background image

41

(IE: relay coil) to this circuit. This will damage the CCB and is not 

covered under the limited warranty.

connecting an external supervisory control

The enable/disable circuit is accessed from the CCB’s J6 plug 

inside the CCB enclosure, see beginning on page 8 to locate the 

CCB enclosure. From the factory there is a short (black) jumper 

wire installed between pins 8 and 11 of the J6 plug, see Figure 

65 on page 67 to locate the J6 plug.
Install field wiring to the enable/disable circuit:
1.  Turn  off  power  at  the  water  heater’s  on/off  switch  and  the 

breaker that supplies power to the water heater.

2.  Locate the CCB enclosure.
3.  remove  the  screws  from  the  CCB  enclosure  cover  and 

carefully open the CCB enclosure. Note how strain relief for 

the wiring is provided between the cover and enclosure along 

one edge.

4.  Activate the enable/disable circuit; locate the S1 dipswitch on 

the CCB, see Figure 65 on page 67. 

•  Toggle S1 dipswitch #2 to the open position.
•  Toggle S1 dipswitch #3 to the open position.

5.  Locate the black jumper wire between pin 8 and 11 on the 

CCB J6 plug, see Figure 65 on page 67 and Figure 66 on page 

68.

6.  Cut the black jumper wire in the middle.
7.  Strip approximately 1/2 inch of insulation from the two ends 

of the black jumper wire.

8.  Using wire nuts connect two field supplied control wires to 

the two ends of the black jumper wire. Wrap electrical tape 

around the wire nut connections.

9.  Thread the control wires out of the CCB enclosure with the 

other wiring and carefully replace the CCB enclosure cover. 

Ensure all wiring is routed through the indented area provided 

for strain relief. Ensure no wiring is being pinched.

10. reinstall the CCB enclosure cover screws and tighten.
11. route  the  control  wires  inside  the  junction  box  on  the  top 

of the water heater, see beginning on page 8 to locate the 

junction box. Use an available knock-out to route the wires 

inside the junction box.

12. Install field supplied control wiring and conduit as required 

by  national  and  local  codes  between  the  water  heater’s 

junction box and the external supervisory control. Connect 

the wiring from the external control to the control wires inside 

the junction box using wire nuts and electrical tape.

13. Connect  the  control  wiring  to  a  set  of  dry  contacts  on  the 

external control. Follow the control manufacturers instructions 

for making connections.

14. restore power to the water heater.

note:

  Whenever  the  external  control  opens  the  set  of 

dry  contacts  used,  heating  operation  will  be  disabled. 

Whenever  the  external  control  closes  the  set  of  dry 

contacts  used,  heating  operation  will  be  enabled.  A 

diagonal line and circle appears over the thermometer icon 

on the control system’s display when heating operation is 

disabled. See the Status Icons descriptions in Table 11 on 

page 45.

note:

  Ensure  the  water  heater  is  protected  from  freezing 

temperatures  when  heating  operation  is  disabled.  Damage  to 

the water heater caused by freezing temperatures is not covered 

under the limited warranty.

electrical wiring

All  electrical  work  must  be  installed  in  accordance  with  the 

National  Electrical  Code,  ANSI/NFPA  70  or  the  Canadian 

Electrical Code, CSA C22.1 and local requirements.
When installed, the water heater must be electrically grounded 

in accordance with local codes or, in the absence of local codes, 

with the National Electrical Code, ANSI/NFPA 70 or the Canadian 

Electrical Code, CSA C22.1.
If any of the original wire as supplied with the water heater must 

be replaced, it must be replaced with 105°C rated wiring or its 

equivalent, except in the burner housing. In this case use 200°C 

rated wire must be used.

power supply connections

read the requirements for the Power Supply on page 14 before 

connecting power.

correct polarity:

The  water  heater’s  control  system  is  polarity  sensitive  and 

will lock out and disable heating operation if the polarity of the 

power  supply  is  reversed.  The  control  system  will  display  the 

“AC  reversed”  Fault  message  on  the  LCD. The  120  VAC  hot 

wire from the power supply must connect to the black wire in the 

junction box and the 120 VAC neutral wire must connect to the 

white wire in the junction box for correct polarity.
Power supply connections must be made as follows: 
1.  Ensure  the  power  supply  is  turned  off  at  the  breaker  or 

disconnect switch.

2.  remove the junction box cover. See beginning on page 8 for 

junction box location. 

3.  Connect the 120 VAC hot wire from the power supply to the 

black wire in the junction box on top of the water heater with a 

properly sized wire nut. Wrap electrical tape around the wire 

nut and wire end. See wiring diagrams Figure 66 on page 68 

and Figure 67 on page 69.

4.  Connect the 120 VAC neutral wire from the power supply to 

the white wire in the junction box. Wrap electrical tape around 

the wire nut and wire end. See wiring diagrams Figure 66 on 

page 68 and Figure 67 on page 69.

5.  Connect  the  ground  wire  from  the  power  supply  to  the 

grounding lug inside the junction box. See wiring diagrams 

Figure 66 on page 68 and Figure 67 on page 69.

6.  replace  the  junction  box  cover  when  connections  are 

complete.

note:

 Do not apply power to the water heater before installation 

is complete and the water heater is filled with water.

enaBle/disaBle circuit

The  water  heaters  covered  in  this  manual  are  equipped  with 

an  enable/disable  circuit  for  use  with  field  supplied  external 

supervisory  controls  such  as  time  clocks  or  building  Building 

management Systems. The enable/disable circuit may be used 

to disable heating operation during periods when the building is 

unoccupied or there is no demand for hot water.
To  use  the  enable/disable  circuit  it  must  first  be  activated  by 

configuring the S1 dipswitch on the water heater’s CCB (central 

control board), see Figure 65 on page 67. Field supplied wiring 

is then installed between the water heater’s CCB and a set of 

“dry contacts” (no voltage or load) on the field supplied external 

control. 

note:

 The water heater’s enable/disable circuit is a switching 

circuit only: Do not apply external voltage or connect any load 

Содержание BTH-120 through BTH-500

Страница 1: ...LLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury o...

Страница 2: ...g Diagram 68 BTH 199 250 Wiring Diagram 69 Circulation Pump Wiring Diagrams 70 Water Piping Diagrams 71 Limited Warranty 78 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Sa...

Страница 3: ...efects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defec...

Страница 4: ...re using any electrical appliance connected to the hot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow The...

Страница 5: ...ment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or ser...

Страница 6: ...ction Detailed installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiri...

Страница 7: ...HOT SURFACE IGNITER 120 000 150 000 Btu hr MODELS COMBUSTION BLOWER FLAME SENSOR MAIN BURNER radial design BLOWER FLANGE INTAKE AIR combustion air CONNECTION 3 INCH PVC HOT SURFACE IGNITER COMBUSTION...

Страница 8: ...p Views 3 2 4 5 6 8 10 12 11 2 13 14 16 1 17 15 9 7 FRONT 120 000 150 000 Btu hr MODELS TOP VIEW BTH 120 150 Components 1 Water Heater s 120 VAC on off switch 2 Powered anode rods The water heater s c...

Страница 9: ...ration on page 44 3 2 4 5 6 8 10 12 11 2 13 14 16 1 17 15 9 7 FRONT 199 000 250 000 Btu hr MODELS TOP VIEW BTH 199 250 Components 1 Water Heater s 120 VAC on off switch 2 Powered anode rods The water...

Страница 10: ...nch PVC drain connection See Figure 9 on page 17 and Condensate Drain Installation on page 38 Side Views 1 Cleanout access panel covers water heater cleanout opening 2 CCB enclosure see beginning on p...

Страница 11: ...C L E A N O U T T P V A L V E D R A IN V A L V E 45 35 64 1 1 2 NPT WATER OUTLET SUPPLY GAS CONNECTION VERTICAL FRONT INTAKE AIR 3 INCH PVC V E N T 3 I N C H P V C 35 22 68 45 18 45 C L E A N O U T T...

Страница 12: ...er heater in a new location observe the following critical points 1 The water heater must be located indoors 2 The water heater must not be located in an area where it will be subject to freezing temp...

Страница 13: ...ation on page 30 Hard Water Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect the dishwashers coffee urns water heaters water...

Страница 14: ...trical Wiring on page 41 for installation instructions Gas Supply Systems Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14 W C 1 2 PS...

Страница 15: ...he elderly and the physically or mentally disabled are at highest risk for scald injury Feel water before bathing or showering Temperature limiting devices such as mixing valves must be installed when...

Страница 16: ...zed temperature pressure relief valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death This water heater is provided with a...

Страница 17: ...n See Condensate Drain Installation on page 38 Combustible Material Storage Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition source...

Страница 18: ...rea through a design of louver or grille or screen is known it shall be used in calculating the size of opening required to provide the free area specified Where the louver and grille design and free...

Страница 19: ...regate input rating of all appliances installed in the enclosure When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum d...

Страница 20: ...the aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in...

Страница 21: ...inal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructio...

Страница 22: ...take air connection Tee fitting is oriented properly on BTH 199 250 models see page 23 for instructions 20 Carefully read the Venting Requirements on page 24 and then proceed to the Venting Installati...

Страница 23: ...e air Fernco coupling 6 Reconnect the Blocked Intake Air switch sensing tube making sure the sensing tube is securely connected at both ends and is not kinked INTAKE AIR CONNECTION PIPE 199 000 250 00...

Страница 24: ...to order Concentric Vent Termination Part Numbers 4 Concentric Termination 9006328005 Venting Requirements Approved Materials Approved vent and intake air pipe materials that may be used in the Unite...

Страница 25: ...h humidity The drain hose should be routed to an adequate floor drain separate from any other condensate drains See Figure 21 on page 26 Note Snow being pulled into the intake air piping and then melt...

Страница 26: ...pe to the exhaust elbow on the water heater 12 If installing 4 inch vent pipe transition to 3 inch pipe at the exhaust elbow on the water heater as shown in Figure 18 on page 25 The field installed 3...

Страница 27: ...nations must have a minimum separation of 24 61 cm measured on center line as shown in Figure 25 on page 28 In colder climates this separation should be increased to at least 48 inches 122 cm The bott...

Страница 28: ...CES 60 cm ABOVE ANY PARAPET VERTICAL WALL OR STRUCTURE WITHIN 10 FEET 3 m HORIZONTALLY VERTICAL TERMINATION S FLAT ROOF CLEARANCE INTAKE AIR AND OR VENT EXHAUST 24 INCHES 60 cm MINIMUM HEIGHT ABOVE IF...

Страница 29: ...diameter hole for 3 inch pipe or 5 inch 13 cm diameter hole for 4 inch pipe where the pipe s will pass through the wall Note Beware of concealed wiring and piping when cutting through the wall 8 Cut a...

Страница 30: ...the length of a concentric termination do not use couplings The use of couplings will restrict flow through the termination and may cause improper combustion The termination s intake air and vent pipe...

Страница 31: ...t cap onto the vent pipe Alternately a field supplied stainless steel screw may be used to secure the 2 components together when field disassembly is desired for cleaning A pilot hole must be drilled...

Страница 32: ...tions are maintained Ensure multiple terminations are arranged or grouped as required Note These clearances must be maintained to prevent the recirculation of vent exhaust gases to the intake air Clea...

Страница 33: ...learances on page 32 for detailed information on clearances and additional arrangement options Note When multiple concentric terminations are installed through a roof in the same location all terminat...

Страница 34: ...34 Venting Arrangements Power Vent Vertical Figure 40 Direct Vent Vertical Figure 42 Power Vent Horizontal Figure 41 Direct Vent Horizontal Figure 43...

Страница 35: ...g Arrangements Direct Vent Vertical Vent Horizontal Intake Figure 44 Direct Vent Vertical Concentric Figure 46 Direct Vent Horizontal Vent Vertical Intake Figure 45 Direct Vent Horizontal Concentric F...

Страница 36: ...other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 36 inches 91cm for appliances above 100 000 Btu...

Страница 37: ...ny other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30 kW 36 inches 91 cm for appliances above 100 00...

Страница 38: ...PVC cement and PVC primer 1 2 inch PVC pipe minimum length to equal the distance between the water heater and a suitable building drain 1 2 inch PVC fittings elbows and couplings necessary to install...

Страница 39: ...PE CAP SEDIMENT TRAP Figure 52 Ensure all gas pipe is clean on the inside before installation To trap any dirt or foreign material in the gas supply line a sediment trap must be installed as shown in...

Страница 40: ...e 5 Use a standard pipe wrench Stillson wrench as a back up on the first pipe nipple installed above when connecting other fittings and pipe in the supply gas line to prevent the 24 Volt Gas Valve on...

Страница 41: ...r caused by freezing temperatures is not covered under the limited warranty Electrical Wiring All electrical work must be installed in accordance with the National Electrical Code ANSI NFPA 70 or the...

Страница 42: ...g Machines on page 15 3 Temperature Pressure Relief Valve on page 16 4 Closed Systems and Thermal Expansion on page 15 5 For multiple water heater installations see Water Piping Diagrams beginning on...

Страница 43: ...on a rise in temperature The ECO is located inside the Upper Temperature Probe two red wires see pages 8 and 9 for location The ECO switch contacts will open when the water temperature reaches approxi...

Страница 44: ...storage tank Heating cycles and ignition are managed by the control system The ECO energy cut out flame sensor pressure switches and temperature probes are monitored by the control system The Combust...

Страница 45: ...See beginning on page 8 for Blower Prover Switch location The Hot Surface Igniter is being energized See Figure 2 on page 7 for Hot Surface Igniter location The igniter has been energized and the con...

Страница 46: ...s from the combustion chamber at the end of a heating cycle Fault The control system has detected a Fault condition Heating operation is disabled until the Fault condition is corrected Power to the wa...

Страница 47: ...ll control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen press the Operational Button under SELECT to enter the Temperatures menu If the...

Страница 48: ...obe Offset 0 F CHANGE BACK HELP Temperatures Bottom of Menu Differential 8 F Tank Temperature 120 F Upper Temperature 122 F Lower Temperature 118 F Heater Regulated to Tank Upper Probe Offset 0 F Lowe...

Страница 49: ...ulated time the control system water heater has been energized Burner On Time Total accumulated time the control system has been in the heating operating state burner run time Cycle Count Total accumu...

Страница 50: ...event will replace the oldest Press the Operational Button under VIEW to view details for each Fault or Alert message stored 1 Blocked Air Intake A7 51 mins ago 2 Blocked Exhaust A8 54 mins ago 3 Low...

Страница 51: ...is menu item Show Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons...

Страница 52: ...ly gas line tighten all supply gas line connections 4 Check for gas leaks see Gas Line Leak Testing on page 40 and repair any leaks found Initial Start Up Required Test Equipment Two U tube manometers...

Страница 53: ...up sequence is complete 4 Using the control system menus and UIM user interface module change the Operating Set Point to a setting higher than the current tank temperature displayed on the control sy...

Страница 54: ...ents and installation instructions are maintained Manifold Gas Pressure Adjustment Fire and Explosion Hazard Gas and carbon monoxide detectors are available Overfiring could result in fire or explosio...

Страница 55: ...n page 47 2 When the water heater has completed its shut down sequence and enters the standby mode turn the water heater s on off switch to the off position 3 Close the Main Gas Shutoff Valve see Figu...

Страница 56: ...fire or explosion Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and...

Страница 57: ...than air and will settle on the floor 2 Set the ON OFF switch on the control panel to the ON position 8 Set the ON OFF switch on the control panel to the ON position 1 Set the thermostat to lowest se...

Страница 58: ...re and the state of other system devices If the tank temperature drops below the Operating Set Point minus the Differential setting the control will automatically return to Step 2 and repeat the opera...

Страница 59: ...tem Igniter is energized for warm up period 24 Volt Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monitors the flame sensor Control System Locks Out...

Страница 60: ...disable circuit disabling heating operation See Enable Disable Circuit on page 41 The heating capacity of the water heater has been exceeded the water heater is unable to meet demand Operational Probl...

Страница 61: ...thening the time required to heat water to desired temperature Hot water piping leaks open faucets water heater drain valve leaking or open Sediment or lime scale accumulation may be affecting water h...

Страница 62: ...below the required minimum pressure see Table 3 on page 12 Supply gas is turned off at the Main Shutoff Valve Supply gas pressure is dropping when other gas fired appliances on a common supply gas li...

Страница 63: ...in the intake air piping system see Venting Requirements on page 24 Intake air screen was not removed prior to connecting the intake air piping to the water heater and is clogged blocked with debris...

Страница 64: ...et the water run until the water is no longer hot Then close the hot water faucet 4 Connect a hose to the drain valve and terminate it to an adequate drain Maintenance General Keep water heater area c...

Страница 65: ...water heater drain valve to flush the storage tank 7 Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean 8 Close the water heater drain valve when fl...

Страница 66: ...pped with a powered anode system The anode rods 2 are of a permanent design and do not need replacing unless damaged Inspection and cleaning should be performed once a year Note Follow the instruction...

Страница 67: ...numbers 1 4 On the other side of the dipswitch is the word OPEN The dipswitches are rocker type switches if one side of the rocker is down the other side will be up Pressing a rocker down on the side...

Страница 68: ...ALVE B CENTRAL CONTROL BOARD C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER INSIDE CCB ENCLOSURE 50VA GROUND STRIP BURNER GROUND BURNER BOLT ON OFF SWITCH GROUND 120 VAC NEUTRAL 1...

Страница 69: ...STRIP BURNER GROUND BURNER BOLT ON OFF SWITCH GROUND 120 VAC NEUTRAL 120 VAC HOT LOW GAS PRESSURE SWITCH 1 BLACK 2 WHITE RED 1 BLACK 2 BLACK 1 BLACK 2 WHITE M USER INTERFACE MODULE I U 1 2 15 4 14 5...

Страница 70: ...UIT DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD S...

Страница 71: ...eview the following 1 See Mixing Valves on page 15 2 See Dishwashing Machines on page 15 3 See Temperature Pressure Relief Valve on page 16 ONE WATER HEATER SINGLE TEMPERATURE WITH BUILDING RECIRCULAT...

Страница 72: ...es on page 15 3 See Temperature Pressure Relief Valve on page 16 ONE WATER HEATER TWO TEMPERATURE WITH HIGH TEMPERAURE LOOP RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF...

Страница 73: ...alve on page 16 ONE WATER HEATER SINGLE TEMPERATURE WITH VERTICAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATI...

Страница 74: ...ONE WATER HEATER SINGLE TEMPERATURE WITH HORIZONTAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN...

Страница 75: ...llowing 1 See Mixing Valves on page 15 2 See Dishwashing Machines on page 15 3 See Temperature Pressure Relief Valve on page 16 TWO WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND...

Страница 76: ...Mixing Valves on page 15 2 See Dishwashing Machines on page 15 3 See Temperature Pressure Relief Valve on page 16 THREE WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE...

Страница 77: ...ves on page 15 2 See Dishwashing Machines on page 15 3 See Temperature Pressure Relief Valve on page 16 FOUR WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RE...

Страница 78: ...stalled at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warra...

Страница 79: ...79...

Страница 80: ...500 Tennessee Waltz Parkway Ashland City TN 37015 www hotwater com...

Отзывы: