background image

12

FIGURE 3 

WIRING DIAGRAMS

C-2 CIRCUIT 

FOR SINGLE 

ELEMENT HEATERS 

EQUIPPED WITH HIGH 

LIMIT CONTROL

A-8 CIRCUIT FOR DUAL ELEMENT HEATER

 

FACTORY WIRED

---------- 

FIELD WIRING

†   

WHITE FOR 120V & 277V 

Содержание BURKAY 102 Series

Страница 1: ...L ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS DEL 6 10 15 20 Series 102 DEL 30 40 50 Series 110 DEN 30 40 52 66...

Страница 2: ...ition to electrical testing skills when performing service ANSI Z223 1 2006 Sec 3 3 83 Qualified Agency Any individual firm corporation or company that either in person or through a representative is...

Страница 3: ...unding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater HYDROGEN GAS FLAMMABLE Hydrogen gas can be produced in a hot wate...

Страница 4: ...om National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 The Canadian Electrical Code is available from the Canadian StandardsAssociation 8501 East Pleasant Valley Road Cleveland OH...

Страница 5: ...element operation 4 1 gal x KW of one element for simultaneous element operation 4 1 gal x 2 3 KW of both elements For other rises multiply element KW as previously explained by 410 and divide by temp...

Страница 6: ...6 APPROVALS MODEL AND RATING DEL 30 40 50 DEN 30 40 52 66 80 120 DEL 6 10 15 20 All models are listed by Underwriters Laboratories Inc...

Страница 7: ...E CANADIAN ELECTRICAL CODE FOR PROPER INSTALLATION INSTALL IN ACCORDANCE WITH ALL LOCAL CODES INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDE...

Страница 8: ...tions where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device...

Страница 9: ...ble and are to be set at a maximum of 125 degree F Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory s...

Страница 10: ...e location Shall not have any valve or other obstruction between the relief valve and the drain The temperature pressure relief valve must be manually operated at least once a year Caution should be t...

Страница 11: ...ingle element heater equipped with a high limit control single phase power input 2 Four wire A 8 circuit for dual element heater equipped with two high limit controls single phase or three phase power...

Страница 12: ...12 Figure 3 WIRING DIAGRAMS C 2 CIRCUIT FOR SINGLE ELEMENT HEATERS EQUIPPED WITH HIGH LIMIT CONTROL A 8 CIRCUIT FOR DUAL ELEMENT HEATER FACTORY WIRED FIELD WIRING WHITE FOR 120V 277V...

Страница 13: ...ness Also check connections on top and or sides of heater Repair water leaks and tighten electrical connections as necessary 3 Depress the red manual reset button on each Thermostat ECO combination co...

Страница 14: ...HI See Figure 5 The approximate equivalent temperatures for these three settings are LO 140 F 60 C MED 160 F 71 C and HI 181 F 83 C These thermostats are set from the factory at the LO 140 F 60 C set...

Страница 15: ...y the anode rod This does not affect water s taste or color The rod must be maintained to keep tank in operating condition Anode deterioration depends on water conductivity not necessarily water condi...

Страница 16: ...ating The sounds are normal however the tank bottom and elements should be cleaned See the Maintenance section of this manual WATER LEAKAGE IS SUSPECTED Refer to Leakage Checkpoint on the following pa...

Страница 17: ...ary to shut off electricity and drain tank to perform procedure Water leaks at the elements may be due to 1 Defective element which leaks at terminals or thru flange Replace element 2 Loose element ga...

Страница 18: ...improper gas supply line sizing gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Abuse misuse accident fi...

Страница 19: ...19 NOTES...

Страница 20: ...s will be shipped at prevailing prices and you will be billed accordingly The model number of your Water Heater will be found on the rating plated located above the lower access panel Be sure to provi...

Страница 21: ...nstruction Manual 322055 0 322055 0 322055 0 322055 0 10 Personnel Protector 9003914015 9003914015 9003914015 9003914015 11 Pipe Nipple 194130 194130 3 194130 3 194130 3 12 Plate Knockout 43293 1 4329...

Страница 22: ...2857015 9002857015 9002857015 9002857015 9002857015 9002857015 9002857015 7 Thermostat Bracket each 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 8...

Страница 23: ...4005 9002875005 TABLE 7 INCOLOY SHEATH ELEMENT AND WATTAGE CHART FOR SMR P72 K W ELEMENT WATTAGE 120 V 208 V 240 V 277 V 480 V PART NO PART NO PART NO PART NO PART NO 1 5 1500 W 9004279005 9004283005...

Страница 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2015 A O Smith All rights reserved...

Отзывы: