background image

6

UNDESIRABLE OPENINGS,  CAUSING POOR COMBUSTION.
SOOTING MAY RESULT WITH AN INCREASED RISK OF
ASPHYXIATION.

THERMAL EXPANSION (CLOSED SYSTEM)

Thermal expansion occurs in any hot water system when system
water is heated or “recovered” during periods of non-use.

If the system is operated in an “open” condition such as being
connected directly to the city main, the volume of expanded water
generated during the recovery periods can be dissipated back
through the “open” connection to the city main so pressure cannot
increase.

However, once a back flow preventer is installed to isolate system
water from the public supply; or a pressure reducing valve is
installed to protect a water meter; or any device preventing flow
back into the cold water supply, the “open” condition becomes
“closed”.  During periods of temperature recovery and no usage,
water expands and the pressure increases until a relief valve
opens spilling hot water.

A relief valve opening on pressure will flow small amounts of water,
whereas relieving on temperature releases large amounts of water.
Consult the section under “High Water Temperature” to determine
the cause of the relief valve to open due to temperature.

Since the water is not compressible, some provision must be made
for THERMAL EXPANSION to protect the system from excessive
pressures.  Two options are:

1. Install an expansion tank properly and adequately sized for

the expanding volume of water.

2. Install a pressure relief valve in the cold water supply line having

a setting of at least 10lbs.  below the system working pressure,
located at or near a suitable drain.  This valve will open at
each heat cycle when there is no hot water demand on the
system.

Service problems or parts failure due to excessive pressure are
NOT covered under warranty.

The pressure and temperature relief valve supplied with the water
heater IS NOT considered to be protection against thermal
expansion.

VENTING

 WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES.  SUCH CONDITIONS
CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Heater must be protected from freezing downdrafts during
shutdown periods.

Remove all soot or other obstructions from chimney, which will
retard free draft.

Venting materials used for this category 1 appliance must be in
accordance with the National Fuel Gas Code and all state and
local requirements.

NOTE:  A NEGATIVE DRAFT MUST BE MAINTAINED IN VENT
PIPING (-0.02 to -0.06).

VENT CONNECTOR

The chimney vent connector diameter should be the same size
as the heater flue outlet, see table 1.  A minimum rise of 1/4” per
foot of horizontal connector length must be maintained between
the heater and chimney opening, fig. 2.  The connector length
should be kept as short as possible.

TABLE 1

     BTP/BTPD/BTPN/COF/COBT

FLUE OUTLET

INPUT (KBTUh)

 (INCHES)

140, 199

5

255, 270, 300

6

400

7

540, 600

8

720, 800, 1000

10

1250, 1500

12

1750, 2000

14

2250, 2500

16

BAROMETRIC DRAFT CONTROL ASSEMBLY

A double-acting barometric draft control assembly is provided with
each unit. This assembly must be attached to the heater as shown
in figure 2.  The direction in which the outlet to the draft control
assembly faces is arbitrary.  This assembly must be fitted to the
jacket cover such that it is plumb and level to the ground. Fasten
the draft control assembly to the top cover using sheet metal
screws at three locations, or more, as required.

Refer to the instructions provided with the barometric damper for
complete installation requirements.

Dampers or other obstructions must not be installed between the
heater and the barometric draft control assembly.

Barometric draft control counterweights can be adjusted for
installation conditions by an authorized A.O. Smith Start-Up Agent.
Any readjustment must be by authorized A.O. Smith  Start-Up
agent.

       

PROPER DRAFT CONTROLLER AND

VENT PIPE INSTALLATION - FIGURE 2

VENT CONNECTION

Vent connections must be made to an adequate stack or chimney.
Refer to the National Fuel Gas Code or to the vent pipe
manufacturer’s gas vent and chimney sizing table to properly
design and size the venting system.  Refer to Table 2 for the vent
pipe size required for installation to the barometric draft control
assembly outlet.

Содержание BTP-140

Страница 1: ...tilate the room then call your gas supplier or service agent Keep area clear until a service agent has been called MODELS BTP 140 140 thru 600 2500 INCLUDING BTPD BTPN COF COBT COMMERCIAL GAS OIL AND...

Страница 2: ...s Association Labortories 55 Scarsdale Road Don Mills Ontario Canada M3B 2R3 TABLE OF CONTENTS This manual is supplemented by the power burner manual All information including start up and maintenance...

Страница 3: ...OW OF COMBUSTION AND VENTILATING AIR ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION LIQUID PETROLEUM MODELS Water heaters for propane or liquefied petroleum gas LPG ar...

Страница 4: ...rsion from American Insurance Association 85 John Street New York NY 11038 Note Some gas utility companies derate the heating value of the supplied gas at high elevations Your authorized A O Smith Sta...

Страница 5: ...T 18 Inches FRONT 18 Inches BACK 0 Inches Back 6 Inches TOP 5 Inches Top 12 Inches LEFT SIDE 0 Inches LEFT SIDE 6 Inches RIGHT SIDE 0 Inches RIGHT SIDE 6 Inches NOTE If a chimney connector is used the...

Страница 6: ...RECIRCULATION OF FLUE GASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts during shutdown periods Remove all soot or other obstruct...

Страница 7: ...LOCATED IN FREEZING AREAS DO NOT THREAD OR CAP THE END OF THIS LINE RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE DISCHARGE LINE SHALL BE INSTALLED TOALLOW COMPLET...

Страница 8: ...OM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOS...

Страница 9: ...9 TYPICAL WIRE DIAGRAM BTP 270 2 500 KBTUH COF 800 2 500 KBTUH COBT 400 2 500 KBTUH TYPICAL WIRE DIAGRAM BTP 140 255 KBTUH...

Страница 10: ...10 TYPICAL WIRE DIAGRAM COF 140 720 KBTUH TYPICAL WIRE DIAGRAM COBT 140 300 KBTUH...

Страница 11: ...te to ask the agent any questions which you may have regarding the units start up operation or maintenance A MAINTENANCE section is included at the rear of this manual Any service required should be p...

Страница 12: ...finished flushing 4 Turn on the heater electrical disconnect switch MAINTENANCE SCHEDULE Component Operation Interval Required Flushing Monthly Sediment Tank Removal Semi Annually Lime Scale UN LIME...

Страница 13: ...ined through your A O Smith dealer or distributor To clean heater through cleanout opening proceed as follows 1 Turn off water inlet valve the heater electrical disconnect switch and open drain valve...

Страница 14: ...FIGURE 3 To test gate for operation gently tap gate and observe DO NOT OIL The red solid fuel tabs supplied with the draft regulator must be removed See instructions supplied with Draft Regulator TROU...

Страница 15: ...et system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the water heater or plumbing system will be damaged When such...

Страница 16: ...ENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a...

Отзывы: