V.  PHASE CONVERSION

    A.  IMMERSION THERMOSTAT MODEL

     

THREE PHASE TO SINGLE PHASE

    1.  Disconnect blue wires and yellow wires from terminal L-3.

    2.  Connect all blue wires to terminal L-1 (with black wires).

    3.  Connect all yellow wires to terminal L-2 (with red wires).

    4.   Incoming power will be connected to 

     

terminals L-1 and L-2 at job site.

   

   

   

 

  B.  IMMERSION THERMOSTAT MODEL 

     

SINGLE PHASE TO THREE PHASE

  1.  Disconnect blue wires from terminal L-1.

  2.  Disconnect yellow wires from terminal L-2.

  3.  Connect all blue wires and yellow wires to terminal L-3.

  4.  Incoming power will be connected to terminals 

     

L-1, L-2 and L-3 at job site.

IMMERSION THERMOSTAT MODEL TRANSFORMER

 

IMMERSION THERMOSTAT MODEL

SINGLE PHASE TERMINAL BLOCK

 

IMMERSION THERMOSTAT MODEL

 THREE PHASE TERMINAL BLOCK

IMMERSION THERMOSTAT MODEL  TRANSFORMER 

CONNECTION TABLES

 

Volts 

Line On 

Load on

 

208 

Common & 208

 

240 

Common & 240  Secondary

 

277 

Common & 277 

  120V

 

480 

Common & 480

480

277

240

208

CO

M

Содержание DURA-Power DRE-52

Страница 1: ...120 Commercial Electric Water Heaters Series 100 CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE ATTEMPTING ANY CONVERSION 500 Tennes...

Страница 2: ...ar the electrical system of the heater Never touch electrical components with wet hands or when standing in water REQUIRED ABILITY CONVERSION OF ANY WATER HEATER LISTED IN THIS MANUAL REQUIRES ABILITY...

Страница 3: ...pleting the unit conversion CONVERSION KIT NUMBER TABLE Models Allowed For Conversion Desired Input Conversion Kit No At Desired Voltage Total kW Element kW 208V 240V 277V 480V DVE DRE 52 80 120 with...

Страница 4: ...storage bin C Open the appropriate conversion kit and remove the elements Check each element to ensure correct voltage and wattage D Install the new element starting it by hand Anew O ring gasket shou...

Страница 5: ...HASE TO THREE PHASE 1 Disconnect blue wires from terminal L 1 2 Disconnect yellow wires from terminal L 2 3 Connect all blue wires and yellow wires to terminal L 3 4 Incoming power will be connected t...

Страница 6: ...L 3 5 Incoming power will be connected to terminals L 1 L 2 and L 3 at job site VI CAUTION Recheck all terminals for tightness proper wiring per schematic and neatness of wiring Heater should be no l...

Страница 7: ...late E SHIPPING CRATE Close and tape the plastic flap on front of crate CHECK LIST All affected parts have been installed properly and have been checked for tightness All affected wires have been chec...

Страница 8: ...SO WILL DAMAGE INTERNAL PARTS OHMS RESISTANCE TABLE VOLTAGE WATTAGE 208 240 480 2000 21 63 28 80 115 20 3000 14 42 19 20 76 80 4000 10 82 14 40 57 60 4500 9 61 12 80 51 20 5000 8 65 11 52 46 08 6000 7...

Страница 9: ...9 NOTES...

Страница 10: ...500 Tennessee Waltz Parkway Ashland City TN 37015 1 800 433 2545 www hotwater com...

Страница 11: ...uffe eau lectriques commerciaux S rie 100 ATTENTION LE TEXTE EN ROUGE OU ENCADR DE ROUGE VISE ASSURER LA S CURIT DES UTILISATEURS IL FAUT DONC LE LIRE ATTENTIVEMENT AVANT DE CONVERTIR LE CHAUFFE EAU 5...

Страница 12: ...r Underwriters Laboratories Inc Par cons quent elles sont interdites et ne doivent m me pas tre entreprises Il convient de noter et de respecter la limitation suivante le chauffe eau apr s conversion...

Страница 13: ...ersion d taill es pages 9 13 5 La conversion termin e remplir la liste de v rification page 12 NUM RO DE PI CE DE LA TROUSSE DE CONVERSION Mod les pouvant tre convertis Puissance voulue Tension d util...

Страница 14: ...de stockage appropri C Retirer les l ments de la trousse appropri e et s assurer que la puissance et la tension de chacun correspondent aux caract ristiques voulues D Placer le nouvel l ment dans son...

Страница 15: ...ES 1 D brancher les fils bleus de la borne L1 2 D brancher les fils jaunes de la borne L2 3 Brancher les fils bleus et les fils jaunes la borne L3 4 L alimentation lectrique se fait aux bornes L1 L2 e...

Страница 16: ...ENTION Les bornes doivent tre bien serr es les connexions doivent tre conformes aux sch mas et le travail doit tre fait de sorte que le chauffe eau converti respecte les exigences de qualit du travail...

Страница 17: ...r vis e E EMBALLAGE Refermer le rabat du film en plastique et le coller avec du ruban adh sif LISTE DE V RIFICATION Chaque pi ce touch e par la conversion est install e correctement et son serrage a...

Страница 18: ...TRUCTIONS DE REMPLISSAGE LE NON RESPECT DE CETTE EXIGENCE EMDOMMAGERA LES COMPOSANTES INTERNES R SISTANCE LECTRIQUE TENSION V PUISSANCE W 208 240 480 2 000 21 63 28 80 115 20 3 000 14 42 19 20 76 80 4...

Страница 19: ...19 NOTES...

Страница 20: ...500 Tennessee Waltz Parkway Ashland City TN 37015 tats Unis 1 800 433 2545 www hotwater com...

Отзывы: