   hotwater  .com 17

The T&P valve must be manually operated at least once 
a year. Caution should be taken to ensure
1.  no one is in front of or around the outlet of the 

discharge line, and

2.  the water manually discharged will not cause any 

bodily injury or property damage because the water 
may be extremely hot.

If after manually operating the valve, it fails to completely 
reset and continues to release water, immediately close 
the cold water inlet to the water heater, follow the draining 
instructions in this manual, and replace the temperature-
pressure relief valve with a properly rated/sized new one.

Note:

 The purpose of a temperature-pressure relief valve 

is to prevent excessive temperatures and pressures in 
the storage tank. The T&P valve is not intended for the 
constant relief of thermal expansion. A properly sized 
thermal expansion tank must be installed on all closed 
systems to control thermal expansion, see “Closed Water 
Systems” and “Thermal Expansion” sections.

 Temperature-Pressure Relief Valve And Pipe 
Insulation

The T&P valve installed on this water heater is covered by 
insulation to minimize heat loss. The insulation has a hole 
on the bottom side to accommodate the valve outlet and 
allow for the piping connection. Do not restrict the outlet 
opening of the T&P valve.

T&P Relief Valve

T&P Relief Valve
Drain Line

Manual Relief Lever

T&P Relief Valve Insulation
(Outlet opening on underside)

Figure 10 

Locate the temperature and pressure relief valve on the 
water heater (also known as a T&P relief valve) (see 
Figure 10).
1.  Locate the slit running the length of the T&P relief 

valve insulation.

2.  Spread the slit open and 

fi

 t the insulation over the T&P 

relief valve (see Figure 10). Apply gentle pressure to 
the insulation to ensure that it is fully seated on the 
T&P Relief Valve. Once seated, secure the insulation 
with duct tape, electrical tape, or equivalent.

Important:

 The insulation and tape must not block the 

discharge opening or hinder access to the manual relief 
lever (Figure 10). Ensure a discharge pipe is installed into 
the T&P valve discharge opening per the instructions in 
this manual.

1.  Locate the hot water (outlet) and cold water (inlet) 

pipes to the water heater.

2.  Locate the slit running the length of a section of pipe 

insulation.

3.  Spread the slit open and slip the insulation over the 

cold water (inlet) pipe. Apply gentle pressure along 
the length of the insulation to ensure that it is fully 
seated around the pipe. Also, ensure that the base 
of the insulation is 

fl

 ush with the water heater. Once 

seated, secure the insulation with duct tape, electrical 
tape, or equivalent.

4.  Repeat steps 2 and 3 for the hot water (outlet) pipe.
5.  Add additional sections of pipe insulation as needed.

  FILLING THE WATER HEATER

 Avoid water heater damage.

 Fill tank with water before operating.

Property Damage Hazard

CAUTION

• 

Never use this water heater unless it is completely full 
of water. To prevent damage to the tank, the tank must 
be 

fi

 lled with water. Water must 

fl

 ow from the hot water 

faucet before turning “ON” gas to the water heater.

To 

fi

 ll the water heater with water:

1.  Close the water heater drain valve by turning handle 

to the right (clockwise). The drain valve is on the lower 
front of water heater (see Figure 9).

2. Important:

 If the heater is equipped with plumbing 

side taps and they are not connected to piping, ensure 
the side taps have been closed with pipe plugs.

3.  Open all hot water faucets served by the water heater 

to allow air to escape from the tank and the water 
piping. Ensure any shut-off valves between the heater 
and the faucets are in the open position.

4.  Open the cold water supply valve to the water heater.

Notes:

• 

The cold water supply valve must be left open when 
the water heater is in use.

• 

Avoid water leakage when 

fi

 lling the tank. Do not 

allow the insulation of the water heater to get wet as 
water can reduce the effectiveness of the insulation.

5.  Allow water to run until a constant 

fl

 ow is obtained. 

This will let air out of the water heater and the piping.

6.  Check all water piping and connections for leaks. 

Repair as needed.

Содержание DIRECT VENTED GAS MODELS

Страница 1: ...IS REQUIRED DIRECT VENTED GAS MODELS NOT FOR USE IN MANUFACTURED MOBILE HOMES For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE D...

Страница 2: ...ly 24 Securing Vent Termination Assembly To The Exterior Wall 24 Vent Restricter Plate 24 Uncompressing The Corrugated Tubing 24 Vent Connection To The Water Heater 25 Offset Vent Arrangement 25 Insta...

Страница 3: ...ects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects...

Страница 4: ...n the vicinity of this water heater the vent termination hood or any other appliance Avoid all ignition sources if you smell gas Do not expose water heater control to excessive gas pressure Use only g...

Страница 5: ...water heater or the vent termina tion hood where flammable products will be stored or used Vapors from flammable liquids may explode and catch fire causing death or severe burns Do not use or store fl...

Страница 6: ...carefully If you don t follow safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURYAND OR PROPERTY DAMAGE This manual contains instructions for installati...

Страница 7: ...eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half...

Страница 8: ...SSACHUSETTS INSTALLATION REQUIREMENTS 1 CONNECT ELECTRONICALLY CONTROLLED TIMER TO AN ALL BRONZE PUMP PUMP MUST ACTIVATE EVERY 6 HOURS FOR 60 SECONDS TURN PUMP TIMER OFF BEFORE CLOSING PIPING LOOP SHU...

Страница 9: ...sembly 21 Rating Plate 22 Anode under cap 23 Hot Water Outlet Nipple or Optional Nipple Anode 24 Inlet Water Shut off Valve 25 Union water connection 26 Air Inlet Snorkel 27 Air Tower 28 Airbox 29 The...

Страница 10: ...nt parts and recommended delimer may be ordered through authorized servicers or distributors When ordering parts provide complete model and serial numbers see rating plate quantity and name of part de...

Страница 11: ...metal drain pan should be installed under the water heater Metal drain pans are available at your local hardware store Such a metal drain pan must have a clearance of at least 1 greater than any poin...

Страница 12: ...he full width and depth of the appliance by at least 3 in every direction or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this war...

Страница 13: ...taining a gas water heater the vent termination hood or other open flame or spark producing appliance Examples of such locations are garages storage and utility areas The water heater must be located...

Страница 14: ...d injury Feel water before bathing or showering Temperature limiting devices such as mixing must be installed when required by codes and to ensure safe temperatures at fixtures BURN HOT HOT DANGER Som...

Страница 15: ...g the water heater for service or replacement 3 If installing the water heater in a closed water system install an expansion tank in the cold water line as specified under Closed Water Systems and The...

Страница 16: ...plate For safe operation of the water heater the temperature pressure relief valve must not be removed from its designated opening nor plugged The T P valve must be installed directly into the fittin...

Страница 17: ...harge opening or hinder access to the manual relief lever Figure 10 Ensure a discharge pipe is installed into the T P valve discharge opening per the instructions in this manual 1 Locate the hot water...

Страница 18: ...must be compatible with potable water Toxic chemicals such as those used for boiler treatment shall not be introduced into the potable water used for space heating When the system requires water for...

Страница 19: ...ately insulated to reduce heat loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Combo Heating Systems requi...

Страница 20: ...he National Fuel Gas Code ANSI Z223 1 NFPA 54 and your gas supplier concerning pipe size There must be A readily accessible manual shut off valve in the gas supply line serving the water heater and A...

Страница 21: ...ay result in fire or explosion Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap sometimes call...

Страница 22: ...er appliance Minimum 12 in from soffit Minimum 9 in to a window or door that may be opened Minimum 18 in from outside corner 1 Permitted only if veranda porch deck or balcony is fully opened on a mini...

Страница 23: ...ANCE HOLE FOR VENT Cut a clearance hole approximately 7 in diameter through the exterior wall for the vent assembly The recommended height is 64 for 40 gal models 73 for 50 gal models and 74 for 50 ga...

Страница 24: ...be then insert the outer corrugated tube through the clearance hole from exterior wall Secure the trim plate to the exterior wall then secure the vent terminal to the exterior wall with 4 screw anchor...

Страница 25: ...tops SMOOTH EASY CURVE GEAR CLAMP CUTAWAY TO SHOW DETAILS RESTRICTER PLATE STOP Figure 24 Apply hi temp red silicone included around the collar on air manifold box Pull the outer corrugated pipe all t...

Страница 26: ...allation 5 1 1 17 MIN Figure 30 NOTES applies to Figure 28 thru Figure 30 1 In any installation the total of dimension A plus dimension B must not exceed 89 2 This heater can be installed with 0 clear...

Страница 27: ...to check all connections and fittings for possible gas leaks Vent Pipe System Evenly stretched out between water heater and vent termination hood Smooth bend with adequate support to prevent sagging...

Страница 28: ...e knob to the OFF position and call a qualified service technician or your gas supplier DANGER Hotter water increases the risk of scald injury Consult the instruction manual before changing the temper...

Страница 29: ...hown on the gas control valve thermostat are approximates The actual temperature of the heated water may vary Important Adjusting the thermostat past the 120 F mark on the temperature dial will increa...

Страница 30: ...or hot water including dishwashers washing machines and shower heads Excessive condensate may be noticed during the winter and early spring months when incoming water temperatures are at their lowest...

Страница 31: ...the system see Water Piping section Smelly water may be eliminated or reduced in some water heater models by replacing the anode s with one of less active material and then chlorinating the water heat...

Страница 32: ...risk or asphyxiation Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors Spray can propellants cleaning solvents refrigerator and air...

Страница 33: ...ing leaks Do not insert any sharp objects into the inlet or outlet connections Damage to the gas control valve thermostat may result Replacing The Gas Control Valve Thermostat To replace the gas contr...

Страница 34: ...screws securing the burner to the manifold see Figure 35 Important DO NOT remove the orifice 3 Remove the screw securing the pilot thermopile assembly to the pilot bracket and keep for reuse later se...

Страница 35: ...bustion chamber Important Do not operate the water heater if the door gasket does not create a seal between the manifold door and the combustion chamber 6 Reconnect the manifold tube 3 4 wrench and pi...

Страница 36: ...r and drain the water heater see Draining Refilling And Flushing section Replace the T P valve with a properly rated sized new one see Temperature Pressure Relief Valve for instructions on replacement...

Страница 37: ...uninterrupted from the faucet Important When operating a cold tank condensation can occur and drip on the burner This should not be confused with a tank leak DRAIN VALVE WASHER REPLACEMENT 1 Turn OFF...

Страница 38: ...pressurize the water tank 4 Connect a hose to the drain valve and terminate it to adequate drain or to the exterior of the building Open the drain valve and drain approximately 5 gallons of water from...

Страница 39: ...is located under the plastic plug and insulation G Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area H The temperature...

Страница 40: ...ansion Tank required for all closed systems 30 Sheet Metal Burner see Figure 3 Figure 4 see see also Figure 47 Figure 48 31 Gas Orifice see Figure 3 Figure 4 see also Figure 47 Figure 48 32 Gas Manifo...

Страница 41: ...Natural gas and Propane LP main burner with igniter assembly for 47k Btu hr models 35 36 34 33 32 31 40 39 38 30 Flare Nut Figure 48 Notes The orifice on Natural gas models has Right hand thread the...

Страница 42: ...ifice clogged 5 Defective thermopile 6 Insufficient combustion air 7 Gas control thermostat ECO switch open 8 Defective igniter or electrode 9 Low gas pressure 10 Incorrect gas 1 Bleed the air from th...

Страница 43: ...d water system thermal expansion 1 Use a pressure reducing valve and relief valve 2 Lower the thermostat setting 3 See Closed System Thermal Expansion THERMOSTAT FAILS TO SHUT OFF 1 Defective gas cont...

Страница 44: ...ly to the Pilot should be checked If the Pilot is visible and the Status Light does not blink after 90 seconds of continuous Pilot operation the Pilot flame may not be heating the thermopile sufficien...

Страница 45: ...ndition only appears if the gas control temperature knob has been turned off and the thermopile continued to produce electric power This condition can occur if the thermopile does not cool down as qui...

Страница 46: ...46 www hotwater com NOTES...

Страница 47: ...www hotwater com 47 NOTES...

Страница 48: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 644 9306 www hotwater com...

Отзывы: