Servicing should only be performed by a Qualified Service Technician
GENERAL SERVICE CHART
Condition
Cause
Solution
DAMPER OPENS NO POWER
TO IID MODULE
•
DAMPER NOT FULLY OPEN
•
REPLACE DAMPER.
•
DEFECTIVE PROTECTOR
SWITCH
•
REPLACE PC BOARD.
PILOT LIGHTS, SPARKS
CONTINUOUSLY
PILOT FLAME NOT PROVING
SEE FLAME RECTIFICATION - STEP
8.
HEATER WILL NOT IGNITE
NOT PROVING PILOT FLAME
EXISTENCE
INTERRUPT 120 VAC POWER.
•
CHECK GROUND WIRE
ATTACHMENT.
• CLEAN OR REPLACE PILOT
ASSEMBLY.
PILOT GAS NOT COMPLETELY
INTERRUPTED AT END OF
HEATING CYCLE
•
CHECK SUPPLY GAS
PRESSURE.
• REPLACE GAS VALVE.
WEEPING TEMPERATURE
AND PRESSURE RELIEF VALVE
•
THERMAL EXPANSION
ADD THERMAL EXPANSION TANK.
•
FAULTY VALVE
REPLACE RELIEF VALVE.
LARGE VOLUME WATER
RELIEF FROM T&P VALVE
• EXCESSIVE WATER
•
TEMPERATURE
CHECK WIRING REPLACE DUAL
CONTROLLER.
•
FAULTY RELIEF VALVE
REPLACE RELIEF VALVE.
PREMATURE TANK
LEAKAGE
CONDENSATION
• INCREASE STORED WATER
TEMPERATURE AND
CONFIRM PROPERLY SIZED
APPLICATION.
CONTAMINATED AIR
•
REMOVE CONTAMINANTS.
•
SUPPLY CLEAN COMBUSTION
AIR.
WATER HAMMER
•
ADD WATER HAMMER
ARRESTOR.
• REDUCE WATER PRESSURE.
•
REMOVE UNNECESSARY
CHECK VALVES.
THERMAL EXPANSION
ADD THERMAL EXPANSION TANK.
DEPLETED ANODES
SCHEDULE ANODE CHECKS -
REPLACE AS NEEDED.
DAMPER WILL NOT OPEN
BINDING SHAFT
SUPPORT VENTING
DAMPER MOTOR
•
REPLACE DAMPER.
NO SPARK AT PILOT -
DAMPER FULLY OPEN
DAMPER ASSEMBLY
SEE STEP 7. Services Switch may
bypass problem until replacement
part is received.
REPLACE DAMPER .
IID MODULE
REPLACE IID STEP 6.
SPARK CABLE
REPLACE CABLE STEP 7.