background image

          www. 

   hotwater  .com 15

INSTALLING THE NEW WATER HEATER

 WATER PIPING INSTALLATION
Note:

 Water piping and vent piping occupy the space 

above the water heater. Plan the water piping to ensure 
it does not cause interference with the vent piping (see 
“Venting”).

• 

The system should be installed only with piping that is 
suitable for potable (drinkable) water such as copper, 
CPVC, or polybutylene. This water heater must not be 
installed using iron piping or PVC water piping.

• 

Use only pumps, valves, or 

fi

 ttings that are compatible 

with potable water.

• 

It is recommend that only full 

fl

 ow ball or gate valves 

are used in water piping installations. The use of valves 
that may cause excessive restriction to water 

fl

 ow is 

not recommended.

• 

Use only 95/5 tin-antimony or other equivalent solder. 
Any lead based solder must not be used.

• 

Piping that has been treated with chromates, boiler 
seal, or other chemicals must not be used.

• 

Chemicals that may contaminate the potable water 
supply must not be added to the piping system.

Piping, 

fi

 ttings, and valves should be installed according 

to the installation drawing (see Figure 9). If the indoor 
installation area is subject to freezing temperatures, the 
water piping must be protected by insulation.

Important:

 Heat must not be applied to the water 

fi

 ttings on 

the heater as they may contain nonmetallic parts. If solder 
connections are used, solder the pipe to the adapter before 
attaching the adapter to the hot and cold water 

fi

 ttings.

Important:

 Always use a good grade of joint compound 

and be certain that all 

fi

 ttings are drawn up tight.

1.  Install the water piping and 

fi

 ttings as shown in Figure 

9. Connect the cold water supply (3/4” NPT) to the cold 
water inlet 

fi

 tting. Connect the hot water supply (3/4” 

NPT) to the hot water outlet 

fi

 tting.

Important:

 These models may contain energy saving heat 

traps to minimize the migration of heat to the pipes. Do 
not remove the inserts within the heat traps.
2.  The installation of unions in both the hot and cold water 

supply lines is recommended for ease of removing the 
water heater for service or replacement.

3.  If installing the water heater in a closed water system, 

install an expansion tank in the cold water line as 
speci

fi

 ed under “Closed Water Systems” and “Thermal 

Expansion”.

4.  Install a shut-off valve in the cold water inlet line. It 

should be located close to the water heater and be 
easily accessible. Know the location of this valve and 
how to shut off the water to the heater.

5.  After piping has been properly connected to the water 

heater, remove the aerator at the nearest hot water 
faucet. Open the hot water faucet and allow the tank 
to completely 

fi

 ll with water. To purge the lines of 

any excess air, keep the hot water faucet open for 
3 minutes after a constant 

fl

 ow of water is obtained. 

Close the faucet, reinstall the aerator and check all 
connections for leaks. Repair as needed.

METAL 
DRAIN 
PAN

FLOOR
DRAIN

HOT WATER 

OUTLET

COLD 

WATER 

INLET

UNION

UNION

3/4” SWEAT 

FITTING

3/4” SWEAT 

FITTING

TEMPERATURE-
PRESSURE 
RELIEF VALVE

DISCHARGE PIPE
(DO NOT CAP 
OR PLUG)

 6 ”  MAX.
AIR GAP

DRAIN
VALVE

SHUT-OFF 

VALVE

SOME 

COMPONENTS 

NOT SHOWN 

FOR CLARITY.

EXPANSION 

TANK

Figure 9 

Figure 9 shows typical attachment of water piping to the 
water heater. The water heater is equipped with 3/4” NPT 
water connections.

  CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements 
or such conditions as high line pressure, among others, 
have installed devices such as pressure-reducing valves, 
check valves, and back 

fl

 ow preventers. Devices such 

as these cause the water system to be a closed system.

  THERMAL  EXPANSION

As water is heated, it expands (thermal expansion). In a 
closed system, the volume of water will increase when 
heated. As the volume of water increases, there will be a 
corresponding increase in water pressure due to thermal 
expansion. Thermal expansion can cause premature tank 
failure (leakage). This type of failure is not covered under 
the limited warranty. Thermal expansion can also cause 
intermittent temperature-pressure relief valve operation: 
water discharged from the valve due to excessive pressure 
build up. The temperature-pressure relief valve is not 
intended for the constant relief of thermal expansion. This 
condition is not covered under the limited warranty.

Содержание DIRECT VENTED GAS MODELS

Страница 1: ...IS REQUIRED DIRECT VENTED GAS MODELS NOT FOR USE IN MANUFACTURED MOBILE HOMES For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE D...

Страница 2: ...ly 24 Securing Vent Termination Assembly To The Exterior Wall 24 Vent Restricter Plate 24 Uncompressing The Corrugated Tubing 24 Vent Connection To The Water Heater 25 Offset Vent Arrangement 25 Insta...

Страница 3: ...ects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects...

Страница 4: ...n the vicinity of this water heater the vent termination hood or any other appliance Avoid all ignition sources if you smell gas Do not expose water heater control to excessive gas pressure Use only g...

Страница 5: ...water heater or the vent termina tion hood where flammable products will be stored or used Vapors from flammable liquids may explode and catch fire causing death or severe burns Do not use or store fl...

Страница 6: ...carefully If you don t follow safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURYAND OR PROPERTY DAMAGE This manual contains instructions for installati...

Страница 7: ...eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half...

Страница 8: ...SSACHUSETTS INSTALLATION REQUIREMENTS 1 CONNECT ELECTRONICALLY CONTROLLED TIMER TO AN ALL BRONZE PUMP PUMP MUST ACTIVATE EVERY 6 HOURS FOR 60 SECONDS TURN PUMP TIMER OFF BEFORE CLOSING PIPING LOOP SHU...

Страница 9: ...sembly 21 Rating Plate 22 Anode under cap 23 Hot Water Outlet Nipple or Optional Nipple Anode 24 Inlet Water Shut off Valve 25 Union water connection 26 Air Inlet Snorkel 27 Air Tower 28 Airbox 29 The...

Страница 10: ...nt parts and recommended delimer may be ordered through authorized servicers or distributors When ordering parts provide complete model and serial numbers see rating plate quantity and name of part de...

Страница 11: ...metal drain pan should be installed under the water heater Metal drain pans are available at your local hardware store Such a metal drain pan must have a clearance of at least 1 greater than any poin...

Страница 12: ...he full width and depth of the appliance by at least 3 in every direction or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this war...

Страница 13: ...taining a gas water heater the vent termination hood or other open flame or spark producing appliance Examples of such locations are garages storage and utility areas The water heater must be located...

Страница 14: ...d injury Feel water before bathing or showering Temperature limiting devices such as mixing must be installed when required by codes and to ensure safe temperatures at fixtures BURN HOT HOT DANGER Som...

Страница 15: ...g the water heater for service or replacement 3 If installing the water heater in a closed water system install an expansion tank in the cold water line as specified under Closed Water Systems and The...

Страница 16: ...plate For safe operation of the water heater the temperature pressure relief valve must not be removed from its designated opening nor plugged The T P valve must be installed directly into the fittin...

Страница 17: ...harge opening or hinder access to the manual relief lever Figure 10 Ensure a discharge pipe is installed into the T P valve discharge opening per the instructions in this manual 1 Locate the hot water...

Страница 18: ...must be compatible with potable water Toxic chemicals such as those used for boiler treatment shall not be introduced into the potable water used for space heating When the system requires water for...

Страница 19: ...ately insulated to reduce heat loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Combo Heating Systems requi...

Страница 20: ...he National Fuel Gas Code ANSI Z223 1 NFPA 54 and your gas supplier concerning pipe size There must be A readily accessible manual shut off valve in the gas supply line serving the water heater and A...

Страница 21: ...ay result in fire or explosion Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap sometimes call...

Страница 22: ...er appliance Minimum 12 in from soffit Minimum 9 in to a window or door that may be opened Minimum 18 in from outside corner 1 Permitted only if veranda porch deck or balcony is fully opened on a mini...

Страница 23: ...ANCE HOLE FOR VENT Cut a clearance hole approximately 7 in diameter through the exterior wall for the vent assembly The recommended height is 64 for 40 gal models 73 for 50 gal models and 74 for 50 ga...

Страница 24: ...be then insert the outer corrugated tube through the clearance hole from exterior wall Secure the trim plate to the exterior wall then secure the vent terminal to the exterior wall with 4 screw anchor...

Страница 25: ...tops SMOOTH EASY CURVE GEAR CLAMP CUTAWAY TO SHOW DETAILS RESTRICTER PLATE STOP Figure 24 Apply hi temp red silicone included around the collar on air manifold box Pull the outer corrugated pipe all t...

Страница 26: ...allation 5 1 1 17 MIN Figure 30 NOTES applies to Figure 28 thru Figure 30 1 In any installation the total of dimension A plus dimension B must not exceed 89 2 This heater can be installed with 0 clear...

Страница 27: ...to check all connections and fittings for possible gas leaks Vent Pipe System Evenly stretched out between water heater and vent termination hood Smooth bend with adequate support to prevent sagging...

Страница 28: ...e knob to the OFF position and call a qualified service technician or your gas supplier DANGER Hotter water increases the risk of scald injury Consult the instruction manual before changing the temper...

Страница 29: ...hown on the gas control valve thermostat are approximates The actual temperature of the heated water may vary Important Adjusting the thermostat past the 120 F mark on the temperature dial will increa...

Страница 30: ...or hot water including dishwashers washing machines and shower heads Excessive condensate may be noticed during the winter and early spring months when incoming water temperatures are at their lowest...

Страница 31: ...the system see Water Piping section Smelly water may be eliminated or reduced in some water heater models by replacing the anode s with one of less active material and then chlorinating the water heat...

Страница 32: ...risk or asphyxiation Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors Spray can propellants cleaning solvents refrigerator and air...

Страница 33: ...ing leaks Do not insert any sharp objects into the inlet or outlet connections Damage to the gas control valve thermostat may result Replacing The Gas Control Valve Thermostat To replace the gas contr...

Страница 34: ...screws securing the burner to the manifold see Figure 35 Important DO NOT remove the orifice 3 Remove the screw securing the pilot thermopile assembly to the pilot bracket and keep for reuse later se...

Страница 35: ...bustion chamber Important Do not operate the water heater if the door gasket does not create a seal between the manifold door and the combustion chamber 6 Reconnect the manifold tube 3 4 wrench and pi...

Страница 36: ...r and drain the water heater see Draining Refilling And Flushing section Replace the T P valve with a properly rated sized new one see Temperature Pressure Relief Valve for instructions on replacement...

Страница 37: ...uninterrupted from the faucet Important When operating a cold tank condensation can occur and drip on the burner This should not be confused with a tank leak DRAIN VALVE WASHER REPLACEMENT 1 Turn OFF...

Страница 38: ...pressurize the water tank 4 Connect a hose to the drain valve and terminate it to adequate drain or to the exterior of the building Open the drain valve and drain approximately 5 gallons of water from...

Страница 39: ...is located under the plastic plug and insulation G Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area H The temperature...

Страница 40: ...ansion Tank required for all closed systems 30 Sheet Metal Burner see Figure 3 Figure 4 see see also Figure 47 Figure 48 31 Gas Orifice see Figure 3 Figure 4 see also Figure 47 Figure 48 32 Gas Manifo...

Страница 41: ...Natural gas and Propane LP main burner with igniter assembly for 47k Btu hr models 35 36 34 33 32 31 40 39 38 30 Flare Nut Figure 48 Notes The orifice on Natural gas models has Right hand thread the...

Страница 42: ...ifice clogged 5 Defective thermopile 6 Insufficient combustion air 7 Gas control thermostat ECO switch open 8 Defective igniter or electrode 9 Low gas pressure 10 Incorrect gas 1 Bleed the air from th...

Страница 43: ...d water system thermal expansion 1 Use a pressure reducing valve and relief valve 2 Lower the thermostat setting 3 See Closed System Thermal Expansion THERMOSTAT FAILS TO SHUT OFF 1 Defective gas cont...

Страница 44: ...ly to the Pilot should be checked If the Pilot is visible and the Status Light does not blink after 90 seconds of continuous Pilot operation the Pilot flame may not be heating the thermopile sufficien...

Страница 45: ...ndition only appears if the gas control temperature knob has been turned off and the thermopile continued to produce electric power This condition can occur if the thermopile does not cool down as qui...

Страница 46: ...46 www hotwater com NOTES...

Страница 47: ...www hotwater com 47 NOTES...

Страница 48: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 644 9306 www hotwater com...

Отзывы: