8
1.2.2 Checking the Float Switch
Switch off the feed voltage and remove
the fuses from the elements. In this
way the control circuit can be tested
without the elements being put into
operation. Drain the device until the
water is de
fi
nitely below the
fl
oat switch.
If desired the
fl
oat switch can now be
removed for visual inspection. Check
the resistance of the contacts with a
multimeter and check whether the switch
point is situated approximately halfway
along the stroke of the
fl
oat. (For new
contacts this resistance is between 1
and 1.5 Ohms). Screw the
fl
oat switch
back into the tank and place it vertically.
Check the exposure height. Close the
door and connect the feed voltage. The
safety relays must not come in. (The
tautening and release of the safety
relays is clearly audible.) Now allow
water to
fl
ow into the device. If the water
presses the
fl
oat upwards, the
fl
oat
switch closes the control circuit and the
safety relays will tauten. Then drain the
device once again. The lowering of the
water level will lead to the
fl
oat switch
blocking the control circuit once again
and the safety relays will release. Repeat
this operation at least one time.
Switch off the feed voltage and
fi
t the
fuses of the elements again. Close the
door and reconnect the feed voltage.