Installation and Service Manual Epsilon-Series
30
Service-Mode
SERV
Value
Description
Range
1
OFF
boiler in operation with burner function on
OFF - max.
2
OFF
fan adjustable and burner off
OFF - max.
3
OFF
pump adjustable with burner on
OFF - max.
4
OFF
showroom position ON = active and OFF = non active
ON - OFF
.
.
.
.
Error-Mode
ERRO
Value
Description
Err.L - Err.5
Last saved error until 5 last predecessing errors
1
error code
2
operation status boiler
3
°C
flow water temperature T1
4
°C
return water temperature T2
5
kW
load
6
%
pump capacity
heating line adjustments Parameter Step 6 and 7
graph 10.2.a
outside temperature in °C
flow water temperature in °C
10.3 Activating factory settings (green key function)
To activate the factory settings again please follow the next procedure (Note: all altered
adjustments will be set back):
- Select, when necessary, the technical read out;
- Select with the MODE-key chapter PARA;
- Press the STORE-key.
The word "Copy" will appear and the facory settings are active again.
Parameter-, Info-, Service- and Error-chapters
Table 10.2.a