A.O. Smith BTR 120-400 Скачать руководство пользователя страница 3

2

Servicing should only be performed by a Qualified Service Technician

INTRODUCTION

This Service Handbook covers the water heater Model and Series numbers listed on the front cover only. 

The instructions and illustrations contained in this service handbook will provide you with troubleshooting 

procedures to verify proper operation and diagnose and repair common service problems.

QUALIFICATIONS

QUALIFIED INSTALLER OR SERVICE AGENCY

Installation and service of this water heater requires ability equivalent to that of a Qualified Agency (as defined 

by ANSI below) in the field involved. Installation skills such as plumbing, air supply, venting, gas supply and 

electrical supply are required in addition to electrical testing skills when performing service.

ANSI Z223.1 2006 Sec. 3.3.83:

 “Qualified Agency” - “Any individual, firm, corporation or company that either 

in person or through a representative is engaged in and is responsible for (a) the installation, testing or 

replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and 

equipment;  that  is  experienced  in  such  work;  that  is  familiar  with  all  precautions  required;  and  that  has 

complied with all the requirements of the authority having jurisdiction.”

SERVICE WARNING

If you are not qualified (as defined by ANSI above) and licensed or certified as required by the authority 

having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this 

service handbook. If you do not understand the instructions given in this service handbook do not attempt to 

perform any procedures outlined in this service handbook.

SERVICE REMINDER

When  performing  any  troubleshooting  step  outlined  in  this  service  handbook  always  consider  the  wiring 

and connectors between components. Perform a close visual inspection of all wiring and connectors to and 

from a given component before replacement. Ensure wires were stripped before being crimped in a wire 

connector, ensure wires are crimped tightly in their connectors, ensure connection pins in sockets and plugs 

are not damaged or worn, ensure plugs and sockets are mating properly and providing good contact.
Failure to perform this critical step or failing to perform this step thoroughly often results in needless down 

time, unnecessary parts replacement, and customer dissatisfaction.

TOOLS RECOMMENDED

• 

Instruction Manual that came with the water heater.

• 

All tools common to installation and service of commercial water heaters such as hand tools, screwdrivers, 

pipe wrenches etc.

• 

Hex (Allen) wrench sizes: 5/32”, 1/8”, 1/4” and 5/16"

• 

Digital manometer: Range -20.00 to +20.00" W.C. Resolution - 0.01" W.C. Required to test supply gas 

pressure.

• 

Digital Multi Meter; capable of measuring:

• 

AC/DC Voltage.

• 

Ohms.

• 

DC micro amps (μA).

Содержание BTR 120-400

Страница 1: ...6 100277701_2000536453_Rev A 500 Tennessee Waltz Parkway Ashland City TN 37015 FOR MODELS BTR 120 thru 400 A Series 118 119 INSTALLATION CONSIDERATIONS PRE SERVICE CHECKS CONSTRUCTION OPERATION SERVIC...

Страница 2: ...ATION FLOW CHART 13 FAULT AND WARNING CODES 14 Ignition Module 14 Flue Damper 14 Diagnostics Codes Ignition Module BTR 118 119 Series 15 TROUBLESHOOTING CHECKLIST 17 GENERAL SERVICE CHART 18 FAULT AND...

Страница 3: ...ied as defined by ANSI above and licensed or certified as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this servic...

Страница 4: ...al expansion can cause premature tank failure leakage This type of failure is not covered under the limited warranty Thermal expansion can also cause intermittent Temperature Pressure Relief Valve ope...

Страница 5: ...he National Fuel Gas Code ANSI Z223 1 and with the Category I Venting Tables If any part of the vent system is exposed to ambient temperatures below 40 F it must be insulated to prevent condensation D...

Страница 6: ...ith power vent kits for sidewall venting A O Smith offers power vent kits for use on installations with a maximum of 100 equivalent feet of vent piping The power vent kits also use type B vent materia...

Страница 7: ...W C for natural gas and 11 0 W C for propane gas The minimum supply pressure is measured while gas is flowing dynamic pressure The supply pressure should never fall below 4 5 W C for natural gas and...

Страница 8: ...as lines or emergency malfunction of the supply system the gas valve must be checked for safe operation Make sure that the outside vents on the supply regulators and the safety vent valves are protect...

Страница 9: ...eak test before placing the water heater in operation Disconnect gas piping and main gas shutoff valve before leak testing Install sediment trap in accordance with NFPA 54 Use joint compound or Teflon...

Страница 10: ...its are equipped with an automatic flue damper that reduces heat loss during the OFF cycles The automatic flue damper drive assembly is a field replaceable part and may be obtained by contacting A O S...

Страница 11: ...witch must be in the ON position to perform ohm continuity tests ON OFF switch replaced the gas cock on this new valve design GAS PRESSURE SPECIFICATIONS MODELS NATURAL BTR 120 400 PROPANE BTR 120 400...

Страница 12: ...tic controls would allow the gas control valve to remain open causing water temperature to exceed the thermostat setting The water temperature would continue to rise until high limit switch operation...

Страница 13: ...g checklist should be examined to eliminate obvious problems from those requiring replacement or servicing Check that main manual gas shut off valve is fully open and that gas service has not been int...

Страница 14: ...13 Servicing should only be performed by a Qualified Service Technician SEQUENCE OF OPERATION FLOW CHART...

Страница 15: ...Condensation on outside of tank normal Rumbling Sediment accumulation on bottom of tank Drain a quantity of water through drain valve If rumbling persists call a qualified service agency Delime heate...

Страница 16: ...ANSION TANK FAULTY VALVE REPLACE RELIEF VALVE LARGE VOLUME WATER RELIEF FROM T P VALVE EXCESSIVE WATER TEMPERATURE CHECK WIRING REPLACE DUAL CONTROLLER FAULTY RELIEF VALVE REPLACE RELIEF VALVE PREMATU...

Страница 17: ...VAC is supplied to the heater Make sure the tank is full of water Make sure the gas is supplied to the unit EFFIKAL DAMPER The wiring colors from the damper PC Board are different colors than the wire...

Страница 18: ...r 3 Yellow White 24V Common 4 Black CONDITION Damper closed High Limit closed FLUE DAMPER Do not turn damper open manually or motor damage will result use the service switch All readings are taken fro...

Страница 19: ...customer to have automatic heat until a replacement damper can be installed C DAMPER ROTATES CONTINUOUSLY Change the entire damper assembly D DAMPER STICKS 1 Make sure no screws obstruct the damper b...

Страница 20: ...AC is not present Check Wiring Harness to Thermostat 24VAC present Damper Opens Continue to Step 3 CONDITION Damper rotates continuously STEP 3 TEST THE THREE AMP FUSE CONDITION Test via the terminals...

Страница 21: ...s lights are not visible on the thermostat 24VAC out of the thermostat via the Yellow wire to ground is not present No Pilot or Main burner flame present Error indication LED light on the Honeywell mo...

Страница 22: ...TEP 5 WIRE HARNESS TEST CONDITION Damper Open no 24VAC to module 24VAC terminal Test for 24 VAC between terminal 24V on the IID module and 24V GND IF THEN 24VAC is present This is correct Continue to...

Страница 23: ...OT VALVE CONDITION 24VAC to module no pilot Using a multimeter test for 24 VAC between terminal PV and 24 V GND on the IID during the 90 second trial for ignition IF THEN The meter does not read 24 VA...

Страница 24: ...k for spark at the pilot assembly Note The pilot burner mounts on the left side of the main burner IF THEN The igniter is not sparking during the 90 second trial for ignition Check for A 7 64 spark ga...

Страница 25: ...ignal becomes a DC current that the module can interpret The pilot hood must be properly grounded and the pilot flame must remain in contact with both surfaces for the flame proving signal to remain c...

Страница 26: ...EST CONDITION Pilot Flame Noted No Sparking No Main Burner Using a multimeter test for 24 VAC between terminal MV on the IID and 24V GND IF THEN 24 VAC is not present Replace the IID module Check the...

Страница 27: ...chnician STEP 10 MAIN BURNER TEST CONDITION Pilot flame Noted Main burner Check Visually check for main burner IF THEN The main burner ignites Sequence is complete The main burner does not ignite Chec...

Страница 28: ...27 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM BTR 118 119 SERIES...

Страница 29: ...28 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM BTR 118 119 SERIES CONTROLS...

Страница 30: ...29 Servicing should only be performed by a Qualified Service Technician NOTES...

Страница 31: ...additional information contact A O Smith Corporation 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2016 A O Smith Water Hea...

Отзывы: