order spare parts it is important to n...

Страница 24: ...tact your installer or the local gas company Clean the pilot burner Find the cause and remove it Set the temperature regulator at a lower temperature Replace the thermocouple Restore the connection Op...

Страница 25: ...ur installer See Condensation Tighten the threaded connections Trace the cause Reduce your hot water use Allow the appliance enough time to warm up water Safety thermostat has closed the gas supply be...

Страница 26: ...Cut Off device c at water pressures and or energy inputs which do not exceed those stated on the rating plate of the water heater d in a non corrosive atmosphere or area e with an approved temperature...

Страница 27: ...uestion further A O Smith does not guarantee this water heater as suitable for purpose except within the terms of warranty detailed above A O Smith Water Products Company will not be liable by virtue...

Страница 28: ...28 MODEL SERIALNUMBER ORIGINALDATEOFINSTALLATION NAMEOWNER ADDRESS TOWN STAMP INSTALLER Important This form should be filled in completely within two weeks of installation...

Страница 29: ...29...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...32 0307 985 R1...

Отзывы: